38
EB 2171 EN
Malfunctions
Table 8:
Troubleshooting
Malfunction
Possible reasons
Recommended action
Temperature at the
sensor does not
reach the set point.
Valve installed against the flow.
Î
Install the valve so that the direction of flow
matches the direction indicated by the arrow
on the body.
Strainer blocked.
Î
Clean strainer.
Regulator or K
VS
/C
V
coefficient too small
Î
Check the sizing.
Î
Change K
VS
/C
V
coefficient, if necessary or
install a different sized regulator.
Î
Contact SAMSON's After-sales Service.
A safety device (e.g. STL or STM) has been
triggered.
Î
Check plant. Unlock safety device (where
necessary).
Insufficient heating energy available
Î
Draw up an energy balance.
Foreign particles blocking the plug
Î
Remove foreign particles.
Î
Replace damaged parts.
Î
Contact SAMSON's After-sales Service.
Sensor installed in the wrong location.
Î
Change the mounting position.
Sensor installed incorrectly.
Î
Immerse the temperature sensor with its entire
immersion depth in the process medium.
Î
Avoid an installation site where idle times or
heat buildup can occur.
Jerky control
response
Increased friction, e.g. due to foreign par-
ticles between seat and plug.
Î
Remove foreign particles.
Î
Replace damaged parts.
Î
Contact SAMSON's After-sales Service.
Loud flow-induced
noise
High flow velocity, cavitation.
Î
Check the sizing.
Î
Install larger regulator, if necessary.
Leak between
control thermostat
and valve
Valve seal defective
Î
Replace defective plug.
Î
Contact SAMSON's After-sales Service.