1.6.2 Entering public holidays
On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holi-
days may be entered.
Parameters
WE
Level / Range of values
Public holidays f. heating circuit 1
–
PA1 / 01.01 to 31.12
Public holidays f. heating circuit 2
–
PA2 / 01.01 to 31.12
Public holidays f. heating circuit 3
–
PA3 / 01.01 to 31.12
Note!
The programmed public holidays and vacations of any heating circuit (HK1, HK2 or HK3) ap-
ply with the setting Co4 -> Fb12 = ON ,
select
1, 2 or 3 also for the DHW heating.
Proceed as follows:
Switch to configuration and parameter level.
Display:
PA1
Select parameter level.
Open parameter level.
Select datapoint for public holidays.
Display shows:
Open data point for public holidays.
If applicable, select
– – – –
.
Activate editing mode for public holiday.
blinks.
Edit public holiday
Confirm public holiday.
To enter additional public holidays, re-select
– – – –
(between 31.12 and 01.01) and repeat the
steps in the fields highlighted in gray.
Exit the parameter level.
Return to the operating level.
16
EB 5179 EN
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Содержание TROVIS 5179
Страница 87: ...EB 5179 EN 87 Communication...
Страница 93: ...EB 5179 EN 93 System Anl 3 Option Type 5244 Type 5257 5 System Anl 4 Option Type 5244 Type 5257 5...
Страница 94: ...94 EB 5179 EN System Anl 5 Option Type 5244 Type 5257 5 System Anl 6 Option Type 5244 Type 5257 5...
Страница 95: ...EB 5179 EN 95 _ _ _ 3 1 2 System Anl 8 Option Type 5244 Type 5257 5 System Anl 7 Option Type 5244 Type 5257 5...
Страница 103: ...Fb Function WE Anl Comments Function block parameters Range of values default setting...