19.13. FAULT INDICATION ON CONTROL PANEL
NC
No connection between the cable and control panel.
Check the cable and connections.
Sensor is broken
Sensor failure.
Check sensors’ connections, measure sensors’ resistance (should be 10kΩ at + 25 °C)
External fault signal
Fault signal (electric heater manual reset protection to 100 °C is active, contaminated filters, external signal if
connected ex.,: fire protection)
Note: If you noticed any of named fault indications, turn off the power supply, remove fault reason, switch power supply again.