Samsung AQ07P8GE Скачать руководство пользователя страница 1

AS12SGGE
AS09S8GE
SH12ZSG
AQ12SGGE
SH09ZS8
AQ09S8GE
SH07ZS8
AQ07S8GE

MODEL LINE-UP

1

SEPECIFICATIONS

7

OUTLINE & DIMENTION

11

PERFORMANCE DATA

17

INSTALLATION

23

FEATURES & OPERATION

41

DIAGRAM

57

TROUBLESHOOTING

73

CONTENTS

 DB98_08187A(1)<S_co  3/27/03 2:20 PM  Page 1

Содержание AQ07P8GE

Страница 1: ...AS09S8GE SH12ZSG AQ12SGGE SH09ZS8 AQ09S8GE SH07ZS8 AQ07S8GE MODEL LINE UP 1 SEPECIFICATIONS 7 OUTLINE DIMENTION 11 PERFORMANCE DATA 17 INSTALLATION 23 FEATURES OPERATION 41 DIAGRAM 57 TROUBLESHOOTING 73 CONTENTS ...

Страница 2: ...Model Line Up 1 1 Model Identification 1 2 Model Line Up 1 ...

Страница 3: ......

Страница 4: ...R 8 PD3 9 PD3MR 0 P J Name V2 M R R T2 T Fashion F V3 C B B G G Used Q Used V Used A Interior I GE E KLIMAT Y Option Outdoor unit sash Active A Active MR B INV C C Specification MR D Active2 E G Mold G Sub_Set Set None Indoor I Outdoor X Set Initial Set A Indoor A Outdoor U Mode H P Q C O S Capacity Btu 30 HP Mark I A Q V 09 A 1 M E Model Name Model Code Model Identification 1 Wall Mounted Type Ai...

Страница 5: ...ducts Separated type S Capa Btu Function H P H C O C Tech Normal Z Tropical T INV R22 V R22 BLDC D Lower temperature model L R407c C R410a A R410a BLDC B S H 09 Z A 1 X Model Name Model Code Design of Grille type S S Standard A Smile B C C C V Lip D G Advanced Model P G Standard Model S G Standard Model K KL Grille Interior I Fashion F GE E KLIMAT Y Secondary specification division Model for Weste...

Страница 6: ...ter 1 4 12 3 4 34 3 8 38 5 8 58 Piping division Initial F Products Export RAC S Domestic RAC R PAC P Cassette B Common Duct D Sealing F DPM M F S 14 38 C N A Model Name Model Code Piping Parts Box Function Export H P H C O C H P H C O C Domestic Oil G Multi M Voltage type Export NONE Indoor N Domestic Outdoor X Version Basic A New1 B 01R Standard Z ...

Страница 7: ...SG AQ12SGGE 7K A STEEL COOLING ONLY HEAT PUMP B MOLD C STEEL D MOLD 9K 12K 7K 7K 7K 9K 9K 9K 12K 12K 12K US07SBGE US07PBGE US09SBGE US09PBGE US12PBGE US12SBGE US07S8GB US07S8GD US07S8GE US09S8GB US09S8GD US09S8GE US12SGGB US12SGGD US12SGGE UQ07SBGE UQ07PBGE UQ09SBGE UQ09PBGE UQ12SBGE SH07ZS8X UQ07S8GE SH07ZPGX UQ07P8GE SH09ZPGX UQ09P8GE SH09ZS8X UQ09S8GE SH12ZSGX UQ12SGGE Indoor Unit Outdoor Unit ...

Страница 8: ...Specifications 2 1 Heat Pump 2 2 Cooling Only 2 ...

Страница 9: ......

Страница 10: ...door unit Outdoor unit Wall mounting 3 5 3 8 1 9 7 9 24 8 6 24 40 50 40 50 2 97 3 25 1 220 240 50 1180 1170 5 3 5 1 96 8 99 7 32 0 250V 10 16A 890x285x179 695x530x280 35 0x11 2x7 0 27 4x20 9x11 0 8 5 33 0 ø6 35 x 5 ø12 7 x 5 ø18 x 2000 Rotary Cross flow Propeller steel steel 15 25 2ROW 12STEP 1ROW 20STEP CAPILLARY TUBE 600 820 RAC 12074 9622 Wall mounting 2 7 2 9 1 4 6 4 19 7 0 19 38 48 38 48 2 81...

