3. Disassembly and Reassembly
3-1 Necessary Tools
■
Refrigerant pipe installation
Refrigerant pipe work
∙ The length of refrigerant pipe should be as short as possible and the height difference between an indoor and outdoor unit should be
minimized.
∙ Piping work must be done within allowable piping length, height difference, and the allowable length after branching.
∙ The pressure of the R-410A is high. Use only certified refrigerant pipe and follow the installation method.
∙ After installing the pipes, calculate the total length of the pipe to check if additional refrigerant is needed. When you need to charge the
additional refrigerant, make sure to use R-410A refrigerant.
∙ Use clean refrigerant pipe and there shouldn’t be any harmful ion, oxide, dust, iron content or moisture inside pipe.
∙ Use tools and accessories that fit on R-410A only.
Tool
Installation process/purpose
Compatibility with conventional tool
Pipe cutter
Refrigerant pipe
installation
Pipe cutting
Compatible
Flaring tool
Pipe flaring
Refrigerant machine oil
Apply refrigerant oil
on flared part
Exclusive ether oil, ester oil, alkali benzene oil or synthetic oil
Torque wrench
Connect flare nut with pipe
Compatible
Pipe bender
Pipe bending
Nitrogen gas
Air tightness test
Prevent oxidation within
the pipe
Welder
Pipe welding
Manifold gage
Air tightness test
~ additional
refrigerant
charging
Vacuuming, charging
refrigerant and checking
operation
Need exclusive one to prevent mixture of R-22 refrigerant oil use
and also the measurement is not available due to high pressure.
Refrigerant charging hose
Need exclusive one since there is risk of refrigerant leakage or inflow
of impurities
Vacuum pump
Pipe drying
Compatible
(Use products which contain the check valve to prevent the oil
from flowing backward into the outdoor unit.)
Use the one that can be vacuumed up to -100.7kpa(5Torr).
Scale for refrigerant
charging
Refrigerant charging
Compatible
Gas leak detector
Gas leak test
Need exclusive one. (Ones used for R-134a is compatible)
Flare nut
Must use the flare nut equipped with the product.
Refrigerant leakage may occur when the conventional flare nut for R-22 is used.
Refrigerant pipe work
∙ The length of refrigerant pipe should be as short as possible and the height difference between an indoor and outdoor unit should be
minimized.
∙ Install the refrigerant pipe according to main pipe size of each outdoor unit capacity.
∙ When the pipe length (including elbow) between an outdoor unit and the farthest indoor unit exceeds 90m, you must increase the size of the
pope (main pipe) by one grade which connects betwen the outdoor unit to the first branch joint.
∙ For H/R model, When the pipe length (including elbow) between an outdoor unit and the farthest indoor unit exceeds 90m, you must increase
the size of the liquid pipe by one grade among the pipes(main pipe) which connects between the outdoor unit to the first branch joint.
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...