manualshive.com logo in svg
background image

   
 
 
   

 
 

 

 

 

 

 

 

Clevertronics Clever-test

 

The Clevertronics Clever-test Lifelight (LLIFEM-PRO-SA-CT) can be programmed to perform  90 minute 
discharge tests at 6-month intervals. A manual test is initiated by pressing the test switch 3 times within a 
5s period (immediate discharge test). A 24 hour delayed test (to allow batteries to fully charge before a 
test)  can  be  initiated  by  pressing  the  test  switch  and  hold  for  10  seconds  (i.e.,  until  LED  Test  Switch 
indicator flashes rapidly). Refer Clever-test Operation Guide for more information. Once the test has been 
completed, maintenance personnel then view the Status Indicator of each fitting  to determine a pass or 
failure: 
 

SOLID GREEN

 (not flashing) 

NORMAL 

– The luminaire is in a normal state charging and awaiting 

next discharge test. 

SLOW YELLOW FLASH

 

(2s Yellow, 2s Off) 

TESTING 

– The luminaire is currently performing a test. 

VERY SLOW YELLOW & Green

 

(4s Yellow, 1s Green) 

RECENTLY PASSED 

– The luminaire has previously tested and 

passed. This indication remains for 5 days after the completion of the 
test and then changes to SOLID Green to indicate a normal state. 

FAST YELLOW & Green FLASH

 

(0.5s Yellow, 0.5s Green) 

FAILED LAST TEST 

– The luminaire has previously tested and failed 

to remain illuminated for the required duration. This indication will 
remain until the required maintenance work has been completed and 
the luminaire passes a subsequent discharge test. 

 

Zoneworks and DATA Monitored Options

 

Lifelights with part numbers 

LLIFEM-PRO-SA-ZW, LLIFEM-PRO-SA-DATA 

are fitted with Zoneworks 

communications modules (nodes).These fittings are monitored using either Powerline Carrier Technology 
that utilising the power cable to provide data communication or a dedicated data cable to/from data routers 
installed on a dedicated data trunk connected to a central Server (can also be connected via 
Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate testing and 
collate test data from each Lifelight. Zoneworks Lifelights can be commissioned by a single push of the test 
switch, or scanning of the supplied barcode. The LED Test Switch indicator provides a multifunction 
indication of the status of the Lifelight during testing and normal operation: 

State

 

LED Operation

 

Commissioned 

LED on Solid (Green) 

Un-commissioned 

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow) 

Emergency Light Test In Progress 

LED flashes at 3s On (Yellow) & 0.5s Off 

 
In the case of the DATA version a 2-

way “figure 8” cable and terminal block facilitates the connection to the 

DATA network via a multi-drop bus (daisy chain connection).    For further information of installation of a 
Zoneworks LW system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 
version)   
 

DALI EM Option

 

Lifelights  with  part  numbers  L

LIFEM-PRO-SA-DALI 

are  fitted  with  DALI  modules  (nodes)  that  facilitate 

connection and integration to 3

rd

 Party Lighting Control Systems.    Before installing the LLIFE-PRO-DALI 

please confirm that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.   
The  LLIFE-PRO-DALI  will  be  addressed  and configured  into  the  control  system  by  the  Lighting  Control 
System Commissioning Technicians and not Clevertronics.     

State

 

LED Operation

 

Commissioned/ Un-commissioned 

LED on Solid (Green) 

Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 
A 2-

way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way 

“structured wiring system” lead and plug facilitating the power and DALI connection.    DALI connections 
are marked as Da Da.   

 

MAXWELL SUB-ZERO REMOTE MAINTAINED 

 

Installation & Maintenance Supplement

 

Models:   

 

 

Testing Options:    xx= 

MAXWELL SUB-ZERO MAINTAINED 184190 

CT 

Clevertest 

 

 

 

 

 

ZW 

Zoneworks 

 

 

 

 

 

DATA 

Zoneworks DATA

 

 

 

 

 

 

DALI 

DALI 

Spare Parts: 

LLIFEM-PRO-SASAMEMIPRM-xx-FIT

 

1530230   

 

 

Battery, 3.3 Volt 5Ah Li-ion 

LLIFEM-PRO-SA-CKIT13V300C 

PCA: Lifelight Control-SA 300mA    CT10142Lx 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before 

installation, ensure that the electricity supply has been switched off and isolated. Installation must be 

carried out in accordance with the relevant Australian and International Standards. 

 

Sammode Lighting Australia Pty Ltd 

15 Industrial Avenue 
WACOL QLD 4076 
Phone: 61 (0) 7 3335 3504 
Fax: 61 (0) 7 3335 3522 

 
 
 
 

 

 

Designed in Australia to comply with the requirements 
of AS2293.3: 2005, AS/NZS CISPR15: 2011   

 

 

 

SAMMODE 