Air conditioner
Installation manual
đ७७७ĘĘߣ७k²७७७
࡛
Thank you for purchasing this Samsung air conditioner.
Before operating this unit, please read this manual carefully and retain it for future
reference.
Страница 1: ...Airconditioner Installation manual k Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference...
Страница 2: ...the indoor unit Step 6 Cutting and flaring the pipes Step 7 Connecting the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test Step 9 Insulating the refrigerant pipes Step10 In...
Страница 3: ...setheunitsifdamaged Ifproblemsoccur switch theunitoffanddisconnectitfromthepowersupply In orderto prevent electric shocks fires or injuries always stop the unit disable the protection switch and conta...
Страница 4: ...ys verify that all connections complywith the standards applicable to the installation of air conditioners Devices disconnected from the power supply should be completely disconnected in the condition...
Страница 5: ...stalling the indoor unit be sure to check whetherthe chosen location is well drained The indoor unit must be installed such that it is beyond public access and is not touchable by users Rigid wall wit...
Страница 6: ...ts 860 Ceiling opening dimension Ceiling Outlet 235 Space of suspension bolts 380 Ceiling opening dimension Model k k A 134 B 180 Liquid pipe connection 6 35 Gas pipe connection 12 7 Drain hose connec...
Страница 7: ...0 80 A B 500 1198 Ceiling 1150 Ceiling opening dimension 249 Space of suspension bolts 440 Ceiling opening dimension 1036 Space of suspension bolts Model Uk Uk Uk A 130 B 179 Liquid pipe connection 6...
Страница 8: ...on Ceiling opening dimension 1380 1410 500 289 470 Space of suspension bolts 1260 85 35 15 1200 85 A B Ceiling 450 148 34 50 Space of suspension bolts Model Uk Uk A 133 138 B 180 180 Liquid pipe conne...
Страница 9: ...ty is over 80 you must apply an extra10 mm thick polyethylene insulation or a similartype of insulation to the body of the indoor unit Cut away the part where pipes are pulled out forthe insulating wo...
Страница 10: ...age pipe connection the refrigerant pipe connection orto remove the unit if necessary 5 Hang the indoor unit to the suspension bolts between two nuts Screw the nuts to suspend the unit 1 2 2 6 Check t...
Страница 11: ...er 2 If you wish to shorten the pipes cut them with a pipe cutter ensuring that the cut edge remains at a 90 angle to the side of the pipe Referto the illustrations below for examples of edges cut cor...
Страница 12: ...on 4 Make sure that there are no cracks orwaves on the bent area 5 It would be necessary to double the insulation thickness 10 mm or more to prevent condensation even on the insulatorwhen if the insta...
Страница 13: ...rds 2 Wind insulating tape around the pipes and drain hose avoiding compressing the insulation too much 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoorunit 4 The...
Страница 14: ...ces and conditions below use the same insulation that is used for high humidity conditions Geological condition High humidity locations such as shorelines hot springs lake or riversides and ridges whe...
Страница 15: ...socket Drain hose Large seailng pad Drain pipe Be sure to bond the drain hose and the main pipe Drain hose PVC Tube Joint VP25 OD 32 mm ID 25 mm VP 20 Drain pipe OD 26mm ID 20mm CAUTION Check that th...
Страница 16: ...more than 1 100 slope Main drain pipe Full thread bolt hanger 1000 to 1500 mm 300 to 550 mm 200 mm or more Individual airvent Main airvent must be installed If 3 or more units are installed install th...
Страница 17: ...ter completing the drainage check turn the unit off and disconnect the power supply Reassemble the control box cover c Check whetherthe drain pump works correctly d Check whetherthe drainage is perfor...
Страница 18: ...245 IEC 57 CENELEC H05RN F or IEC 60245 IEC 66 CENELEC H07RN F Screws on terminal block must not be unscrewed with When installing the indoor unit in a computer room use the double shielded tape alumi...
Страница 19: ...unication M3 5 screw 11 13 7 5 9 0 18 13 8 Powersupply single phase MCCB ELB Min 198V Max 242V XA XA 30 mA 0 1 s Powercable Earth cable Communication cable 2 5 mm or more 2 5 mm 0 75 to1 5 mm Decide t...
Страница 20: ...he unbalanced power is exceeded over10 of supply rating the indoorunit is protected stopped and the errormode indicates Connectthepowercabletotheauxiliarycircuitbreaker Anallpoledisconnectionfromthepo...
Страница 21: ...oints and flip it over and compress anothertwo points in the same location The compression dimension should be 8 0 Compression dimension After compressing it pull both sides of the wire to make sure i...
Страница 22: ...es from the remote control and then insert them again b While holding down the High Temp and Low Temp buttons simultaneously insert the batteries into the remote control c Make sure that you are enter...
Страница 23: ...2 Press the Mode button Cool and On appearon the remote control display 3 Set the SEG4 and SEG5 values a Set the SEG4 value by pressing the Low Fan button repeatedly until the value you want to set ap...
Страница 24: ...remote control display SEG9 b Set the SEG10 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High Fa...
Страница 25: ...r SEG15 12 Press the Mode button Cool and Off appear on the remote control display 13 Set the SEG16 and SEG17 values a Set the SEG16 value by pressing the Low Fan button repeatedly until the value you...
Страница 26: ...e remote control display SEG21 b Set the SEG22 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High...
Страница 27: ...t the indoor unit by disconnecting and then reconnecting the power cable of the indoor unit or by pressing the RESET button on the outdoor unit b Remove the batteries from the remote control insert th...
Страница 28: ...set the Use of drain pump SEG8 option to 0 it is automatically set to 2 the drain pump is used with 3 minute delay If you set the Maximum filter usage time SEG18 option to a value otherthan 2 and 6 it...
Страница 29: ...g Disuse 0 Disuse 0 Disuse recessed installation 1 Use Cooling Heating Disuse 2 Disuse Heating Use 2 1 Use 1 High ceiling mode recessed installation 3 Use Heating Use 2 1 Use 4 Disuse Cooling Use 4 Di...
Страница 30: ...peration 5 5 Outputofcooling throughexternal airintake cooling ThermoOn 6 3 Window ON or OFF control 6 Outputofcooling throughexternal airintake cooling dehumidifying ThermoOn 6 Option SEG19 SEG20 SEG...
Страница 31: ...3 The fan is turned off when the hot water heater is turned on with cooling only indoor unit Cooling only indoor unit To use this option install the Mode Select switch MCM C200 on the outdoor unit and...
Страница 32: ...m 20 minutes although the indoor unit is turned off afterthe Cool mode is turned to the Heat mode Installation options forthe 05 series SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 5 Use of Auto Change Overfor HR...
Страница 33: ...hange Over forHR only 3 1 5 3 1 5 3 2 5 4 2 4 2 4 3 5 2 5 5 2 5 5 3 5 2 Setting the indoor unit for cooling only 6 3 6 3 6 4 7 3 5 7 3 5 7 4 5 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Function Page Whe...
Страница 34: ...ht between the target indoor unit and the indoor unit installed at the lowest place For example When the target indoor unit is installed 40 m higherthan the indoor unit installed at the lowest place s...
Страница 35: ...D B a Ts Set temperature forAuto mode Reference temperature for cooling Reference temperature for heating Reference temperature for change from heating to cooling Reference temperature for cooling Coo...
Страница 36: ...tails 0 D Option type 0 to F Tens position value 0 to 9 Units position value 0 to 9 New value 0 to F Example Changing the Buzzer control SEG17 option of the installation options to1 disuse Option SEG1...
Страница 37: ...tor connection Correct operation follow the steps below Afterfinishing the installation of the airconditioner you should explain the following to the user Referto appropriate pages in the User s Manua...
Страница 38: ...E154 X X X X 1 Error on outdoortemperature sensor Short or Open E221 X X X 2 Error on cond sensor E237 3 Error on discharge sensor E251 Other outdoor unit sensor errorthat is not on the above list uni...
Страница 39: ...sump down_1 prevetion control E413 13 Compressor down due to low pressure sensor prevention control_1 E410 14 Simultaneous opening of cooling heating MCU SOLvalve 1st detection E180 15 Simultaneous op...