Страница 11: ...ng test Condition Maximum operation Condition Wall mounting 12 500 1 9 7 9 24 40 50 2 97 1 220 240 50 1180 5 3 96 8 32 0 250V 10 16A 890x285x179 695x530x280 35 0x11 2x7 0 27 4x20 9x11 0 8 5 32 5 ø6 35 x 5 ø12 7 x 5 ø18 x 2000 Rotary Cross flow Propeller steel steel 15 25 2ROW 12STEP 1ROW 20STEP CAPILLARY TUBE 600 820 RAC 12074 9622 Wall mounting 9 200 1 4 6 4 19 38 48 2 81 1 220 240 50 960 4 4 94 ...

Страница 12: ...Outline Dimension 3 1 Indoor Unit 3 2 Outdoor Unit 3 ...

Страница 13: ......

Страница 14: ...IMENSION 3 3 1 Indoor Unit Indoor Unit C 60 19 275 252 100 158 60 45 275 252 90 165 A B Air in Front view Rear view Remote control Type A B C 7K 9K 795 258 179 12K 890 285 179 Air out Installation plate 22 45 115 7K 9K 12K ...

Страница 15: ...14 SAMSUNG OUTLINE DIMENSION 3 3 2 Outdoor Unit 506 506 252 525 230 11 20 252 238 485 658 11 20 50 740 55 7K 9K 12K A C series Outdoor Unit 457 11 20 475 254 242 660 7K 9K B D series ...

Страница 16: ...SAMSUNG 15 OUTLINE DIMENSION 3 Outdoor Unit Cont 12K B D series 489 11 20 530 300 280 695 55 ...

Страница 17: ...MEMO 16 SAMSUNG 16 SAMSUNG ...

Страница 18: ...Performance Data 4 1 Performance Data 4 2 Noise Level Measurement 4 ...

Страница 19: ......

Страница 20: ...SAMSUNG 19 PERFORMANCE DATA 4 4 1 Performance Data 4 1 1 Capacity Performance Data 7 000BTU 9 000BTU Cooling Heating Cooling Heating ...

Страница 21: ...20 SAMSUNG PERFORMANCE DATA 4 4 1 1 Capacity Cont 12 000BTU Cooling Heating Performance Data Cont ...

Страница 22: ...SAMSUNG 21 PERFORMANCE DATA 4 Performance Data Cont 4 1 2 Cooling Capacity Correction Factors ...

Страница 23: ...MEMO 22 SAMSUNG ...

Страница 24: ...allation 5 1 Selecting Area for Installation 5 2 Installation Diagram of Indoor Unit and Outdoor Unit 5 3 Performing Leak Tests 5 4 Placing the Indoor Unit in Position 5 5 Checking and Testing Oeprations 5 ...

Страница 25: ......

Страница 26: ...area from which hot or cool air is spread evenly in a room 5 Make sure that you install the indoor unit in an area away from TVs audio units cordless phones fluorescent lighting fixtures and other electrical appliances at least 1 meter 6 Make sure that you install the indoor unit in an area which provides easy pipe connection with the outdoor unit and easy drainage for condensed water 7 Make sure ...

Страница 27: ... outdoor unit in area easy to drain condensed water from the indoor unit 7 Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe 8 Make sure that you install the outdoor unit in an area which is large enough to accommodate the measurements shown in figure on the next page 5 1 3 Remote Control Unit 1 Make sure that y...

Страница 28: ...slightly A Indoor unit gas leak test check point Tape vinyl Piping Indoor unit B Drain hose installation Cut the piping hole sloped slightly Piping may be laid to the rear left right or down Wrap the refrigerant pipes and the drain hose up in the abgorbent pad and the vinyl thape Triply wind the pipes and hose to the end of the indoor unit with the absorbent pad make intervals of 20mm The designs ...

