Mounting and start-up
SAMSON's After-sales Service can provide
more detailed storage instructions on re
-
quest.
4.4 Preparation for installation
Proceed as follows:
Î
Check all connections for the valve, hy
-
draulic controller and control thermostat.
Î
Check all parts for damage.
Î
Check to make sure that the type desig
-
nation, pressure rating and temperature
range of the valve, hydraulic controller
and control thermostat match the plant
conditions (pressure rating of the pipe-
line, medium temperature etc.).
Î
Check any mounted thermometers to
make sure they function.
Tip
5
Mounting and start-up
Risk of overheating due to excessive
ambient temperatures or insufficient heat
dissipation when components are insulated.
−
Do not include the temperature regulator in
the insulation of the pipeline.
5.1
Assembling the valve,
hydraulic controller and
control thermostat
The Type 43-8/Type 43-8 N Temperature
Regulator consists of the Type 2432 Valve
(1), Type 2438 Hydraulic Controller (20)
and Type 2430 Control Thermostat (30).
The hydraulic controller and the control
thermostat can be attached to the valve body
either before or after the valve is installed in
the pipeline.
On installation, make sure that the tempera-
ture does not exceed the max. permissible
ambient temperature of 35 °C.
Install the plate heat exchanger in such a
way that the heating water flows vertically
between the plates.
Heat exchanger connections
For district heating supply (heating water)
and hot water (top connection),
for district heating return (heating water)
and cold water (bottom connection)
NOTICE
!
NOTICE
!