![Salda Smarty 2R VE Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/salda/smarty-2r-ve/smarty-2r-ve_user-and-service-technical-manual_3723642009.webp)
9
Smarty 2R VE / 2R VE plus
www.salda.lt
• The maintenance side can be changed for the ventilation unit, i.e. it can be mounted with the left ambient air inlet or the right ambient air inlet. That
can be implemented by switching over the back door and the front door. The default version of the ventilation unit is right.
Smarty 2R VER / Smarty 2R VER plus
Smarty 2R VEL / Smarty 2R VEL plus
• Rotor heat exchanger must be serviced once a year.
• Ensure that the gaps of the heat exchanger are clean, the brushes are not worn, the belt drive is not worn and the clamping nodes of the rotor heat
exchanger are tight.
• Rotor heat exchanger can be easily removed from the unit. The power cord of the motor of the heat exchanger is disconnected. The clamp of rotor
heat exchanger section is released and raised and the heat exchanger is removed.
• The heat exchanger is cleaned using the solution of warm water and non-corrosive toward aluminum alkaline agent or the air stream. It is not recom-
mended to apply direct stream of liquid as it can harm the device.
• While cleaning, protect the motor of heat exchanger from entry of moisture and fluids.
• After reinstalling the heat exchanger, fasten the heat exchanger section with the clamp. Connect the heat exchanger motor.
CAUTION: the heat exchanger can not be used when
the filters are removed!
Outdoor air
Supply air
Exhaust air
Extract air
Kitchen hood
Smarty 2R VE / Smarty 2R VE plus