In
St
alla
tI
on
Base construction and installation
18
English
Installation precautions
Connecting the anchor bolt
CaUtIon
Plastic (rubber)
washer
• Tighten the rubber washer to
prevent the bolt connection
part of the DVM CHILLER from
corroding.
anchor specification
a
b
c
m
• Use the anchor bolts and nuts
that is zinc plated or made
of STS material. Regular
anchor bolts or nuts may get
damaged by corrosion.
Size
Diameter of
drill bit (a)
anchor
length (b)
Sleeve
length (c)
Insertion
depth
Fastening
torque
ø10
14 mm
75 mm 40 mm 50 mm 30 N·m
Connecting the pipe
Water inlet pipe
Water outlet pipe
f
If you install the DVM CHILLER on the rooftop,
check the strength and make sure to waterproof the
rooftop.
f
Construct draining pit around the supporting base
and pay attention to the drainage around the
product. (Condensation or defrost water may form
during product operation.)
f
If there's any possibility of small animals entering
into the product through pipe outlet, block the outlet.
DB68-05916A-09_IM_DVM Chiller Outdoor_EU_EN_.indd 18
2022-05-02 오전 8:59:58