background image

SAFEGREASE, SAFEOIL, MULTILUBE 
ST-1340 
 

 

13401BEN.doc 

27.12.2004  Rev. 1B 

10 (19) 

 

Display function keys 

Key Description 

Chnl

 Channel 

selection 

Press key to display the lubrication cycle counter for the next channel. 
Channel can also be selected with 

Í

 and 

Î

 keys, which can used for toggling 

between channel up and down. 

Clr

 Counter 

reset 

Press key to reset counter. The program requires a password (

1340 

or

 1440

before it resets the counter. The counter reset time is saved and it is displayed. 

Esc

 

Back to basic display 

3.5   Power failure 

The set values and program status are preserved in the memory also during power failures. 
After power is back on, the center will resume from the status it was before power failure 
occurred. Possible paused pressurization is re-started for the same line. Interval times are not 
counted during power failures. 

3.6   Alarms 

The center is in alarm mode, when the red 

Alarm

 LED-signal on the cover is lit. 

Channel specific alarms are visible in channel module 

AL

 LED-signals and in the channel basic 

displays. 

Press the 

Ack

. key for the channel in question to reset the alarm. 

Note 

The alarm can be reset only after the problem causing the alarm has been 
resolved. 

After the alarm has been successfully reset, the channel will perform the lubrication cycle as 
soon as it is possible due to delays and the pressurization of other channels. 

  

CH2 SG2 Machine 1

  

Press.al. L1 0020min

  

L1:085bar L2:005bar

  

Chnl Page  Ack. Manu

 

Figure 7. 

Basic display, pressure alarm 

3.6.1   Low level alarm 

The channel triggers a low level alarm, pauses pressurization and forces the center into alarm 
mode, if the lubricant barrel is empty which means that the low level switch is closed. In this 
case, a phase code 

Low level

 and the elapsed alarm time are displayed. Also the channel 

module LED-signals 

LO

 and 

AL

 are lit. The same line will be pressurized again, when low level 

switch is open and the alarm has been reset by pressing the 

Ack. 

key for the channel in 

question. The channel low level alarm mode does not affect the operation of other channels. 

Содержание ST-1340

Страница 1: ...brication 7 3 3 Manual operation 7 3 4 Lubrication cycle counter 9 3 5 Power failure 10 3 6 Alarms 10 3 6 1 Low level alarm 10 3 6 2 Pressure alarm 11 3 6 3 Power failure alarm 11 3 6 4 Error alarm fr...

Страница 2: ...rawing 461838A ST 1340 control center main switch pos 1 is located on the side of the center enclosure The enclosure cover has a green LED signal for power pos 2 and a red LED signal for alarm pos 3 C...

Страница 3: ...nnel input via a serial bus interface A designated channel number has been preprogrammed for each module and the number is also printed on the module cover The programming switch PR RN for a channel m...

Страница 4: ...e LED signal is lit when extra lubrication is applied not included in standard delivery L1 L2 Line controls The LED signal is lit when control is switched on SV Shut off valve control The LED signal i...

Страница 5: ...the channel automatically if the keypad has been used during the past five 5 minutes or if the center is in alarm mode 3 1 1 Basic display CH2 SG2 Machine 1 Interval 012h10min L1 005bar L2 005bar Chnl...

Страница 6: ...example if the channel is in alarm mode one of the function keys acts as an alarm reset key Display function keys Key Description Chnl Channel selection Press key to go to next channel Channel can als...

Страница 7: ...nnel is closed maximum pressurization time 0 Closed status duration Channel module error An error in the communication between channel module and CPU unit or in channel module power input will also tr...

Страница 8: ...een pressurization phases A phase code Delay and the remaining delay time are displayed The second pressurization phase in pressure transmitter channel is started when the pressure in the lines drops...

Страница 9: ...sed pumping time 00025s The fourth line indicates the function key texts Display function keys Key Description Line Line control Off L1on L2on Press key to switch line control on Off no line controls...

Страница 10: ...ontrol is being used time value is not reset although pressure control unit stops and starts the pump 3 4 Lubrication cycle counter Channel lubrication cycle counter is displayed by selecting Page Oth...

Страница 11: ...lit Channel specific alarms are visible in channel module AL LED signals and in the channel basic displays Press the Ack key for the channel in question to reset the alarm Note The alarm can be reset...

Страница 12: ...he same line will be pressurized again when the alarm has been reset by pressing the Ack key for the channel in question Pressure transmitter operation In pressure transmitter operation pressure alarm...

Страница 13: ...rm relay The red Alarm LED signal on the center cover shows the status of the center specific alarm relay with the exception of the case when the center is potential free The alarm relay is in alarm m...

Страница 14: ...exts in brackets are sample display texts The first line indicates the selected channel number CH2 operation mode SG2 name Machine 1 The second line indicates the selected channel set lubrication cycl...

Страница 15: ...this command Esc Back to basic display 4 3 Settings mode The settings for the selected channel can be displayed by selecting Page Set at basic display The program requires a password before it accepts...

Страница 16: ...he first line indicates the selected channel number CH2 operation mode SG2 name Machine 1 The second line indicates the selected channel set lubrication cycle Tc 024h00min set maximum pressurization t...

Страница 17: ...t within 0 160 bar The pressure low limit can be set between 0 bar and the set pressure high limit 4 5 Configuration display Channel configuration settings are displayed by selecting Page Othr Conf at...

Страница 18: ...are installed These changes are usually implemented by the supplier Configuration mode requires a password 1341 or 1441 Each channel can be set to different operation modes regardless of the settings...

Страница 19: ...g the system F 6 A Automatic fuse 600 x 380 x 210 w x h x d mm Steel enclosure IP55 Protection classification Time settings Channel specific lubrication cycle can be set within 1 min 999 h 59 min Chan...

Страница 20: ...to be lubricated in operation switch open Extra lubrication Outputs channel Line 2 pcs channel changeover contact 24V 2A max Pump control changeover contact 24V 2A max shut off valve control changeov...

Страница 21: ......

Страница 22: ......

Отзывы: