9-2
EB 9511 EN
Malfunctions
Table 9-2:
Troubleshooting
Error ID
Message
Possible causes and recommended action
103
Memory error (calibration)
The gateway has an internal device error.
Î
Contact SAMSON's After-sales Service.
104
Memory error (data)
105
No factory calibration
107
Internal data processing error
205
Temperature inside device below min.
limit
The temperature limit inside the device has fallen
below the adjusted min. limit.
Î
Check whether the heating functions proper-
ly and the heating control is switched on.
Î
Select lower temperature limit.
206
Temperature inside device above max.
limit
The temperature limit inside the device has ex
-
ceeded the adjusted max. limit.
Î
Check whether the heating functions proper-
ly and the heating control is switched on.
Î
Select a better location to mount the device,
if necessary.
301
Power supply unit not recognized
The current firmware of the device does not sup
-
port the supply voltage. A firmware update is
necessary.
Î
Contact SAMSON's After-sales Service.
302
Option not recognized
The current firmware of the device does not sup
-
port the option. A firmware update is necessary.
The option is defective.
Î
Contact SAMSON's After-sales Service.
Содержание 5007-2 Series
Страница 8: ...1 4 EB 9511 EN...
Страница 12: ...2 4 EB 9511 EN...
Страница 24: ...3 12 EB 9511 EN...
Страница 29: ...EB 9510 EN 5 3 Cover Option module Fig 5 1 Inserting option modules...
Страница 36: ...5 10 EB 9510 EN...
Страница 50: ...11 2 EB 9511 EN...
Страница 52: ...12 2 EB 9511 EN...
Страница 54: ...13 2 EB 9511 EN...
Страница 56: ...14 2 EB 9511 EN...
Страница 68: ...17 2 EB 9511 EN...
Страница 69: ......
Страница 70: ...4 EB 9511 EN...
Страница 71: ...EB 9511 EN 5...