Safewatch
QuickConnect Plus
Security System
Programming Guide
BYPASS
RECORD
TEST
FUNCTION
STATUS
VOLUME
PLAY
CODE
CHIME
ESCAPE
ADD
DELETE
SELECT
1
2
4
5
7
9
8
0
ARMED
READY
OFF
AWAY
STAY
3
6
AUX
800-03859-4V2 11/10 Rev. A
Страница 1: ... QuickConnect Plus Security System Programming Guide BYPASS RECORD TEST FUNCTION STATUS VOLUME PLAY CODE CHIME ESCAPE ADD DELETE SELECT 1 2 4 5 7 9 8 0 ARMED READY OFF AWAY STAY 3 6 AUX 800 03859 4V2 11 10 Rev A ...
Страница 2: ...ter the program mode 2 Upon entry into Program mode data field 20 INSTALLER CODE will be displayed the first data field in the system and both keypad LEDs will flash To Program the Data Fields 1 Press followed by the desired field number e g 21 then make the required entry 2 The keypad beeps three times after entering data then displays the next data field in sequence 3 For phone number and accoun...
Страница 3: ... 0 no 1 yes 22 22 22 22 KEYPAD KEYPAD KEYPAD KEYPAD BACKLIGHT BACKLIGHT BACKLIGHT BACKLIGHT Keypad Backlight Timeout 0 0 none backlighting always on 1 backlight off after 10secs 23 23 23 23 FORCED FORCED FORCED FORCED BYPASS BYPASS BYPASS BYPASS Forced Bypass UL installations 0 1 0 none 1 bypass open zones 24 24 24 24 RF RF RF RF HOUSE HOUSE HOUSE HOUSE ID ID ID ID CODE CODE CODE CODE RF House ID ...
Страница 4: ...lection with the default value 30 which is displayed on the keypad and advances to the next field SIA The entry delay must be set to a minimum of 30 seconds The sum of entry delay 1 entered in Field 35 and the burglary abort window entered in 50 should not exceed 1 minute 36 36 36 36 ENTRY ENTRY ENTRY ENTRY DELAY DELAY DELAY DELAY 2 2 2 2 Entry Delay 2 zone type 02 UL installations 45 seconds max ...
Страница 5: ...t fill unused spaces If fewer than 20 digits entered pressing advances to the next field To clear entries from field press 41 42 42 42 42 SECOND SECOND SECOND SECOND TEL TEL TEL TEL NUM NUM NUM NUM Secondary Phone Number Enter up to 24 digits Do not fill unused spaces If fewer than 24 digits entered pressing advances to the next field To clear entries from field press 42 All four digits of the sub...
Страница 6: ...arms Restore Cancel 2 All except Open Close Test 3 Alarms Restore Cancel 4 All except Open Close Test 5 All To Primary Phone No 6 All reports except Open Close 7 All reports 8 All reports 9 All reports except Open Close To Primary Phone No 10 All except Open Close 11 All reports 12 All reports 13 All except Open Close To Secondary Phone No None unless primary fails then all Others Open Close Test ...
Страница 7: ... Enabled 6 Enabled Enabled Disabled 7 Enabled Enabled Enabled Note The control validates the data entered in this field If the selection is not valid it will emit a single long beep indicating that the selection has been rejected The control replaces the selection with the default value 7 which is displayed on the keypad and advances to the next field 58 58 58 58 RF RF RF RF JAM JAM JAM JAM DETECT...
Страница 8: ...L CANCEL CANCEL CANCEL REP REP REP REP CODE CODE CODE CODE Cancel Report Code 1 0 69 69 69 69 RECENT CLOSE REP RECENT CLOSE REP RECENT CLOSE REP RECENT CLOSE REP Recent Close Report Code 1 Note The control validates the data entered in this field If the selection is not valid the control will emit a single long beep indicating that the selection has been rejected The control replaces the selection...
Страница 9: ...0 81 83 85 See Procedures later in this manual 86 86 86 86 MULTI MULTI MULTI MULTI MODE MODE MODE MODE EMAIL EMAIL EMAIL EMAIL Multi Mode E Mail Notification RIS is always enabled 0 0 Disable multi mode devices RIS enabled 1 Enable multi mode device address 6 only RIS enabled 2 Enable multi mode device address 7 only RIS enabled 3 Enable multi mode addresses RIS enabled 87 87 87 87 AUX AUX AUX AUX...
Страница 10: ...nd LRR IP communications device is enabled you must enter 0 primary dialer preferred channel as the second entry in Field 77 92 92 92 92 SWINGERSHUTDOWN SWINGERSHUTDOWN SWINGERSHUTDOWN SWINGERSHUTDOWN Swinger Shutdown 1 1 shutdown after one alarm 2 shutdown after two alarms Note The control validates the data entered in this field If the selection is not valid the control will emit a single long b...
Страница 11: ...nation of codes Continue If this is zone 95 96 or 99 the system skips to the VOICE DESCRIPTOR prompt 1C Return to previous prompt d INPUT INPUT INPUT INPUT TYPE TYPE TYPE TYPE Input Type Enter the input type i for the transmitter assigned to this zone Note Zones 2 25 should be assigned as Input Type 3 or 4 and Zones 26 41 should be assigned as Type 5 only 3 Supervised RF RF 4 Unsupervised RF UR 5 ...
Страница 12: ...med Note 00 was entered as a zone type in prompt b 00 will be retained and system will advance to prompt 1C 0 Discard the delete request 1 Confirm the requested delete 1 1 1 1A A A A ENROLL ENROLL ENROLL ENROLL MODE MODE MODE MODE Enroll Mode this prompt applies to Manually enrollment only Confirm delete or enter Serial Number 0 Skip to the VOICE DESCRIPTOR prompt 1C If zone type is 00 then skips ...
Страница 13: ...ed word 1 1 1 1E E E E Note System displays 2 digit selection alpha descriptor OR 99 No selection Descriptor 2 Enter 2 digit vocabulary index number of second descriptor word for this zone To change the entered index number press desired index number 6 accept word and advance to descriptor 3 descriptor 3 will be announced 8 accept word and advance to next zone prompt A zone descriptor will be anno...
Страница 14: ...e zt hex rc Index Wired Zone 1 0 1 00 00 00 I I Zone No Zone Alarm Report Input Loop Transmitter Vocabulary A 01 Type zt Code in hex rc Type i No l Serial Number Index 0 2 01 01 00 3 2 47 04 99 0 3 01 01 00 3 2 33 04 99 0 4 03 01 00 3 2 80 99 99 0 5 10 01 00 3 1 56 99 99 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 Duress 9 2 00 00 I I Keypad Panic 1 9 5 09 01 00...
Страница 15: ...rior with Delay 14 Carbon Monoxide 16 Fire with verification 20 Arm Stay 21 Arm Away 22 Disarm 23 No Alarm Response 24 Silent Burglary rc ALARM REPORT CODE Two Hex Digits For each Hex Digit enter 00 09 for 0 9 10 for A 11 for B 12 for C 13 for D 14 for E 15 for F If 00 is entered as the first digit there will be no report for that zone For Contact ID reporting this is enabling code only Enter any ...
Страница 16: ...ART START EVENT EVENT EVENT EVENT TYPE TYPE TYPE TYPE Start Event Type If applicable Enter the 1 digit start event type 0 3 for the device being programmed 0 Not used 3 Trouble 1 Alarm Continue 2 Fault Return to previous prompt d START START START START ZONE ZONE ZONE ZONE LIST LIST LIST LIST Start Zone List If applicable Enter the 1 digit zone list number 1 3 or 0 if not used for the device being...
Страница 17: ...t zone number to be added to this zone list The system will announce the Voice Descriptor for the selected zone if it is programmed Accept zone number and enter the next zone number 00 Accept zone number and continue to next prompt C C C C DEL DEL DEL DEL WHOLE WHOLE WHOLE WHOLE ZN ZN ZN ZN LST LST LST LST Delete Entire Zone List 0 Don t delete continue to next prompt 1 Delete the current zone lis...
Страница 18: ...ll STOP It need not be same list as used for START Note Do not assign zones with types 20 21 or 22 to a zone list ZT ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 01 Entry Exit 1 02 Entry Exit 2 03 Perimeter 04 Interior Follower 05 Trouble Day Alarm Night 06 24 Hour Silent 07 24 Hour Audible 08 24 Hour Aux 09 Fire Zone without Verification 10 Interior with Delay 14 Carbon Monox...
Страница 19: ...ance is indicated by two beeps after copying A single long beep emitted when copying templates indicates the template is not valid 9 Delete existing serial number Go to the 1A prompt For 4 button key zones 26 29 30 33 34 37 and 38 41 deletes all four at once Advance to the next unlearned zone Return to previous prompt 1A 1 1 1 1b SERIAL SERIAL SERIAL SERIAL NUMBER NUMBER NUMBER NUMBER Serial Numbe...
Страница 20: ...or will be announced Press any other key to repeat the selected word d DESCRIPTOR DESCRIPTOR DESCRIPTOR DESCRIPTOR 3 3 3 3 Descriptor 3 Enter 2 digit vocabulary index number of third descriptor word for this zone To change the entered index number press desired index number 6 or 8 accept word and advance to next zone prompt A zone descriptor will be announced Press any other key to repeat the sele...
Страница 21: ...ode A A A A CUSTOM CUSTOM CUSTOM CUSTOM DESC DESC DESC DESC Custom Descriptor Number Enter 7 d where d 0 4 each representing custom word 70 71 72 73 or 74 respectively Existing descriptor will be announced Press to start recorder Begin speaking immediately after the third beep Speak the desired word clearly near the keypad microphone Recording stops after 1 5 seconds 6 Accept word and ready to rec...
Страница 22: ...OOP 3 LOOP 1 LOOP 1 LOW SENSITIVITY LOOP 2 HIGH SENSITIVITY LOOP 3 TEMP LOOP 4 TAMPER LOOP 1 HIGH SECURITY LOOP 2 STANDARD SECURITY LOOP 3 TILT MODE LOOP 4 TAMPER LOOP 1 LOW SENSITIVITY LOOP 2 HIGH SENSITIVITY LOOP 3 TEMP LOOP 4 TAMPER LOOP 1 LOOP 2 LOOP 4 YOU MUST ENROLL THIS BUTTON 5849 ENROLL AS RF 5894PI ENROLL AS RF LOOP 1 SOUND 5802MN2 ENROLL AS UR OR RF LOOP 1 5878 ENROLL AS BR 5870API ENRO...
Страница 23: ...ification 0 55 Reporting channels 0 56 Enhanced zone programming See 56 table 57 False alarm options 7 58 RF jam detection 0 59 Exit error report code 1 60 Trouble report code 1 0 61 Bypass report code 0 0 62 AC loss report code 0 0 63 Low battery Report code 1 0 64 Test report code 1 0 65 Open report code 0 66 Arm away stay report code 0 0 67 RF transmitter low battery report code 1 0 68 Cancel r...
Страница 24: ...SEC SMOKE DETECTOR MODEL DELAY SEC THIS UNIT MAY BE PROGRAMMED TO INCLUDE AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED FIRE CIRCUITS THE TOTAL DELAY CONTROL UNIT PLUS SMOKE DETECTORS SHALL NOT EXCEED 60 SECONDS NO OTHER INITIATING DEVICES SHALL BE CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION WARNIN...