Страница 29: ...of the wooden uprights to be attached to the window frame 5 Attach the wooden upright to the window frame in a manner appropriate to the weight of the indoor unit 6 Using tapped screws attach the installation plate to the wooden upright as illustrated in the last figure opposite 60 19 275 252 100 158 30mm Installation plate Pipe hole Ø65mm Unit mm 7K 9K 60 45 275 252 90 165 12K 5 2 2 Purging the U...

Страница 30: ...end of the cable through the 65mm hole in the wall 7 Replace the connector cover carefully tightening the screw 8 Close the front grille 9 For further details on how to plug the other end of the assembly cable into the outdoor unit E E N1 1 N 1 1 N1 1 N1 N1 1 2 3 Indoor unit Outdoor unit 1 Extend the assembly cable if necessary 2 Open the front grille by pulling on the tabs on the lower right and ...

Страница 31: ...irections Keep a clearance of at least 5cm between the end of the hose and the ground 5cm less Do NOT place the end of the drain hose in a hollow 1 If necessary connect the 2 meter extension to the drain hose 2 If you are using the extension insulate the inside part of the extension drain hose with a shield 3 Pass the drain hose under the refrigerant piping taking care to keep the drain hose tight...

Страница 32: ...1 Cut the pipe using a pipe cutter 2 Remove burrs at the tip of the pipe cut 3 Insert a flare nut into the pipe and modify flare Outer diameter A mm ø6 35mm 1 3 ø9 52mm 1 8 ø12 7mm 2 0 90 D A Oblique Roughness Burr Pipe Reamer Unproper flaring Inclined Surface damaged Cracked Uneven thickness CAUTION Burrs not removed may result in leakage of gas ...

Страница 33: ...o the packed valve having a service port as shown at the figure 4 Open the valve of the low pressure side of manifold gauge counterclockwise 5 Purge the air from the system using vacuum pump for about 10 minutes Close the valve of the low pressure side of manifold gauge clockwise Make sure that pressure gauge show 0 1MPa 76cmHg after about 10minutes This procedure is very important in order to avo...

Страница 34: ...ide of packed valve to the open position 7 Mount the valve stem nuts and the service port cap to the valve and tighten them at the torque of 18N m with a torque wrench 8 Check for gas leakage At this time especially check for gas leakage from 3 way valve s stem nuts and from the service port cap B liquid Stem cap Valve stem A gas ...

Страница 35: ... the pressure indicated by the pressure gauge low pressure side Standard pressure is should be 4 5 5 5kg cm2 in a regular high operation mode 6 Open the refrigerant tank and fill with refrigerant until the rated pressure is reached It is recommended not to pour the refrigerant in too quickly but gradually while operating a pres sure valve 7 Stop operation of the air conditioner 8 Close the 3 way v...

Страница 36: ...aused by a lack of refrigerant Installation position difference between the indoor unit and the outdoor unit should not exceed over than B meters When the connection pipe is been extended longer than 5 meters it might need to change the diameter of the electrical wire to a larger size in order to keep a voltage drop for starting room air conditioner is not less than 85 of the rated voltage And the...

Страница 37: ...o close 2 Way Valve 3 Way Valve Relocation of the Air Conditioner Refer to this procedure when the unit is relocated 1 Carry out the pump down procedure refer to the details of pump down 2 Remove the power cord 3 Disconnect the assembly cable from the indoor and outdoor units 4 Remove the flare nut connecting the indoor unit and the pipe At this time cover the pipe of the indoor unit and the other...

Страница 38: ...the indoor unit to the installation plate you must check that there are no gas leaks Performing Leak Tests To check for gas leaks on the Then using a leak detector check the Indoor unit Flare nuts at the end of sections C and D Outdoor unit Valves on sections A and B C D B A The designs and shape are subject to change according to the model ...

