Functions and logic of the control board are designed on the basis of DIN 1946-06 and EN 12098-3 standards.
System modes:
stand-by
in this mode the system stops for the limited time period under the settings of standby mode blocking
function;
building protection
the mode is intended to protect the building from moisture accumulation. In this mode the system
works at speed 1. By default, temperature is not controlled, but under request it is possible to specify
the desired temperature;
economy
the mode is intended to save energy when there are no people in the premises. In this mode the sys-
tem works at speed 2. By default, temperature is controlled (indicating the desired temperature), but
under request it is possible to disable the temperature control;
comfort
the mode is intended for ventilation of the premises when there are people inside. In this mode the sys-
tem works at speed 3. By default, there temperature is always controlled, it is set in the main window.
Versions and working hours of the system:
Software and its configuration versions can be monitored in service menu. Specific configuration version for each unit is installed on the production
line. Working hours of the unit are displayed as well. Working hours calculate when the fan is running.
System state
Information for the user about the current state of the system. Possible system states and their descriptions:
State
Description
Stand-by mode
System operates in Stand-by mode
Building protection mode
System operates in Building protection mode
Economy mode
System operates in Economy mode
Comfort mode
System operates in Comfort mode
Emergency run
System operates in Emergency run
Preparing
System is preparing for operation
Opening dampers
Dampers are being opened
BOOST function activated
Activated BOOST function
Cooling heaters
Electric heaters are being cooled before stopping the fans
Closing dampers
Dampers are being closed
Critical alarm
Critical fault, system is stopped
Fire alarm
Fire alarm protection is activated from external contact.
MCB control board can be controlled with:
Ptouch remote control panel
Stouch remote control panel
MB - GATEWAY
web application
Ptouch remote control panel controllable all the
functions described in the technical documenta-
tion.
General description of the functions and instruc-
tion of the user’s settings are described below.
Download instructions for adjuster and service
settings:
http://salda.lt/en/products/category/ven-
tilation/
;
Stouch remote control panel c o n t r o l l a b l e
temperature, speed, air filter timer, BOOST
function settings, display of the faults.
General description of the functions and in-
struction of the user’s settings are described
below. Download instructions for adjuster and
service settings:
http://salda.lt/en/products/cat-
egory/ventilation/
;
in MB-GATEWAY web application
controllable all the functions described in the
technical documentation.
General description of the functions. Down-
load instructions of the user’s, adjuster’s and
service settings:
http://salda.lt/en/products/
category/ventilation/
. The software upgrade
via MicroSD card.