Sound and noise data
Noise data
Noise data is stated in:
SWL
: A-weighted
s
ound po
w
er
l
evel
SPL
: A-weighted
s
ound
p
ressure
l
evel, in free field over reflecting plane (1 m distance).
• Noise data is based on measurements according to
ISO 9614-2
.
• The stated SPL values are calculated using the formula 8.3 in
ISO 3744
.
• The stated values are for a complete unit operating in 100% capacity.
Noise data for SAB 283 and SAB 355
Evaporating temperature, TE
-15°C
Condensing temperature, TC
+35°C
Refrigerant
R717/HCFC/HFC
Speed
2950 rpm
For 60 Hz-driven compressors, add +2 dBA to the stated levels.
Table 12: Noise data
Type of unit
SWL
SPL
SAB 283 S
106
88
SAB 283 L
107
88
SAB 283 E
108
88
SAB 283 X
108
88
SAB 355 S
112
89
SAB 355 L
112
89
SAB 355 E
112
89
SAB 355 X
112
89
Johnson Controls Denmark can provide noise data for other operating conditions on request.
Note:
• The actual SPL value on site will be between the stated SPL and SWL depending on the
acoustic environment in the machine room.
• In a typical machine room without any noise absorbing materials, the actual SPL will be
approximately 14 dBA higher than the stated SPL (free field value).
• Checking the actual SPL must therefore always be accompanied by measurements of the
acoustic environment of the machine room. Alternatively,
ISO 9614-2
could be followed at
the installation site to obtain SWL comparable values.
• Be aware of local and national requirements for the use of ear protection. Generally, it is
recommended to use ear protection in machine rooms.
SAB 283-355 A-Frame OHU 6042 and OHU 7650 (including ATEX) Screw Compressor Unit
34