SAFEGREASE, SAFEOIL, MULTILUBE 
ST-1340 
 

 

13401BEN.doc 

27.12.2004  Rev. 1B 

12 (19) 

 

3.6.5   Channel-specific alarm relay 

The channel module 

AL

 LED-signal shows the status of the channel-specific alarm relay, with 

the exception of the case when the channel module is potential-free. 

The relay operation options, which are set in the configuration mode, are 

 Alarm 

output 

(Relay 0)

The relay goes into alarm mode, if there is a low level alarm or a pressure alarm or if the 
channel module is potential-free. 

 

Status output (

Relay 1

): 

Contact opens, when the channel is not in automatic operation mode, in other words, the 
channel is 

 closed 

 

interlocking is on 

 

in manual operation mode 

 in 

alarm 

mode 

 not 

configured 

The relay goes into alarm mode regardless of the relay settings also when there are problems 
in the communication between channel module and CPU-unit and these problems have lasted 
more than 1 minute. The alarm is automatically reset, when the problem is solved. 

3.6.6   Center-specific alarm relay 

The red 

Alarm

 LED-signal on the center cover shows the status of the center-specific alarm 

relay, with the exception of the case when the center is potential-free. 

The alarm relay is in alarm mode, when 

 

there are alarms from one or more channels 

 

the center is potential-free 

 

the diagnostic program detects an electronic fault 

The center alarm is inactivated, when all the problems that caused the alarms have been 
resolved and all alarms have been reset at the control panel. The alarm triggered by the 
diagnostic program for electronics is automatically reset, when the problem is solved. 

4   SETTINGS 

4.1   General 

Channel-specific settings can be divided into two groups 

 Set 

values 

 Configuration 

settings 

Set values are lubrication system basic values, for example lubrication cycle and maximum 
pressurization time. Set values can be changed in settings mode. 

Configuration settings determine the channel functions according to the lubrication system. 
These settings are usually factory settings and there should not be any reasons to change 
them during operation. 

All settings are password-protected. Different passwords are used for set values and 
configuration settings. 

Содержание ST-1340

Страница 1: ...brication 7 3 3 Manual operation 7 3 4 Lubrication cycle counter 9 3 5 Power failure 10 3 6 Alarms 10 3 6 1 Low level alarm 10 3 6 2 Pressure alarm 11 3 6 3 Power failure alarm 11 3 6 4 Error alarm fr...

Страница 2: ...rawing 461838A ST 1340 control center main switch pos 1 is located on the side of the center enclosure The enclosure cover has a green LED signal for power pos 2 and a red LED signal for alarm pos 3 C...

Страница 3: ...nnel input via a serial bus interface A designated channel number has been preprogrammed for each module and the number is also printed on the module cover The programming switch PR RN for a channel m...

Страница 4: ...e LED signal is lit when extra lubrication is applied not included in standard delivery L1 L2 Line controls The LED signal is lit when control is switched on SV Shut off valve control The LED signal i...

Страница 5: ...the channel automatically if the keypad has been used during the past five 5 minutes or if the center is in alarm mode 3 1 1 Basic display CH2 SG2 Machine 1 Interval 012h10min L1 005bar L2 005bar Chnl...

Страница 6: ...example if the channel is in alarm mode one of the function keys acts as an alarm reset key Display function keys Key Description Chnl Channel selection Press key to go to next channel Channel can als...

Страница 7: ...nnel is closed maximum pressurization time 0 Closed status duration Channel module error An error in the communication between channel module and CPU unit or in channel module power input will also tr...

Страница 8: ...een pressurization phases A phase code Delay and the remaining delay time are displayed The second pressurization phase in pressure transmitter channel is started when the pressure in the lines drops...

Страница 9: ...sed pumping time 00025s The fourth line indicates the function key texts Display function keys Key Description Line Line control Off L1on L2on Press key to switch line control on Off no line controls...

Страница 10: ...ontrol is being used time value is not reset although pressure control unit stops and starts the pump 3 4 Lubrication cycle counter Channel lubrication cycle counter is displayed by selecting Page Oth...

Страница 11: ...lit Channel specific alarms are visible in channel module AL LED signals and in the channel basic displays Press the Ack key for the channel in question to reset the alarm Note The alarm can be reset...

Страница 12: ...he same line will be pressurized again when the alarm has been reset by pressing the Ack key for the channel in question Pressure transmitter operation In pressure transmitter operation pressure alarm...

Страница 13: ...rm relay The red Alarm LED signal on the center cover shows the status of the center specific alarm relay with the exception of the case when the center is potential free The alarm relay is in alarm m...

Страница 14: ...exts in brackets are sample display texts The first line indicates the selected channel number CH2 operation mode SG2 name Machine 1 The second line indicates the selected channel set lubrication cycl...

Страница 15: ...this command Esc Back to basic display 4 3 Settings mode The settings for the selected channel can be displayed by selecting Page Set at basic display The program requires a password before it accepts...

Страница 16: ...he first line indicates the selected channel number CH2 operation mode SG2 name Machine 1 The second line indicates the selected channel set lubrication cycle Tc 024h00min set maximum pressurization t...

Страница 17: ...t within 0 160 bar The pressure low limit can be set between 0 bar and the set pressure high limit 4 5 Configuration display Channel configuration settings are displayed by selecting Page Othr Conf at...

Страница 18: ...are installed These changes are usually implemented by the supplier Configuration mode requires a password 1341 or 1441 Each channel can be set to different operation modes regardless of the settings...

Страница 19: ...g the system F 6 A Automatic fuse 600 x 380 x 210 w x h x d mm Steel enclosure IP55 Protection classification Time settings Channel specific lubrication cycle can be set within 1 min 999 h 59 min Chan...

Страница 20: ...to be lubricated in operation switch open Extra lubrication Outputs channel Line 2 pcs channel changeover contact 24V 2A max Pump control changeover contact 24V 2A max shut off valve control changeov...

Страница 21: ......

Страница 22: ......

Отзывы: