EB 8389S EN
19
Statistical information
Settings > Positioner > Error control
−
Logging of int. solenoid valve: [Yes], No
−
Min. clearance new logging int. solenoid valve:
0 to 5000 s, [300 s]
Table 3:
Condensed state reading
Status message
TROVIS-VIEW 4/DTM
Positioner
Priority
Function check
1)
orange
Text e.g. tESting, tunE or
tESt
Maintenance alarm
red
Out of specification/invalid
process state
yellow
blinking
Maintenance demanded/
maintenance required
blue
No message, OK
green
3
Statistical information
The positioner records the
set point w, valve
position x, drive signal y
and
set point devi-
ation e
even while the process is running to
obtain information on the valve, actuator
and pneumatic air supply. The data com-
piled while the process is running are saved
and analyzed by the monitoring functions in
Statistical information. In addition, a back-
ground hysteresis test can detect any chang-
es in friction.
The monitoring functions in Statistical infor-
mation do not have any affect on the run-
ning process.
The measured data are analyzed after the
positioner has been in automatic mode or in
manual mode for an hour. However, the
analysis for the 'Cycle counter histogram'
and 'Trend of travel end position' start direct-
ly after the positioner changes to automatic
mode or manual mode.