13.2 Parameter lists
PA1: Boiler 1
(systems Anl 1 to 7)
PA2: Boiler 2
(systems Anl 4 to 7)
In the PA2 parameter level, “2” appears instead of “1” on the left of the display.
Display
Parameter designation
Range of values (default setting)
Maximum flow temperature KF1, 2
20 to 160 °C (90 °C)
Minimum return flow temperature RüF1, 2
20 to 120 °C
Minimum activation time for boiler K1, 2
0 to 90 min
This time must have elapsed before the boiler switched off.
Minimum deactivation time for boiler K1, 2
0 to 90 min
This time must have elapsed before the boiler switched on.
EB 5474 EN
93
Appendix