Class 70 - IP Telemetry Client (1st IPT Master)  

 

This class includes the general parameters for IP telemetry mode. 

 

Factory configuration:  

The factory configuration 

(def.) 

of class 70 is shown in bold. 

 

Parameter 

Offset 

Len 

Values (ASCII) 

Description 

String length IP 
destination 
address / host 
name 

‘00‘ .. ‘64‘ 

If the parameter is set to '00', the IP 
telemetry mode is switched off. 

Def: 

'00'

 

IP destination 
address / host 
name  

64 

(0x20....) 

IP address or host name under which the 
first IPT master can be reached, e.g.: 
'172.68.1.30' / 'test.dyndns.org'. 
Def: 

'Empty

 

Destination port

 

66 

(‘0‘ .. ‘9’) 

IP port number under which the first IPT 
master can be reached.

 

Def: 

'26862

 

Reserved

 

71 

n/a 

Without function 

Number of login 
attempts  

 

76 

‘01‘ .. ‘99‘ 

A login attempt in GPRS-IPT mode always 
consists of GPRS Connect / TCP Connect / 
IPT Login and is executed in one block. 

Def: 

'03'

 

Reserved 

78 

n/a 

Without function 

Def: 

'03'

 

String length IPT 
login name 

80 

‘00‘ .. ‘32‘ 

String length of the user name that is 
transferred when logging on to the IPT 
master.  

With length '00' the IMEI is used 

Def

: '00' 

IPT login name 
 

82 

32 

(0x20....) 

User name for logging on to the IPT master 

Def: 

'<IMEI>' 

The 15-digit IMEI number of the radio 
module is used as the default value. 

Attention:

 The

 

character '/ ' (0x2F) may 

only be contained once! 

The default value '<IMEI>' cannot be read 
out at this point. 

String length IPT 
password  

114 

‘01‘ .. ‘32‘ 

String length of the password for logging on 
to the IPT master 

Def: 

'03'

 

IPT password  
 

116 

32 

(0x20....) 

Password for logging on to the IPT master 

Def: 

'PW0

 

Reserved 

148 

n/a 

Without function

 

Reserved 

150 

n/a 

Without function

 

Reserved 

151 

n/a 

Without function

 

Reserved 

152 

n/a 

Without function

 

Reserved

 

155 

n/a 

Without function

 

Reserved

 

157 

n/a 

Without function

 

Reserved

 

158 

n/a 

Without function

 

Содержание Dr. Neuhaus ZDUE-LTE-PLUS-VII

Страница 1: ...ZDUE LTE PLUS VII User manual...

Страница 2: ...s and product names are trademarks registered trademarks or product names of their respective owners All deliveries and services are provided by Sagemcom Dr Neuhaus GmbH based on the General Terms and...

Страница 3: ...ate precautions are not taken Warning means that death or serious bodily injury may occur if the appropriate precautions are not taken Caution with warning triangle means that minor personal injury ma...

Страница 4: ...are persons who are authorised to commission earth and label devices systems and circuits in accordance with the standards of safety technology Intended use Note the following Warning The device may o...

Страница 5: ...ces such as hearing aids or pacemakers Your doctor or the manufacturer of such devices can advise you To prevent data media from being demagnetised do not store floppy disks credit cards or other magn...

Страница 6: ...tional installation guidelines for lightning protection must be followed Connection costs Caution Please note that data packets are also exchanged during the re establishment of a connection during co...

Страница 7: ...20 4 3 Interface types 21 4 4 Auxiliary voltage source 23 5 Operation in AT mode 24 6 Operation in meter mode 25 6 1 Communication according to EN 62056 21 25 6 2 Establishing a connection to the mob...

Страница 8: ...he ZDUE 56 9 5 6 Read the firmware version of the radio module 56 9 5 7 Read version of the booter 56 9 5 8 Read out the position of the DIP switches parameter status 57 9 5 9 Read mobile radio operat...

Страница 9: ...munication via GSM dial up connections CSD Circuit Switched Data 1 2 Topologies The ZDUE LTE PLUS VII uses the IP data service of a mobile network LTE GSM GPRS UMTS for data transmission for remote en...

Страница 10: ...dressed to the ZDUE LTE PLUS VII itself these commands will not be forwarded to the connected meters but answered by the ZDUE LTE PLUS VII IP server mode The integrated mobile radio module of the ZDUE...

Страница 11: ...on software Modem ZDUE GSM PLUS V 1 meter Modem Auxiliary power source 9V HS HS In addition the device has an auxiliary voltage source 9V for supplying meters All meters connected to the ZDUE LTE PLUS...

Страница 12: ...II 1 8 Configuration parameterisation and firmware update Configuration via software The configuration is done via configuration software e g the ZDUEParametrierTool With the help of this software par...

Страница 13: ...evice parameters to factory settings as well as for a simplified readout of the firmware version The service button is only effective in meter mode Reset to factory setting Pressing and holding the se...

Страница 14: ...after a short time LED Colour Action Meaning Status Error Orange 3s on 3 x short flashing Boot phase network search 3s on 2 x short flashing Error condition 3s on 1 x brief flashing SIM PIN error 3s...

Страница 15: ...erminal block supply auxiliary voltage CL RS 485 as well as an RJ45 socket RS 232 L N HS HS RTX RTX RT RT RJ45 Terminal block PIN no Signal Function Comment 1 L Mains voltage connection 2 N Mains volt...

Страница 16: ...g of the ZDUE LTE PLUS VII in parameter class 79 to the PIN of the SIM card see Chapter 7 3 2 Alternatively you can change the PIN of the SIM card with a mobile phone With some network operators it is...

Страница 17: ...according to V 24 V 28 A maximum of 1 meter can be connected to this interface Further information Page 22 ZDUE Meter 1 TX RX DSR GND RS 485 interface 2 wire It is used to connect meters with RS 485 i...

Страница 18: ...0 Hz to 300 GHz in public spaces For details see recommendations of the EU Council 1999 519 EC of 12 July 1999 Installation outdoors must be carried out by a qualified person The standards EN 60728 1...

Страница 19: ...orrect SIM PIN If the PIN function of the SIM card used is activated and the PIN on the SIM card used matches the parameterised PIN the device automatically attempts to log into the mobile radio netwo...

Страница 20: ...es are supported by the meter interfaces Data format Default 7E1 Adjustable 7E1 8N1 8E1 Handshake No hardware software handshake Interface speed Default 300 baud Mode C Adjustable 300 600 1200 2400 48...

Страница 21: ...received communication continues at the current speed 4 3 Interface types CL1 Optional The CL1 interface corresponds to the current interface according to EN 62056 21 This is an active 20mA interface...

Страница 22: ...k L N HS HS RTX RTX RT RT RJ45 Pin Signal Description 2 DSR Output always aktive 4 GND Signal Ground 5 TXD Output data to the meter 6 RXD Eingang data from the meter All other pins are reserved RJ45 M...

Страница 23: ...e 23 of 62 4 4 Auxiliary voltage source Auxiliary voltage source 9V Some variants of the ZDUE LTE PLUS VII have a 9V auxiliary voltage source The connection is made via the terminals HS HS terminals 4...

Страница 24: ...hange the Start baud rate parameter to the desired value Then activate the AT mode again To set the bit rate back to the default value without parameterisation software you can switch back to meter mo...

Страница 25: ...n accordance with EN 62056 21 6 1 Communication according to EN 62056 21 Control features In meter mode the ZDUE LTE PLUS VII controls the communication between the head end system and the meters conn...

Страница 26: ...cess data must be configured in parameter classes 60 and 61 Provider selection of the LTE GPRS network provider e g T D1 Vodafone PDP Context access parameters of the LTE GPRS network operator USER Lo...

