18
KH 5757 EN
Configuration list and customer settings
5
Configuration list and customer settings
Function block list
The function blocks have the following listed functions.
F = Function block
WE = Default setting
F
Function
WE Meaning
01 DHW tapping recognition
1
0: Continuous control
1: Flow rate sensor active
02
Flow rate sensor
1
0: Flow switch
1: Water flow sensor
03 Adaptation
1
0: Not active
1: Active (with water flow sensor)
04
Direction of action
0
0: >> (increasing/increasing)
1: <> (increasing/decreasing)
05 Current input
0
0: Not active (binary input)
1: Active
06
Function of current input
0
0: Actual value
1: Set point
07
Measuring range of cur
-
rent input
0
0: 0 to 20 mA
1: 4 to 20 mA
08
Function of binary input
0
0: Termination of maintaining heat exchanger at constant
temperature
1: Switchover between internal set points
09
Maintain heat exchanger
at constant temperature
0
0: Time adjustable
1: Continuous
10 Upper limit (GWH)
0
0: No limitation
1: Exceeding GWH causes switch-off
11 Lower limit (GWL)
0
0: No frost protection
1: Violation of GWL causes frost protection to start