Saia-Burgess Controls AG
Manual PCD7.D412DTPF & PCD7.D4xxxT5F │ Document 27-620 – Release ENG07 │ 2019-06-20
3-10
Logic Controller
Communications interfaces
3
3.1.2.4
PCD7.F180S Serial Interface Module Belimo MP-Bus
Up to 8 actuators and sensors can be connected.
PCD7.F180S
Belimo connection
Port x.1
Belimo MP-Bus
10 pin spring-loaded terminal block
0 PGND
MP
1
2
‘MFT’
‘IN’
3
4
PGND 5
6
7
8
(SGD)
9
MP-Bus cabling
0 PGND
Earth connection, MP line
1
MP
Multi-point
The MP-Bus is the Belimo master slave
bus. Up to 8 slaves can be connected to
a master device.
These are:
■ MFT(2) flap drives
■ MFT(2) valve drives
■ MFT fire damper drives
■ VAV NMV-D2M compact controller
2
‘MFT’ MFT programming unit (internal MP-Bus)
3
‘IN’
detection of MFT programming unit
(input 10 kΩ, Z5V1)
5 PGND
Earth connection, MFT programming unit