background image

 Indice de révision : G

11

6102

3.2.2.6.  Parameter P9: Fault Accept by External Trigger
This parameter is a switch to authorize the recovery from a fault by the external trigger, available only if
P5 = 0.

3.2.2.7.  Parameter P15: High Voltage Value Correction
This parameter can be used to adjust the displayed voltage on the front panel to correlate to the meas-
ured high voltage at the applicator tip. A small difference can exist between high voltage units because
of the accuracy of the resistors used. This difference should not /- 3 kV.

3.2.2.8.  Over-Current Programming Parameters MP19SP19TP19RP19 
The over-current programming evaluates the current draw while the controller is active. The GNM 100
has two over-current protection schemes. The first scheme is to regulate the voltage when the current
reaches its maximum value; this scheme is referred to as limitation and utilizes all of above-mentioned
parameters. In the second scheme if the current exceeds the maximum allowable value the controller is
faulted and the front panel displays “I overflow” and only utilizes the parameter SP19.
MP19: Current Management
This is a switch used to select which type of current management the user desires to use.

The front panel display shows which current management scheme is in use by Il for limitation and Io for
fault management. Il and Io are high voltage unit dependent and can be adjusted below their maximum
values in the user menu.

SP19: Minimum Current Return Threshold
This value is the minimum current return value that must be obtained before the current management
system is enabled.
This value is expressed in micrometers and the adjustment range depends on the characteristics of the
high voltage unit. Increments are in multiples of one or five micro amperes

TP19: Fault Delay 
This value is the maximum time during which the system accepts the return current above the value
defined in Io. This value is expressed in milliseconds (ms) and incremented in steps of 4 milliseconds.

RP19: Current Ramp Function This is a switch, which enables the maximum allowable current to be
lower during the initial voltage ramp.

The system creates an imaginary voltage ramp incremented by one unit per each cycle of the program
until the maximum high voltage unit voltage or set point is reached. During this ramp the maximum allow-
able current draw is adapted to the imaginary voltage ramp by the relation:
Allowable Current = Io * Imaginary Set Point / high voltage units Maximum Voltage 

MP19 = 0 

Current Management by Limitation

MP19 = 1

Current Management by Fault

SP19

Minimum Adjustment    

1 to 5 mA

SP19

Maximum Adjustment     

Io

TP19 

Minimum adjustment

4 ms 

TP19 

Maximum adjustment

996 ms

RP19 = 1

Enables the ramp programming

RP19 = 0

Disables the ramp programming

Содержание GNM 100-A

Страница 1: ...8 Merriman Road Livonia Michigan 48 150 Tel 734 261 5970 Fax 734 261 5971 www sames com GNM 100 A Automatic mode of operation This product is protected by French patents N 2724787 et 2724786 which hav...

Страница 2: ...logies is registered as a Training Center approved by the Ministry of Employment Trainings with the aim of getting the necessary know how to use and for the main tenance of your equipment can be organ...

Страница 3: ...lt screens 13 3 3 2 V limit trip I limit trip 14 3 3 3 Coherence trip 14 3 3 4 Fault tempeture 14 3 3 5 Fault CC 14 3 3 6 Fault reg freq 14 3 3 7 Fault supply 14 3 3 8 Starting up of the HV after a mi...

Страница 4: ...iding of cable with a gauge up or equal to 6 mm2 WARNING Customer is responsible the checking which local fire safety standards apply for his operation For a use in cabinet the room temperature must b...

Страница 5: ...e Number E4PTFS343 B PLC Cable 22 Gauge Minimum 0 34mm2 shielded 19 Pin Connector 30 Meters Maximum Length 100 feet Female Plug Reference Number E4PTFS406 C Atomizer Cable Cable no specifications 7 Pi...

Страница 6: ...ecognizes the high voltage unit the unit remains in the automatic operating mode If the high voltage unit is disconnected or the controller is unable to recognize the high voltage unit the controller...

Страница 7: ...Key 4 permits one to go to the next screen 3 2 1 2 Adjusting Current Set Point Current adjustment set point is adjusted by keys 2 and 3 Key 4 permits one to go to the next screen 3 2 1 3 Parameter P5...

Страница 8: ...e list again press key 5 WARNING An interruption in the power supply to the controller erase the list of faults 3 2 1 5 Display of Effective Voltage and Current when Trigger is Activated When the gene...

Страница 9: ...reference is called Hard Di Dt and is set at a value of 50mA s The second Di Dt control is referred to as the Di Dt soft and can be adjusted to the user s spe cific application MP3 Di Dt Soft Function...

Страница 10: ...t voltage P4 s adjustment is linear and in increments of 0 7 milliseconds from 0 to 6 3 milliseconds The response is linear 3 2 2 4 Parameter P6 Voltage Set Point Internal External This parameter is a...

