- 20 -
4.3.2 Installation Position
Do not expose the inverter to direct solar irradiation as this could cause power
derating due to overheating. The ambient temperature should be between -40°C
~
+60°C(-40° F
~
140° F) to ensure optimum operation. Choose locations with
sufficient air exchange. Ensure additional ventilation, when necessary.
To make sure the installation spot is suitably ventilated, if multiple SAJ on-grid
solar inverters are installed together, the following safety clearance in Figure 4.2
shall be followed for proper ventilation conditions.
30CM
50CM
50CM
30CM
30CM
4.2 Installation position
4.4 Mounting Procedure
4.4.1 Mark the Positions of the Drill Holes of the Rear Panel
The mounting position should be marked as shown in Figure 4.3, Figure 4.4 &
Figure 4.5.