Test Operation
9-1-3 How to resolve NG items
1) Indoor unit's thermistors
∙
What to inspect: Indoor unit's thermistors (the temperature of the indoor air and the temperatures at the entrance and exit
of the heat exchanger on the indoor unit)
∙
Error code: None ("NG" is only indicated in the result report)
∙
How to determine error: Check the temperature difference between the thermistors on the indoor units before
the compressors are started.
∙
Perform inspection according to the steps shown below.
Operate all the indoor units in
fan mode for 10 min.
Is there
an indoor unit with a thermistor
that shows a deviation greater than 10
℃
compared to other
indoor units?
Change the device
used to the indoor air temp
(Wired remote control
→
Indoor unit)
* How to measure resistance Disconnect
the thermistor connectors from the PBA
and then measure the resistance
between the terminals of the connectors.
Take corrective measures.
Replace the thermistors.
Take corrective measures.
Is the device
used to read the indoor
air temperature for the indoor unit set to
the wired remote control?
Are the thermistor
connectors on the indoor unit properly
connected to the PBA?
Are the resistance
values* for the thermistors on
the indoor unit normal?
Are the thermistors
on the indoor unit attached to
the correct positions?
Replace the Hub PBA.
Perform Auto Trial Operation again.
■
Precautions
- If issues occur on multiple components at the same time, the inspection accuracy may degrade.
- If the device used to read the indoor temperature is set to the wired remote control, change the device to the indoor
unit's thermistors and then perform Auto Trial Operation.
Presence of an "NG" item may occur due to a temp difference according to the positions of the indoor unit and the wired remote control.
- Thermistors on indoor units where outdoor air is applied are excluded from inspection.
- To replace a component or inspect the PBA, be sure to cut off the power supply first. If inspection must be performed with the power
supply on, exercise extra care to prevent electric shock.
Temperature (
℃
)
Resistance (KΩ)
70
2.2
60
3.0
50
4.2
40
5.8
30
8.3
20
12.1
10
18.0
0
27.3
-10
43.0
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
9-1 Auto Trial Operation (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...