13
Smarty 2R VE / 2R VE plus
www.salda.lt
NOTE
. Subject to technical modification
Smarty
2R VER / 2R VEL
2R VER plus / 2R VEL plus
Heat exchange
- phase/voltage
[f/VAC/Hz]
~1/230/50
~1/230/50
- power/current
[kW/A]
0,006/0,1
0,006/0,02
-thermal efficiency up to
75%
75%
Heater
- power/current
[kW/A]
0,6/2,61
0,6/2,61
Exhaust air fan
- phase/voltage
[f/VAC/Hz]
~1/230/50
~1/230/50
- power/current
[kW/A]
0,07/0,6
0,084/0,75
- speed
[min
-1
]
1380
3200
- protection class
IP44
IP54
- control imput
[VDC]
0-10
0-10
Supply air fan
- phase/voltage
[f/VAC/Hz]
~1/230/50
~1/230/50
- power/current
[kW/A]
0,07/0,6
0,084/0,75
- speed
[min
-1
]
1380
3200
- protection class
IP44
IP54
- control imput
[VDC]
0-10
0-10
Total
- power/current
[kW/A]
0,75/3,91
0,77/4,13
Automatic control integrated
+
+
Insulation of walls
[mm]
20
20
Weight
[kg]
36
36
Exhaust air filter
class class
M5
M5
width
[mm]
270
270
height
[mm]
86
85
depth
[mm]
46
173
model
MPL
FMK
Supply air filter
class
M5
M5
width
[mm]
270
270
height
[mm]
86
85
depth
[mm]
46
173
model
MPL
FMK
Smarty 2R VE
LWA total, dB(A)
LWA, dB(A)
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Supply
65
50
59
61
59
55
51
40
Exhaust
60
45
58
53
45
37
28
21
Surrounding
46
37
40
42
38
29
19
16
Measured at
flow/pressure
[m
3
/h / Pa]
214/100
Smarty 2R VE plus
LWA total, dB(A)
LWA, dB(A)
125 Hz
250 Hz
500 Hz
1 kHz
2 kHz
4 kHz
8 kHz
Supply
56
39
40
49
52
54
46
39
Exhaust
51
38
39
47
45
43
40
32
Surrounding
38
30
28
30
33
31
29
25
Measured at
flow/pressure
[m
3
/h / Pa]
113/60