that the system can be simultaneously controlled by remote control panel or Modbus commands. Controller detects if the device (remote control
panel or Modbus) is connected to the connection X12. When the remote control panel is connected to the connection X12 the controller recognizes
it and starts constant checking the connection with the remote control panel. If there is no communication for 10 seconds, the controller stops the
system and shows the NC error.
When the controller is connected Modbus device, the controller recognizes it after the first Modbus command. When the controller is connected
Modbus device, then within 10 seconds after the controller. After the last command a brake system.
19.11. MODBUS TYPE – RTU 15
RS485 connection X12 is used to connect Modbus;
(See. Flex technical manual II-6-6.2).
Meanings of X12 connections:
4 3 2 1
1 +24V; 2 485 B; 3 485 A; 4 GND
The controller also responds to command 11h (slave id) and returns a response EKR-KE / Ver.1.4 or similar. Slave device is connected to the
system. Table includes Modbus parameters of the controller.
Parameter
Possible values
Set value
Device address
1-247
1
Connection speed
19200
19200
Parity
EVEN
NONE
Stop bit
1
1
ModBus type – RTU, MB slave addres – 1.
Port settings: RS485, 19200bps, 1STOP, PARITY-NONE
Remote control don’t support MB protocol, not connect to MB line.
Data address from 0x00
Name
ModBus function R/W
Data
address
(dec)
Data
address
(hex)
Description
Value
0x....) Coils Read - 01h, Write – 05h, 0Fh ( Present value, Unsigned Word )
Fire alarm
Coils
R
1
0x01
Alarm from A1 input (A1)
1-active, 0-passive
Filter
Coils
R
2
0x02
Info from Filter input
1-active, 0-passive
Fan overheat Coils
R
3
0x03
Alarm from A4 input (A4)
1-active, 0-passive
LowPower
Coils
R
5
0x05
Low voltage alarm (A7)
1-active, 0-passive
T limit
Coils
R
8
0x08
Supply air temperature sensor alarm
1-active, 0-passive
Reset
Coils
W
18
0x12
System restart
Read =0
Overheat
Coils
R
44
0x2C
Alarm from A6 input (A6)
1-active, 0-passive
(1x....) Discrete Read – 02h ( Present value, Unsigned Word )
Tsupplay
Discrete
R
2
0x02
Supply air temperature sensor alarm
1-active, 0-passive
Twater
Discrete
R
4
0x04
Return water temperature sensor alarm
1-active, 0-passive
Toutdoor
Discrete
R
5
0x05
Outdoor air temperature sensor alarm
1-active, 0-passive
Fire alarm
Discrete
R
9
0x09
Alarm from A1 input (A1)
1-active, 0-passive
Coldspell (ex-
changer)
Discrete
R
10
0x0A
Tsupplytemp.lessthan(Tset-10’C)alarm (A2)
1-active, 0-passive
Fan overheat Discrete
R
12
0x0C
Alarm from A4 input (A4)
1-active, 0-passive
Sensors
Discrete
R
13
0x0D
Any sensor fail alarm
1-active, 0-passive
Water
Discrete
R
18
0x12
Critical return water temper. alarm (A5)
1-active, 0-passive
LowPower
Discrete
R
19
0x13
Low voltage alarm (A7)
1-active, 0-passive
Overheat
Discrete
R
22
0x16
Alarm from A6 input (A6)
1-active, 0-passive
Filter
Discrete
R
23
0x17
Info from Filter input
1-active, 0-passive
Supply
Discrete
R
24
0x18
Air supply valve output active
1-active, 0-passive
Fan speed 1 Discrete
R
25
0x19
Fan 1 speed output active
1-active, 0-passive
Fan speed 2 Discrete
R
26
0x1A
Fan 2 speed output active
1-active, 0-passive
Fan speed 3 Discrete
R
27
0x1B
Fan 3 speed output active
1-active, 0-passive
Water pump Discrete
R
28
0x1C
Water pump output active
1-active, 0-passive
Overheat
Discrete
R
30
0x1E
Tsupply temp. higher than 40 ‘C alarm (A6)
1-active, 0-passive
Alarm
Discrete
R
31
0x1F
Any alarms alarm
1-active, 0-passive
(3x....) Input Read - 04h ( Present value, Signed Word )