Страница 39: ...insulating tape around the pipe assembly cable and drain hose 3 Place the resulting bundle carefully in the lower part of the indoor unit making sure that it does not jut out from the rear of the indoor unit 4 Hook the indoor unit up to the installation plate and move the unit to the right and left until you are sure that it is securely to place in 5 Finish wrapping insulating tape around the rest...

Страница 40: ...ss to detect any gas leakages Connection wiring Heat resistant insulation of the piping Drainage Earthing wire connection Correct operations follow the steps below 2 Press the On Off button 3 Press the button 4 Air flow direction Press the button and check that the air flow blades work properly Result The indicator lights on the indoor unit flash at half second intervals While the indoor unit open...

Страница 41: ...MEMO 40 SAMSUNG ...

Страница 42: ...Features Operation 6 1 The Feature of key in Remote Control 6 2 Details for Operation Property 6 3 Operating Recommendations 6 4 Temperature and Humidity Ranges 6 5 Pressure Graph 6 ...

Страница 43: ......

Страница 44: ... 30 minutes to 24 hours To cancel press the Set Cancel button Temp down button To decrease the temperature by the pressing the temperature button Temp up button To increase the temperature by the pressing the temperature button FUNCTION OF KEY Auto Mode Fan Only Cool Mode Heat Mode Dry Mode If you wish to save energy when using your air conditioner select the Energy saving mode with the Energy sav...

Страница 45: ...ime by deice condition 4 DRY MODE Has 3 states each determined by room temperature The unit operates in DRY mode Compressor ON OFF Time is controlled compulsorily can not set up the fan speed always breeze Protective function Low temperature release Prevention against freeze 5 TURBO MODE This mode is available in AUTO COOL HEAT DRY FAN MODE When this button is pressed at first the air conditioner ...

Страница 46: ...e On Timer enables you to switch on the air conditioner automatically after a given period of time You can set the period of time from 30 minutes to 24 hours OFF TIMER The Off Timer enables you to switch off the air conditioner automatically after a given period of time You can set the period of time from 30 minutes to 24 hours 11 SELF DIAGNOSIS 12 BUZZER SOUND Whenever the ON OFF button is presse...

Страница 47: ...lects the operation mode and setting temperature 1 In case of Heat pump model 1 In case that Room Temp 21 C T the unit is operated in the Cool Mode 1 In case that Room Temp 21 C T the unit is operated in the Heat Mode 1 T means that user is able to change setting temperature within 2 C 2 In case of Cooling only model 1 In case the Room Temp 25 C T the unit is operated Compressor 1 In case the Room...

Страница 48: ...ixed by setting the remote controller The setting temperature will be dropped by 1 C at the starting of operation and by 1 C one hour later The operation will stop after 6 hours 6 2 5 Turbo Operation Cooling or Heating Mode If turbo operation is selected during heating or cooling mode compressor is operated for 30minutes regardless of room temperature After 30minutes of turbo operation the unit wi...

Страница 49: ... heat exchanger Indoor fan speed below 28 C off 28 C below 34 C LL speed 34 C below 40 C L speed above 40 C setting speed When compressor is on 40 C 34 C 28 C 20 C Setting speed L Speed LL Speed OFF Compressor OFF OFF UL ON When compressor is off When compressor begins operating The temperature of indoor heat exchanger Indoor fan speed above 20 C UL speed below 20 C off after 10 minutes when compr...

Страница 50: ...changer temp is over 60 C outdoor compressor stops and Indoor fan speed is low After compressor and fan are off if indoor heat exchanger temp is below 50 C indoor fan and outdoor compressor and outdoor fan operate normally Indoor Heat Exchanger Temp 60 C offset 53 C offset 50 C offset Compressor Outdoor Fan Indoor Fan On On Time On Off Off Low Speed 3min Delay 2Sec On Setting Speed offset 0 1 2 3 ...

Страница 51: ...the temperature of indoor heat exchanger increase over 0 C during 6 minutes counting 6 minutes counter is cleared If the temperature of indoor heat exchanger maintains for a minute at 4 C during the 6 minutes counting switch off the compressor If the compressor is off by Low Temp Release 5 minutes release is impossible Operating Pattern Indoor Heat exchanger Temp C 5 C 0 C 1 C 6min COUNT ON 6min C...