Страница 27: ...und in parameter class 70 and 78 see chapter 7 3 5 and 7 3 7 The ZDUE LTE PLUS VII proceeds in two stages If a login attempt fails a number of login attempts defined by the counter is repeated at a ce...

Страница 28: ...etwork and IPT Was the Logon to the mobile network and IPT successful Operation Was the maximum number of attempts counter reached Wait Timer 2 no yes no yes Wait Timer 1 Connection establishment in I...

Страница 29: ...emselves LTE GPRS Head End System Meter Data and Configuration via TCP IP Internet Intranet IP server mode ZDUE with TCP IP Server Meter Attention In order to be able to establish an IP connection to...

Страница 30: ...tomatically in the same way as dialling into the mobile radio network when LTE GPRS mode is activated The following properties of the IP server must be set in class 82 LTE GPRS function must be set fo...

Страница 31: ...e ZDUE LTE PLUS VII establishes an IP telemetry connection to the parameterised IP telemetry master according to DIN 43863 4 For this purpose access for the device must be set up at the IP telemetry m...

Страница 32: ...r classes 60 61 R W IP Telemetry Client Parameters 70 76 78 R W Writing parameters can only be done by writing a complete class Activation In order for the ZDUE LTE PLUS VII to operate in IP telemetry...

Страница 33: ...configuring the access data to the mobile network e g APN username password etc Class 82 IP server parameters Parameter class for configuring the IP server mode e g IP address port access protection A...

Страница 34: ...ZDUE LTE PLUS VII via the mobile radio network remote configuration or directly via the RS 232 interface local configuration Remote configuration via the mobile radio network The remote configuration...

Страница 35: ...e radio online state are configurable Attention Please note that the RS 232 interface can only be used if the current loop is closed by at least one connected meter or a wire jumper between the two cu...

Страница 36: ...ength Device address IEC address 18 2 01 16 Def 08 Device address ZDUE LTE PLUS VII 20 16 0 9 a z A Z Def 99999999 String length Set password 36 2 00 16 Def 08 Set password 38 16 20h 7Eh without Def 0...

Страница 37: ...dog every 12 hours 2 Watchdog every 6 hours 3 Watchdog every 3 hours 4 Watchdog every 2 hours 5 every 1 hour Watchdog Data format to the head end system 1 109 1 0 Data format 7E1 simulated 1 Data form...

Страница 38: ...the firmware automatically recognises the GSM Net ID first 5 digits of the IMSI of the responsible provider and searches for this GSM Net ID in parameter classes 60 and 61 If it finds it the parameter...

Страница 39: ..._CONTEXT 47 128 20h 7Eh C60 1 IP internet t d1 de 0 0 0 0 0 0 C61 1 IP web vodafone de 0 0 0 0 0 0 String length APN username 175 2 00 32 C60 04 C61 04 APN username 177 32 Max 32 characters 0 9 a z A...

Страница 40: ...heck is switched off 1 IP check is switched on Def 0 Check source port of communication 12 1 0 or 1 0 Port check is switched off 1 Port check is switched on Def 0 Source IP No 1 for permitted access 1...

Страница 41: ...0000 to 9999 A cyclic ping is executed on one or more URLs in the specified cycle Def 0030 IP address 1 for ping test 118 15 0 9 and Target IP of a potential communication partner for a ping 7 e g 06...

Страница 42: ...disconnect 197 3 000 300 Time in seconds after the module automatically terminates the TCP server service 000 Module remains permanently logged on to the service Def 000 Waiting time after x failed GP...

Страница 43: ...onsists of GPRS Connect TCP Connect IPT Login and is executed in one block Def 03 Reserved 78 2 n a Without function Def 03 String length IPT login name 80 2 00 32 String length of the user name that...

Страница 44: ...Reserved 159 3 n a Without function Reserved 162 12 n a Without function Reserved 174 3 n a Without function Reserved 177 3 n a Without function Reserved 180 1 n a Without function Reserve for paramet...

Страница 45: ...rved 71 5 n a Without function Reserved 76 1 n a Without function String length IPT login name 77 2 00 32 String length of the user name that is transferred when logging on to the IPT master With leng...

