EB 8389-1S EN
25
Data logger
3.2.4
Triggered by internal so
-
lenoid valve/forced
venting
This setting is only active when an internal
solenoid valve/forced venting is installed in
the positioner.
See 'Internal solenoid valve/
forced venting' reading. If this is not the
case, the Progress bar indicates 'Cannot start
data logger – trigger cannot be set'.
The measured values are included in the trig-
gered data logging when the solenoid valve
is triggered or the forced venting is activat-
ed.
1.
Diagnostics > Data logger
−
Function:
Triggered
2.
−
Triggered by:
Internal solenoid valve/
forced venting
−
Trigger lead time:
0.0 s to 100 x 'Sampling time', [20.0 s]
3.
−
Sampling time: 0.2 to 3600.0 s, [1.0 s]
4.
−
Start data logger
3.2.5
Triggered by set point or
internal solenoid valve/
forced venting
This setting is only active when an internal
solenoid valve/forced venting is installed in
the positioner. See 'Internal solenoid valve/
forced venting' reading. If this is not the
case, the Progress bar indicates 'Cannot start
data logger – trigger cannot be set'.
The measured values are included in the trig-
gered data logging when one of the condi-
tions defined in 'Triggered by internal sole
-
noid valve/forced venting“ or 'Triggered by
set point' are met.
1.
Diagnostics > Data logger
−
Function:
Triggered
−
Triggered by:
Set point or internal solenoid
valve/forced venting
−
Trigger value: 0.0 to 100.0 %, [99.0 %]
−
Trigger band: 0.0 to 100.0 %, [99.0 %]
−
Trigger lead time:
0.0 s to 100 x 'Sampling time', [1.0 s]
−
Trigger condition: [Decreasing signal/lower
band value undercut], Increasing signal/up-
per band value exceeded, Band exit, Band
entry
3.
−
Sampling time: 0.2 to 3600.0 s, [20.0 s]
4.
−
Start data logger