Страница 52: ...r heat exchanger is below about 40 3 C when the compressor is on it is considered as defrost B condition C condition When the accumulating time of compressor ON is over 20 minutes D condition When the accumulating time of compressor ON is over 3Hr E condition When operating time of compressor without stopping is over 6 minutes F condition If the compressor is off thermo off when the temperature of...

Страница 53: ...tails for Operation Property Cont Operation pattern Defrost Compressor Outdoor Fan 4Way Valve Indoor Fan On On On On 55sec 1min Defrost Time Off Off Off On On more than 58sec 2sec 55sec 1min Low Speed Thermo On Setting Speed Off Off On ...

Страница 54: ...hort time before you wish to use the room Frost When outside temperatures are low and humidity is high frost may form in the outdoor unit when heating with your air conditioner If this happens The heating operation is stopped The Deice mode is triggered automatically for about seven minutes The OPERATION indicator on the indoor unit lights up red No intervention is required from you after about se...

Страница 55: ...ome other malfunction may happen if the heat exchanger freezes High humidity levels Water may condense on and drip from the surface of the indoor unit if it is used for long periods Mode Outdoor Temperature Indoor Temperature Indoor Humidity Heating 0 C to 24 C approx 27 C or less Cooling 21 C to 43 C approx 18 C to 32 C approx 80 or less Drying 18 C to 43 C approx 18 C to 32 C approx If the heati...

Страница 56: ... air D B temp C Low pressure kg cm 2 G Low pressure kg cm 2 G Low pressure kg cm 2 G 20 25 30 35 40 45 32 4 24 0 30 6 22 5 28 8 21 0 27 0 19 0 24 0 17 0 21 5 15 0 6 5 5 5 4 5 3 5 Outdoor inlet air D B temp C Indoor inlet air D B temp C 20 25 30 35 40 45 32 4 24 0 30 6 22 5 28 8 21 0 27 0 19 0 24 0 17 0 21 5 15 0 6 5 5 5 4 5 3 5 Outdoor inlet air D B temp C Indoor inlet air D B temp C Pressure Grap...

Страница 57: ...MEMO 56 SAMSUNG ...

Страница 58: ...Diagram 7 1 Refrigerating Cycle Block Diagram 7 2 Circuit Diagram 7 ...

Страница 59: ......

Страница 60: ...AGRAM 7 7 1 Refrigerating Cycle Block Diagram 7 1 1 Cooling Only 7K 9K Refrigerating Cycle Block Diagram A C Series STANDARD 7000 9000BTU COOLING ONLY Valve 4 Way Valve Packed 3 8 Valve Packed 1 4 Air in Air in Capi ...

Страница 61: ...60 SAMSUNG DIAGRAM 7 Refrigerating Cycle Block Diagram Cont B D Series Valve 4 Way Valve Packed 3 8 Valve Packed 1 4 Air in Capi 9000 BTU 7000 BTU STANDARD 7000 9000BTU COOLING ONLY ...

Страница 62: ...SAMSUNG 61 DIAGRAM 7 Refrigerating Cycle Block Diagram Cont 12K A C Series STANDARD 12000BTU COOLING ONLY Valve 4 Way Valve Packed 1 2 Valve Packed 1 4 Air in Capi ...

Страница 63: ...62 SAMSUNG DIAGRAM 7 Refrigerating Cycle Block Diagram Cont B D Series STANDARD 12000BTU COOLING ONLY Valve 4 Way Valve Packed 1 2 Valve Packed 1 4 Air in Capi ...

Страница 64: ...SAMSUNG 63 DIAGRAM 7 Refrigerating Cycle Block Diagram Cont 7 1 2 Heat Pump 7K 9K A C Series STANDARD 7000 9000BTU HEAT PUMP Valve 4 Way Valve Packed 3 8 Valve Packed 1 4 Air in Capi 7000 9000 BTU ...

