ENGLISH-11
PR
EP
AR
AT
IO
N
Checking before use
Using outdoor unit
Take away any covers or barriers.
X
f
It may cause product failure and poor performance in cooling/heating by blocking air flow.
Checking the auxiliary power switch
Turn on the auxiliary power switch before turning on the air conditioner.
X
f
When the auxiliary power switch is off, the air conditioner will not turn on even if you press the
On/Off
button.
Auxiliary power switch
• Auxiliary power switch (MCCB, ELB) is not included in the package.
Purchase and install it separately.
• You must install the auxiliary power switch (MCCB, ELB) in the switch box of
the building and turn it off when you clean the air conditioner or if you're
not planning on using the air conditioner for long time.
• If you are to use the air conditioner for the first time in a long period of
time, turn on the auxiliary power switch (MCCB, ELB) 6 hours prior to the
operation (to protect the compressor).
NOTE
Operational temperature and humidity range
The table below indicates the temperature and humidity ranges the air
conditioner can be operated within. Refer to the table for efficient use.
Mode
Indoor temperature
Outdoor temperature
Indoor humidity
Cool
18 °C ~ 32 °C
-5 °C ~ 48 °C
Relative humidity 80 % or less
Dry
18 °C ~ 32 °C
-5 °C ~ 48 °C
-
Heat
Below 27 °C
-20 °C ~ 24 °C
-
X
f
If the air conditioner operates in cooling mode for long period of time in high humidity area, dew may be formed.
X
f
Extra heating load calculation is necessary when the air conditioner is going to be used for main heating source in
winter timer. In cold regions, we recommend to purchase the product designed for cold regions which has great heating
efficiency. (Please contact nearest service center for any inquiries.)
X
f
The standardized temperature for heating is 7˚C. If the outdoor temperature drops to 0˚C or below, the heating capacity
can be reduced depending on the temperature condition.
Operating precautions
X
f
Refrigerant used in air conditioner is non-toxic and non-flammable. However, when the air conditioner is installed in
small space, extra ventilation system is required in case of refrigerant leakage.
X
f
When using H/R model, indoor units connected to same outdoor unit cannot be operated in different operation modes.
Indoor units should all be in Cooling (Cool/Dry/Fan mode) or Heating (Heat mode).
PAC SUPER_AM096HNPDCH_IB_EN_DB68-04904A-00.indd 11
2014-09-18 오전 9:44:19