Страница 11: ...in use by Il for limitation and Io for fault management Il and Io are high voltage unit dependent and can be adjusted below their maximum values in the user menu SP19 Minimum Current Return Threshold...

Страница 12: ...ment 1 to 24 mA s SP3 Di Dt inhibition limit 0 10 kV RP3 Di Dt ramp 0 1 1 P4 Set point ramp 0 to 9 P6 Internal external set point 0 1 0 P8 HV enabled upon start up 0 1 0 P9 Fault accepted by external...

Страница 13: ...tion for internal trigger see 3 2 2 4 page 10 3 3 1 Fault screens Major faults Minor faults Fault tempeture Excessive case temperature see 3 3 4 page 14 Fault UP high voltage unit not recognized Fault...

Страница 14: ...sensor which creates a fault if the internal temperature exceeds roughly 70 C 158 F 3 3 5 Fault CC A low voltage short circuit causes a fault 3 3 6 Fault reg freq The GNM is equipped with an automati...

Страница 15: ...rs WARNING see RT Nr 6169 for use with a high voltage unit UHT 153 4 2 1 GNM 100 A module 4 3 Connecting plug 12 pins A Connection to the high voltage unit A Connecting plug 12 pins B Connecting plug...

Страница 16: ...e used for low currents Example of a PLC cabling Cabling for HV ON signalling light N of pins Signal 1 earth 2 phase 1 output protected 3 phase 2 output protected 4 common to trigger image relay 5 tri...

Страница 17: ...ustment point of 16 mA and read the HV value on the GNM screen A simple calculation permits one to fine the corresponding point N of pins Signal 1 Earth 2 Not connected 3 Not connected 4 Input 4 20 mA...

Страница 18: ...ntrol of the Vm output The Vm scale is 0 5 V for 0 100 kV The minimum impedance of the measure equipment has to be 50 k 4 5 2 2 Control of the Im output The Im scale is 0 5 V for 0 500 A The minimum i...

Страница 19: ...follows 4 5 4 Using information relative to the faults The closed contact of the OK board relay signals that the board is under voltage and that there is no fault WARNING This relay is for passing lo...

Страница 20: ...Indice de r vision G 20 6102 Liaison wiring with an PLC Wiring of a HV fault signalling lamp 1 Inside GNM 2 PLC input 14 to 16 GNM case 1 Inside GNM 2 220 VAC oR 110 VAC 3 Fault 14 to 16 GNM case...

Страница 21: ...h key 4 the param eters of this new high voltage unit are automatically selected and all old adjust ments are lost User must confirm new type of high voltage unit 5 Initial menu high voltage unit mode...

Страница 22: ...i Dt soft programming disabled 14 Adjustment of parameter P3 15 Adjustment of parameter SP3 16 Adjustment of parameter RP3 17 Adjustment of parameter P4 18 Adjustment of parameter P6 19 Adjustment of...

Страница 23: ...P19 1 Current management by Fault MP19 0 Current management by Limitation 23 Adjustment of parameter SP19 24 Adjustment of parameter TP19 25 Adjustment of parameter RP19 26 Modify the calibrating menu...

Страница 24: ...2 GNM powered display and green LED on 3 No 4 Power on GNM 5 Yes 6 Turn the GNM off for a minute then on again 7 GNM power on display and green LED on 8 Replace the GNM 9 If an over voltage occurs the...

Страница 25: ...Problem with low voltage cable 3 Yes 4 Replace the low voltage cable 5 No 6 Check the connector s low voltage termi nals 7 Problem with the connector terminals 8 Repair the low voltage terminals 9 Rep...

Страница 26: ...ow voltage cable 3 Yes 4 Defective low voltage cable 5 No 6 Check the connector low voltage termi nals 7 Defective connector terminal 8 Repair replace the low voltage termi nals 9 Replace GNM 10 Has t...

Страница 27: ...orked correctly but current consumption has increased 4 Yes 5 Adjust Il at maximum value 6 Maintenance necessary for the HV sys tem the paint hose becomes conductive air arrival circuit 7 Remove the H...

Страница 28: ...y 7 Check HV cable connections if this is the case length HV contact sufficient quantity of dielectric grease black part of cable earthed 8 Problem solved 9 Adjust parameter P3 10 Apply dielectric gre...

Страница 29: ...e 4 No 5 Carry out same controls for excess of I or Di Dt 6 Yes 7 Check low voltage cable 8 Problem with low voltage cable 9 Replace repair the low voltage cable 10 Check the low voltage connections 1...

Страница 30: ...Description Qty Sold in units of 858224 GNM 100 A metal case 110 220V 1 1 Ref Part number Description Qty Sold in units of 1 E4PTFS316 Male plug 7 contacts 1 1 2 E4PTFS343 Male plug 12 contacts 1 1 3...

Отзывы: