Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
40/175
008831 en 2022.02
Multilingual system
UniSAB III is available in 19 different languages and you can switch to the English version at
any time.
Easy to operate
UniSAB III has a systematic and easily accessible user interface which does not require any
special knowledge or education.
Operational data and status appear from the distinct display which features four lines with
twenty characters each. The user interface has arrow keys for menu selection, set key for pa-
rameter changing and keys for selection of start/stop and resetting. Manual/automatic opera-
tion and manual capacity regulation is performed with function keys.
Safety monitoring and control
UniSAB III provides safe monitoring by means of shutdown and alarm values/settings for all
measuring points. If a set value is exceeded, a red diode will flash slowly in alarm situations
without stopping the compressor and quickly in shutdown situations. A display text will show
the cause of the alarm or shutdown. In both alarm and shutdown situations separate relays are
activated for connection of a remote lamp, bell or alarm panel.
It is easy to find all the set values and their alarm and shutdown values through the straightfor-
ward menu system.
Besides monitoring the compressor pressures and temperatures, UniSAB III also calculates
the suction pressure vapour overheating, monitors the capacity slide position and oil flow and
calculates the oil filter differential pressure on screw compressors and SMC reciprocating
compressors.
For correct fault diagnosis in case of compressor shutdown, UniSAB III immediately stores all
shutdown situations in its memory which can be displayed and analysed on the display at any
time.
Instrumentation
Depending on the compressor type, UniSAB III is equipped with a number of pressure and
temperature transducers as well as position transmitters on the compressor.
Screw compressors are fitted with four pressure transducers and three temperature trans-
ducers as well as one or two slide position transmitters.
Furthermore, a thermistor input is available for motor protection.
Factory test
Every UniSAB III is tested during the production process and when it is mounted on the com-
pressor. A computer test is performed before the compressor leaves the factory.
For further information, see separate UniSAB III manual.
4.5
Compressor
The compressor is equipped with an integral suction strainer placed in the transversely suction
side “cylinder like cavity” with access from the side on top of the compressor block. The filter
prevents impurities in the gas from entering and damaging the compressor.