Страница 65: ...64 SAMSUNG DIAGRAM 7 Refrigerating Cycle Block Diagram Cont B D Series STANDARD 7000 9000BTU HEAT PUMP Valve 4 Way Valve Packed 3 8 Valve Packed 1 4 Air in Capi 9000 BTU 7000 BTU ...

Страница 66: ... 12K SAMSUNG 65 DIAGRAM 7 Refrigerating Cycle Block Diagram Cont A C Series STANDARD 12000BTU HEAT PUMP Valve 4 Way Valve Packed 1 2 Valve Packed 1 4 Air in C Capi Check Valve H Capi ...

Страница 67: ...MSUNG DIAGRAM 7 Refrigerating Cycle Block Diagram Cont B D Series STANDARD 12000BTU HEAT PUMP Valve 4 Way Valve Packed 1 2 12K BTU Valve Packed 3 8 7K 9K BTU Valve Packed 1 4 Air in C Capi H Capi Check Valve ...

Страница 68: ...SAMSUNG 67 1 DIAGRAM 7 7 2 Circuit Diagram 7 2 1 7K 9K Indoor Unit Circuit Diagram ...

Страница 69: ...7 2 2 12K Indoor Unit AC Part 68 SAMSUNG 7 DIAGRAM Circuit Diagram Cont ...

Страница 70: ...7 2 3 12K Indoor Unit DC Part SAMSUNG 69 1 DIAGRAM 7 Circuit Diagram Cont ...

Страница 71: ...IT 7K 9K 12K Cooling only model A C series B D series DIAGRAM OUTDOOR C1 MOTOR CAPACITOR FM FAN MOTOR S SPARK KILLER C2 COMP CAPACITOR O L P OVER LOAD PROTECTOR Code No DB98 09522A DIAGRAM OUTDOOR C1 MOTOR CAPACITOR C2 COMP CAPACITOR Code No DB68 01625A ...

Страница 72: ...pump model A C series B D series DIAGRAM OUTDOOR C1 MOTOR CAPACITOR FM FAN MOTOR S SPARK KILLER C2 COMP CAPACITOR O L P OVER LOAD PROTECTOR Code No DB68 02773A DIAGRAM OUTDOOR C1 MOTOR CAPACITOR FM FAN MOTOR C2 COMP CAPACITOR O L P OVER LOAD PROTECTOR Code No DB98 11762A ...

Страница 73: ...MEMO 72 SAMSUNG ...

Страница 74: ...ooting for Non Inverter Cooling Only 7K 9K 8 2 Troubleshooting for Non Inverter Heat Pump 7K 9K 8 3 Troubleshooting for Non Inverter Cooling Only 12K 8 4 Troubleshooting for Non Inverter Heat Pump 12K 8 5 Set up the Model Option 8 ...

Страница 75: ......

Страница 76: ... operation intermittently in DRY mode 5 Timer LED of the indoor unit lights up and the air conditioner does not operate 6 The compressor stops intermittently in a COOL mode or DRY mode and fan speed of the indoor unit decreases It indicates power is on The LED stops blinking if the operation ON OFF button on the remote control unit is pushed In happens after a delay of 3 minutes when the compresso...

Страница 77: ...ower cord and plug it after 5 seconds Press the Power Button on the remote control unit to operate the air conditioner Check whether two wires of power cord are connected correctly to the terminal block and control board Check whether the fuse on the control board is normal F701 3 15 A 250 V Check the output of SMPS on the control board Input power AC230 15 V IC02 Input DC 12 V IC02 output DC 5 V ...

Страница 78: ...hooting procedure After unplugging out the power cord should be reconnected within five seconds Does the OPERATION lamp blink Does the Solid State Relay SS71 work properly Is the supply voltage of the fan motor sufficient Test rod location PCB CN72 Condition Fan operate about AC 180V Normal voltage pin 3 and 5 YES YES YES NO NO NO Check as in the procedur NO power parts Microcomputer is out of ord...

