9
Smarty 2R VE
www.salda.lt
Installation should only be performed by qualified and trained staff.
• When connecting air ducts, consider the notices indicated on the casing of the unit.
• Before connecting to the air duct system, the connection openings of ventilation unit should be closed.
• Do not connect the bends close to connection flanges of the unit. The minimum distance of the straight air duct between the unit and the first branch of
the air duct in the supply air duct must be 1xD, in air exhaust duct 3xD, where D is diameter of the air duct.
• It is recommended to use the accessories-holders. This will reduce vibration transmitted by the unit to the air duct system and environment.
• Enough space must be left for opening of the maintenance door and filter covers.
• If the installed ventilation unit is adherent to the wall, it may transmit noise vibrations to the premises. Though the level of noise caused by the fans is
admissible, it is recommended to mount the unit at the distance of 400 mm from the nearest wall. If it is not possible, the mounting of the unit is recom-
mended on the wall of the room where the level of noise is not important.
• Ducts are connected to the unit in such way that they could be easily disassembled and the heater could be removed from the unit when performing
service or repair works.
224,5 mm
273,1 mm
100,4 mm
598 mm
276,3 mm
237,7 mm
84 mm
Ø 125 mm
320 mm
1
16,3 mm
98 mm
105,7 mm
598 mm
320 mm
653 mm
620 mm
653 mm
620 mm
320 mm
598 mm
Ø 175 mm
160 mm
286 mm
Содержание Smarty 2R VE
Страница 49: ...49 Smarty 2R VE www salda lt...