6.4
Intermediate heating operation
This function is only available in systems Anl 2.x, 4.1 to 4.5 and 8.x. With the setting
CO4 -> F07 - 1, heating operation of the UP1 heating circuit is reactivated for a period of
10 minutes after 20 minutes of priority (heating deactivated during DHW heating). By setting
CO4 -> F07 - 0, storage tank charging is given unlimited priority over the heating operation
in the UP1 heating circuit.
Function
WE
Configuration
Intermediate heating
1
CO4 -> F07 - 1
6.5
Parallel pump operation
This funtion is only available in systems Anl 2.1 to 2.4, 4.1 to 4.5 and 8.x. With the setting
CO4 -> F06 - 1, the circulation pump UP1 remains switched on during DHW heating unless
certain operating situations occur. These situations include, for example, those when the cur-
rent flow temperature demand of the pump circuit is lower than the adjusted
Flow limit tem-
perature for parallel pump operation. In this case, the controller applies priority operation, if
necessary with intermediate heating. Once a parallel pump operation cycle has been acti-
vated and the time for
Stop parallel operation in case of deviation has elapsed, system devi-
ations greater than 5 °C cause the controller to suspend parallel operation for 10 minutes
and to apply priority operation. By setting
Stop parallel operation in case of deviation to 0
min. leads to a parallel operation once initiated remaining regardless of a deviation.
Function
WE
Configuration
Parallel pump operation
0
10 min
40 °C
CO4 -> F06 - 1
Stop parallel operation in case of deviation /
0 to 10 min
Flow limit temperature for parallel pump operation /
20 to 90 °C
6.6
6.6
Circulation pump operation during storage tank charging
With the setting CO4 -> F11 - 1, the circulation pump continues operation according to the
programmed time schedule even during storage tank charging.
With the setting CO4 -> F11 - 0, the circulation pump is switched off as soon as the storage
tank charging pump is activated. The circulation pump returns to operate according to time
schedule when the storage tank charging pump has been switched off again.
EB 5576 EN
67
Functions of the DHW circuit