8
Smarty 2R VE
www.salda.lt
• Rotor heat exchanger must be serviced once a year.
• Ensure that the gaps of the heat exchanger are clean, the brushes are not worn, the belt drive is not worn and the clamping nodes of the rotor heat
exchanger are tight.
• Rotor heat exchanger can be easily removed from the unit. The power cord of the motor of the heat exchanger is disconnected. The clamp of rotor
heat exchanger section is released and raised and the heat exchanger is removed.
• Heat exchanger is washed with the warm water and the alkaline solution non-corrosive towards aluminum, or the air stream. Direct contact with the
fluid stream is not recommended as the heat exchanger can be affected.
• While cleaning, protect the motor of heat exchanger from entry of moisture and fluids.
• After reinstalling the heat exchanger, fasten the heat exchanger section with the clamp. Connect the heat exchanger motor.
• CAUTION: the heat exchanger can not be used when the filters are removed!
Smarty 3X VER
Smarty 3X VER 3.0
Smarty 3X VEL
Smarty 3X VEL 3.0
Exhaust air
Smarty 3X VER
Smarty 3X VER 3.0
Smarty 3X VEL
Smarty 3X VEL 3.0
Extract air
Smarty 3X VER
Smarty 3X VER 3.0
Smarty 3X VEL
Smarty 3X VEL 3.0
Outdoor air
Smarty 3X VER
Smarty 3X VER 3.0
Smarty 3X VEL
Smarty 3X VEL 3.0
Supply air
Kitchen hood
The maintenance side can be changed for the ventilation unit, i.e. it can be mounted with the left ambient air inlet or the right ambient air inlet. That
can be implemented by switching over the back door and the front door. The default version of the ventilation unit is right.
Smarty 2R VER
Smarty 2R VEL
Содержание Smarty 2R VE
Страница 49: ...49 Smarty 2R VE www salda lt...