Страница 46: ...actory configuration def of class 78 is shown in bold Parameter Offset Len Values ASCII Description Reserved 0 40 n a Without function Delay times between connection attempts at socket IP level 40 40...

Страница 47: ...1 0 9 2 6 JJMMTT Date 1 1 C 91 0 15 String Firmware version of the radio module 129 72 23 7 0 15 String Current IP address in GPRS mode The register data record of the ZDUE LTE PLUS VII contains the v...

Страница 48: ...llowing bits of the operating status in brackets the bit number in the operating status word see also 9 4 Bit 0 Bit 08 Voltage recovery Bit 1 Bit 09 reserved 0 Bit 2 Bit 10 Parameter reset to factory...

Страница 49: ...23 mm minute 00 59 ss second 00 59 2 Time stamp DS7 yYYMMTT y time zone 0 winter time 1 summer time YY year 00 99 MM month 01 12 DD day 01 31 3 Set password String with max 16 characters except for th...

Страница 50: ...an continue the communication by sending another permissible VDEW command Set password parameterised in the ZDUE LTE PLUS VII default 00000000 All passwords sent by the head end system must match the...

Страница 51: ...he subgroup parameter class 79 to the following values EVU identifier 12345678 Device address 74747474 Set password 18871887 Head end system password active 0 Head end system password PW0 Communicatio...

Страница 52: ...0000 80000000000000000003PW00000 EOT BCC ACK CR LF STX 0040 000000000151KGL923390R000300099015 00000021000040000000001150 ETX BCC 9 3 3 Parameter transfer command Function Take over parameters Command...

Страница 53: ...the supply voltage If no time is set 0000000 is returned as the time if no date is set 0070101 is returned Function Set time Command format SOH W5 STX 0 9 1 ZS7 set password ETX BCC Function Read time...

Страница 54: ...14 Reserved Bit 15 Reserved Note Other status information that can be read out from the ZDUE is GSM field strength GSM network operator ID e g 26201 for T Mobile GSM Location Area ID GSM Cell ID IMEI...

Страница 55: ...ry configuration Function Parameter reset to factory configuration Command format SOH W1 STX S98 ETX BCC Explanation This command loads the factory parameters All customer specific settings are overwr...

Страница 56: ...m Explanation This command is also permitted via the LTE GPRS connection 9 5 5 Read out the firmware version of the ZDUE Function Read out the firmware version of the ZDUE Command format SOH R3 STX S6...

Страница 57: ...lable Net ID Net ID of the GSM network operator max 6 characters e g 26202 Location GSM Location Area ID max 4 digits hex coded Cell ID GSM Cell ID max 4 digits hex coded IMEI Serial number of the rad...

Страница 58: ...2 LocalIP NetMask Gateway DNS1 DNS2 ETX BCC Legend LocalIP IP address currently assigned to the device If the device is not currently assigned an address 000 000 000 000 is output NetMask This value r...

Страница 59: ...sources Device does not log on Incorrect PIN or APN Check PIN or APN SIM card is not activated or in PUK status Check activation and status SIM card is not activated for the selected service UMTS LTE...

Страница 60: ...efore storing it Store the ZDUE LTE PLUS VII a place protected from the weather and not subject to fluctuating temperatures Temperature range 25 C 85 C Relative humidity max 95 11 3 Disposal Applicabl...

Страница 61: ...1 8V or 3V Antenna connection SMA or FAKRA D approx 50 Ohm Meter interfaces CL1 Current interface 20mA according to EN 62056 21 Mode A C up to 19 2 kbit s RS 232 Full duplex Signals Rx Tx DSR GND Spee...

Страница 62: ...The full text of the EU Declaration of Conformity is available at the following internet address www sagemcom com neuhaus Frequency bands GSM GPRS EDGE 900 1800MHz UMTS HSPA 900 2100MHz LTE 700 800 9...

Отзывы: