Universal Stopper Install

STI-13000 & STI-14000 Series

Specifications

Polycarbonate Enclosure
·  Flammability - flush and surface mount models (Fig. 2 & 3): UL 94 V-2, enclosed flush and  

 

  enclosed back box models (Fig. 4 & 5): UL 94 5VA
·  Cover wall thickness  0.125 inches
Gaskets   
STI-1318 3” Gasket - Neoprene 1/8” diameter
Mounting gasket (embedded in housing at STI factory prior to shipping) - Two part polyurethane
STI-6004 1/2” or 3/4” conduit weather gasket - Closed Cell Neoprene

Horn 9V 

(Battery included)

 12V 

24V

·  Low (95 dB @ 1 ft.) 

40mA 

38mA 

22mA

·  High (105 dB @ 1 ft.) 

105mA 

125mA 

95mA

·  Min.  Operating  Req. 

2V  @  20mA 

4V  @  20mA 

4V  @  20mA           

Dry Contact Relay
·  30 VAC/VDC, 1A

Temperature Range
·  Electronics operating range: -40° to 120°F (-40° to 49°C) 

Below -4°F (-20°C), a remote   

 

power source is recommended
·  Polycarbonate rated: -40° to 284°F (-40° to 140°C)

Installation Notes

·  When used outdoors, the manual station must also be rated for outdoor use.
·  UL Listing does not permit external power source or connection of horn relay contacts to fire alarm 

or life safety devices.

·  When properly installed, the operation of this cover will not interfere with the function of your life 

safety system.

·  Horn operation and performance must be tested annually.  Battery replacement is recommended 

annually dependent on usage and battery expiration date.

·  Ensure the service pin is properly inserted in the service pin receptor to silence horn while performing 

installation or servicing horn.

·  If mounting to an uneven surface, a backplate (STI-1314) is recommended to help ensure proper 

sealing to mounting surface. 

·  The backplate may be drilled if wire access or screw mounting holes are needed. 

4.08 in.

(104mm)

5.42 in.

(138mm)

4.96 in.

(126mm)

4.31 in.

(110mm)

3.25 in.

(83mm)

2.54 in.

(84mm)

2.66 in.

(68mm)

2.0 in.

(51mm)

1.5 in.

(38mm)

1.0 in.

(25mm)

FLUSH END VIEW

.67 in.

(17mm)

5.95 in.

(151mm)WITHOUT HORN

5.28 in.

(134mm)WITH HORN

.42 in.

(11mm)

5.42 in.

(138mm)WITH HORN

6.36 in.

(162mm)WITHOUT HORN

FLUSH SIDE VIEW

LIFT HERE

TEXT HERE

6.45 in.

(164mm)

2.73 in.

(69mm)

2.29 in.

(58mm)

4.58 in.

(116mm)

LIFT HERE

6.45 in.

(164mm)

2.73 in.

(69mm)

2.29 in.

(58mm)

4.58 in.

(116mm)

LIFT HERE

TEXT HERE

6.45 in.

(164mm)

2.73 in.

(69mm)

2.29 in.

(58mm)

4.58 in.

(116mm)

LOCKING
TAB

LOCKING
TAB

LOCKING
TAB

TEXT HERE

Fig. 1 - Dimensions

Center pull station to the Universal Stopper with the help of 
dimensions shown in 

Fig. 1.

Open cover, use frame or optional backplate to mark 
mounting holes.

NOTE: Be sure the entire cover travel will not interfere 
with operation of the pull station or other safety system 
equipment when installed.