Страница 79: ...econnected within five seconds Does the OPERATION lamp blink YES YES NO NO NO NO YES YES Outdoor unit is out of order Power relay is out of order Power relay should be replaced PCB should be checked Microcomputer is out of order PCB should be checked Room temperature sensor is out of order Check as in the procedure No Power parts Is the room sensor normal register 10 C 20 C 30 C 17 96kΩ 12 09kΩ 8 ...

Страница 80: ...tor Remove power cord and plug in again in approx 5 seconds Is STD lamp blinking Does operation start when swing button of the remote control unit pushed Voltage at pin 57 60 of micom ICO4 change Squarewave Volatge at pin 16 of IC06 ULN2003A and 10 12 of IC08 ULN2003A change Squarewave UP DOWN louver motor is faulty Driver IC06 08 ULN2003A is faulty Micom IC04 is faulty Normal Check as in the proc...

Страница 81: ...ation intermittently in a HEAT mode 9 The compressor stops intermittently in a COOL mode or DRY mode and fan speed of the indoor unit decreases It indicates power is on The LED stops blinking if the operation ON OFF button on the remote control unit is pushed In happens after a delay of 3 minutes when the compressor is reoperated The same phenomenon occurs when a power is on As a phenomenon that t...

Страница 82: ...ower cord and plug it after 5 seconds Press the Power Button on the remote control unit to operate the air conditioner Check whether two wires of power cord are connected correctly to the terminal block and control board Check whether the fuse on the control board is normal F701 3 15 A 250 V Check the output of SMPS on the control board Input power AC230 15 V IC02 Input DC 12 V IC02 output DC 5 V ...

Страница 83: ...fter unplugging out the power cord should be reconnected within five seconds Does the OPERATION lamp blink Does the Solid State Relay SS71 work properly Is the supply voltage of the fan motor sufficient Test rod location PCB CN72 Condition Fan operate about AC 180V Normal voltage pin 3 and 5 YES YES YES YES NO NO NO Check as in the procedur NO power parts PCB is out of order PCB should be replaced...

Страница 84: ...fter unplugging out the power cord should be reconnected within five seconds Does the OPERATION lamp blink YES NO YES NO NO NO YES YES Outdoor unit is out of order Power relay is out of order Power relay should be replaced PCB should be checked Microcomputer is out of order PCB should be checked Room temperature sensor is out of order Check as in the procedure No Power parts Is the room sensor nor...

Страница 85: ...wing button of the remote control unit pushed Voltage at pin 57 60 of micom ICO4 change Squarewave Volatge at pin 16 of IC06 ULN2003A and 10 12 of IC08 ULN2003A change Squarewave UP DOWN louver motor is faulty Driver IC06 08 ULN2003A is faulty Micom IC04 is faulty Normal Check as in the procedure No Power parts After training on the heating operation should start in five minutes Is the munber 38 o...

Страница 86: ...NDOOR FAN should operate 3 Fan speed setting is not allowed in AUTO or DRY mode 4 Compressor stops operation intermittently in DRY mode 5 The compressor stops intermittently in a COOL mode or DRY mode and fan speed of the indoor unit decreases It indicates power is on The LED stops blinking if the operation ON OFF button on the remote control unit is pushed In happens after a delay of 3 minutes wh...

Страница 87: ...rmal 4 5VDC 5 5VDC 2 Troubleshooting procedure Unplug the power cord and plug it after 5 seconds Press the Power Button on the remote control unit to operate the air conditioner Check whether two wires of power cord are connected correctly to the terminal block and control board Check whether the fuse on the control board is normal F701 3 15 A 250 V Check the output of SMPS on the control board In...

Страница 88: ...oting procedure After unplugging out the power cord should be reconnected within five seconds Does the OPERATION lamp blink Does the Solid State Relay SS71 work properly Is the supply voltage of the fan motor sufficient Test rod location PCB CN72 Condition Fan operate AC 180V Normal voltage pin3 pin5 YES YES YES NO NO NO Check as in the procedur NO power parts PCB is out of order Refer to replace ...

Страница 89: ...connected within five seconds Does the OPERATION lamp blink YES YES NO NO NO NO YES NO YES Outdoor unit is out of order Power relay is out of order Power relay should be replaced PCB should be checked Microcomputer is out of order Room temperature sensor is out of order PCB Should be checked Check as in the procedure No Power parts YES Is the room sensor normal register 10 C 20 C 30 C 17 96kΩ 12 0...

Страница 90: ... Squarewave Volatge at pin 16 of IC06 ULN2003A 10 12 of IC08 ULN2003A change Squarewave UP DOWN louver motor is faulty Driver IC06 08 ULN2003A is faulty Micom IC04 is faulty Normal Check as in the procedure No Power parts YES YES YES NO NO NO NO YES In the mode When there is no cool air current Check this first 1 Is the set temperature of Remote Control lower than room temperature in Cool mode 2 I...

Страница 91: ... intermittently in a HEAT mode 9 The compressor stops intermittently in a COOL mode or DRY mode and fan speed of the indoor unit decreases It indicates power is on The LED stops blinking if the operation ON OFF but ton on the remote control unit is pushed In happens after a delay of 3 minutes when the compressor is reoperated The same phenomenon occurs when a power is on As a phenomenon that the c...

Страница 92: ...mal 4 5VDC 5 5VDC 2 Troubleshooting procedure Unplug the power cord and plug it after 5 seconds Press the Power Button on the remote control unit to operate the air conditioner Check whether two wires of power cord are connected correctly to the terminal block and control board Check whether the fuse on the control board is normal F701 3 15 A 250 V Check the output of SMPS on the control board Inp...

Страница 93: ...lugging out the power cord should be reconnected within five seconds Does the OPERATION lamp blink Does the Solid State Relay SS71 work properly Is the supply voltage of the fan motor sufficient Test rod location PCB CN73 Condition Fan operate about AC 180V Normal voltage Pin 3 and Pin 5 YES YES YES YES NO NO NO Check as in the procedur NO power parts PCB is out of order Refer to replace PCB modul...

Страница 94: ...g procedure After unplugging out the power cord should be reconnected within five seconds Does the OPERATION lamp blink YES YES NO NO NO NO YES YES Outdoor unit is out of order Power relay is out of order Power relay should be replaced PCB should be checked Microcomputer is out of order PCB should be checked Room temperature sensor is out of order Check as in the procedure No Power parts Is the ro...

Страница 95: ...YES NO NO YES YES Does operation start when swing button of the remote control unit pushed Voltage at pin 57 60 of micom ICO4 change Squarewave Volatge at pin 16 of IC06 ULN2003A and 10 12 of IC08 ULN2003A change Squarewave UP DOWN louver motor is faulty Driver IC06 08 ULN2003A or IC06 is faulty Micom IC04 is faulty Normal Check as in the procedure No Power parts After training on the heating oper...

Страница 96: ...ntil the correct letter appears 1st If the first stage number appears on the display proceed to the second stage 2nd Every time the and button and each continue to appear 3rd Whenever pressing the 1 2 button the number increases from 0 9 0123456789 and A b C d E F each time If the first number is it is correct otherwise press until appear When pressing the button appear on the display select one o...

Страница 97: ...rom the remote controller Second Re insert the battery into the remote controller Third Press ON OFF key with the direction of remote controller for set If the first number is it is correct otherwise press until appear When pressing the button appear on the display select one of them When pressing the button appear on the display select one of them When pressing the button appear on the display se...

Страница 98: ...SAMSUNG 97 1 TROUBLESHOOTING 8 Set up the Model Option Cont Table of the option code MODEL SH12ZSG SH09ZS8 SH07ZS8 OPTION CODE 066025 172362 027064 17221d 026064 1720Fb Non Inverter 7K 9K 12K ...

Страница 99: ...MEMO 98 SAMSUNG ...

Страница 100: ...MEMO SAMSUNG 99 ...

Страница 101: ...MEMO 100 SAMSUNG ...

Страница 102: ... Samsung Electronics Co Ltd Mar 2003 Printed in Korea Code No DB98 08187A 1 ELECTRONICS ...