Opal Pro to Mod TCP
Page 12
Relay Status
Status of the Relay Outputs
Bit 0 – Running
Bit 1 – By-Pass
Bit 2 – Shorted SCR
Bit 3 – Reverse
1.07
Input Word 9
Bit 4 – Faulted
1.08
Input Word
10
Analog Output Analog Output value in Volts X 100
2.01
Input Word
11
Stack Size
Opal Pro Stack Size in Amps
2.02
Input Word
12
Comm
Module Type
0 – None
2 – Ethernet
2.03
Input Word
13
Firmware
Version
Opal Pro Firmware Version x 100
10.01
Input Word
14
Start/Stop
Control
4 = 2 Wire
5 = 3 Wire
6 = Comm Module
10.02
Input Word
15
Ramp Time
Time is seconds
10.03
Input Word
16
Step Current
In % of nameplate current
10.04
Input Word
17
Current
Reference
7 = Internal
8 = Analog Input
9 = Comm Module
10.05
Input Word
18
Phase Angle
10 = Internal
11 = Analog Input
12 = Comm Module
10.06
Input Word
19
Jog Accel
Current Limit
In % of nameplate current
10.07
Input Word
20
Jog Current
Limit
In % of nameplate current
10.08
Input Word
21
Jog Ramp
Time is seconds x 10
11.01
Input Word
22
Stop Mode
13 = Coast
14 = Soft Stop
15 = DC Injection
11.02
Input Word
23
Soft Stop
Step
In % of incoming line voltage
11.03
Input Word
24
Soft Stop
Ramp
Time in seconds
11.04
Input Word
25
DCI Current
In % of nameplate current
11.05
Input Word
26
DCI Time
Time in seconds