![Samsung AM056FN2DEH Series Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/samsung/am056fn2deh-series/html/samsung/am056fn2deh-series/am056fn2deh-series_service-manual_4744774047.webp)
Product Specifications
Samsung Electronics
47
Indoor Unit (cont.)
■
Big Ceiling
Model
AM112JNCDKH/EU
AM140JNCDKH/EU
Power Supply
φ,V,Hz
1,220~240,50/60
1,220~240,50/60
Mode 1)
-
HP / HR
HP / HR
Performance
Capacity
Cooling 2)
kW
11.2
14.0
Heating 3)
kW
12.5
16.0
Power
Input Consumption (Cooling/Heating)
W
92/80
160/160
Running Current (Cooling/Heating)
A
0.94/0.83
1.45/1.45
Indoorunit refrigerant adding amount
Kg/EA
0.56
0.95
Noise Level
Actual Noise Pressure (High)
dB(A)
↓
49
52
Fan
Type
-
Sirocco, Φ168*3EA
Sirocco, Φ168*4EA
Motor
Model
-
SIC-70CW-F1153-6,
DL-12830SSBF
(DB31-00660A)
SIC-80CW-F1244-2,
DL-12830SSBK
(DB31-00661A)
Type
-
BLDC Feedback
BLDC Feedback
Output
W
153W
244W
Airflow Rate
Fan(H/M/L)
㎥
/min
29.3/23.9/18.5
36.4/30.8/26.0
Refrigerant
Type
-
R410a
R410a
Control Method
-
EDM EEV 4.0C
EDM EEV 4.0C
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
250V/5A
250V/5A
Piping
Connections
Liquid (Flare)
Φ,mm
9.52
9.52
Φinch
3/8
"
3/8
"
Gas (Flare)
Φ,mm
15.88
15.88
Φinch
5/8
"
5/8
"
Drain
Φ,mm
VP25 (OD25,ID 20)
VP25 (OD25,ID 20)
Φinch
-
-
Weight
Net Weight
kg
33.5
42.5
Shipping Weight
kg
39.5
48.5
Dimensions
Net Dimensions (W×H×D)
mm
1350*235*675
1650*235*675
inch
-
-
Shipping Dimensions (W×H×D)
mm
1439*758*321
1739*758*321
inch
-
-
Functions
Auto Restart
-
O
O
Auto Swing
-
O
O
Group/Individual Control
-
O
O
External Contact Control
-
O
O
Trouble Shooting by LED
-
O
O
Standard
Accessories
Installation Manual
-
O
O
Operation Manual
-
O
O
Pattern Sheet for Installation
-
O
O
Flexible Drain Hose
-
O
O
Filter / Safety Grille
-
Filter (Washable)
Filter (Washable)
Optional
Accessories
Wireless Remote Controller
-
AR-DH00
AR-DH00
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
External Contact Interface Module
-
MIM-B14
MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
- Indoor temperature : 27
℃
DB, 19
℃
WB - Outdoor temperature : 35
℃
DB, 24
℃
WB
*3) Norminal heating capacities are based on;
- Indoor temperature : 20
℃
DB, 15
℃
WB - Outdoor temperature : 7
℃
DB, 6
℃
WB
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Содержание AM056FN2DEH Series
Страница 526: ...PCB Diagram and Parts List 526 Samsung Electronics 5 1 4 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 540: ...PCB Diagram and Parts List 540 Samsung Electronics 5 1 11 Duct type HSP BLDC PCB AM112 128 140FNHDEH 1 2 3 4...
Страница 593: ...PCB Diagram and Parts List Samsung Electronics 593 OAP DUCT AM220 280 NEPEH EU Cont BLDC Driver PCB cont 6 5 4 3 2 1...
Страница 643: ...Wiring Diagram Samsung Electronics 643 AMSSSMNFDEHS This Document can not be used without Samsung s authorization...
Страница 654: ...654 Samsung Electronics 6 1 27 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 655: ...Samsung Electronics 655 6 1 28 OAP Duct AM140MNEPEH EU This Document can not be used without Samsung s authorization...
Страница 656: ...656 Samsung Electronics 6 1 29 OAP DUCT AM220 280 NEPEH EU This Document can not be used without Samsung s authorization...
Страница 657: ...Samsung Electronics 657 6 1 30 V AHU AMSSSJNZDCHS This Document can not be used without Samsung s authorization...
Страница 660: ...660 Samsung Electronics AM280JNPDKH TK AM280RNPDKH EU This Document can not be used without Samsung s authorization...