background image

AERASGARD

®

RPS - SD 

AERASGARD

®

RFTM - PS - xx 

D G F r

D

  

Bedienungs- und Montageanleitung

Multifunktionaler Raumfühler bzw. Messumformer  
für Feuchte, Temperatur, Feinstaub (PM) und CO2 - Gehalt,  
kalibrierfähig, mit aktivem ⁄ schaltendem Ausgang 

G

  

Operating Instructions, Mounting & Installation

Multifunctional room sensor and measuring transducer  
for humidity, temperature, fine dust (PM) and CO2 content,  
calibratable, with active ⁄ switching output 

F

  

Notice d’instruction

Sonde d’ambiance multifonctions, resp. convertisseur de mesure,  
pour l’humidité, la température, les particules fines (PM) et teneur en CO2,  
étalonnable, avec sortie active ⁄  de commutation

r

  

Руководство по монтажу и обслуживанию

Многофункциональный датчик для помещений или измерительный  
преобразователь для измерения влажности, температуры,  
содержания мелкой пыли (твердые частицы, ТЧ) и углекислого газа,  
калибруемый, с активным ⁄ релейным выходом

CARTONS 

ET EMBALLAGE 
PAPIER À TRIER

RPS - SD 

RFTM - PS

 

- CO2 - W 

RFTM - PS

 

- CO2 - W 

mit Display 

with display 

avec écran 

с дисплеем

6000-3880-0000-1XX   

38800-2021  V100

    02  ⁄  2021

S+S REGELTECHNIK GMBH 
THURN-UND-TAXIS-STR. 22 
90411 NÜRNBERG ⁄ GERMANY 
FON +49 (0) 911 ⁄ 5 19  47- 0
[email protected] 
www.SplusS.de

Содержание AERASGARD RFTM-PS Series

Страница 1: ...ture fine dust PM and CO2 content calibratable with active switching output F Notice d instruction Sonde d ambiance multifonctions resp convertisseur de mesure pour l humidit la temp rature les partic...

Страница 2: ...2 AERASGARD RPS SD AERASGARD RFTM PS xx D G F r Ma zeichnung Geh use Baldur2 Dimensional drawing Housing Baldur2 Plan cot bo tier Baldur2 Baldur2 T K 6 0 98 98 32 6...

Страница 3: ...24 V DC 6 4 VA 24 V AC Peakstrom 200 mA Ausgang RPS SD 0 10 V fest eingestellt RFTM PS CO2 W 0 10 V oder 4 20 mA B rde 800 ber DIP Schalter w hlbar gew hlte Variante gilt einheitlich f r alle Ausg ng...

Страница 4: ...AERASGARD RPS SD Raumf hler f r Feinstaub PM Standard RFTM PS W Multifunktionaler Raumf hler f r Feuchte Temperatur und Feinstaub PM Premium RFTM PS CO2 W Multifunktionaler Raumf hler f r Feuchte Temp...

Страница 5: ...3 default ON OFF 0 300 g m3 OFF ON 0 500 g m3 ON ON Feinstaub PM Partikelgr e DIP 3 PM 2 5 default ON PM 10 OFF CO2 Gehalt DIP 4 0 2000 ppm default OFF 0 5000 ppm ON CO2 Nullpunktautomatik DIP 6 deakt...

Страница 6: ...m f llt Dies sollte typischerweise w hrend den Zeiten in denen die R ume nicht belegt sind erfolgen Der Sensor erreicht seine normale Genauigkeit nach 24 Stunden Dauerbetrieb in einer Umgebung die ein...

Страница 7: ...00 1900 ppm bei MB 0 2000 ppm bzw 900 4700 ppm bei MB 0 5000 ppm Bei den anderen Mess gr en wird die jeweilige Untergrenze direkt als Basis verwendet PM 10 95 vom Messbereich g m Temperatur 5 48 C Feu...

Страница 8: ...ger t abzugreifen Hierbei wird die Ausgangssignal gegen das Nullpotenial O V der Eingangsspannung ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Betriebsspannungseingang UB f...

Страница 9: ...ie EMV Richtlinien zu beachten Dieses Ger t ist nur f r den angegebenen Verwendungszweck zu nutzen dabei sind die entsprechenden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des...

Страница 10: ...RPS SD 0 10 V fixed RFTM PS CO2 W 0 10 V or 4 20 mA working resistance 800 selectable via DIP switches selected version applies uniformly to all outputs with offset potentiometer 10 of measuring range...

Страница 11: ...dust and CO2 content as well as for switch point display AERASGARD RPS SD Room sensor for fine dust PM Standard RFTM PS W Multifunctional room sensor for humidity temperature and fine dust PM Premium...

Страница 12: ...3 OFF OFF 0 100 g m3 default ON OFF 0 300 g m3 OFF ON 0 500 g m3 ON ON Fine dust PM Particle size DIP 3 PM 2 5 default ON PM 10 OFF CO2 content DIP 4 0 2000 ppm default OFF 0 5000 ppm ON CO2 automatic...

Страница 13: ...l 350 400 ppm at least three times in 7 days This should typically occur during times in which rooms are unoccupied The sensor reaches its normal accuracy after 24 hours of continuous operation in an...

Страница 14: ...ppm or 900 4700 ppm with MR 0 5000 ppm With other measurands the corresponding lower limit is used directly as a basis PM 10 95 of measuring range g m Temperature 5 48 C Humidity 10 95 r H The assign...

Страница 15: ...reverse polarity protection diode is integrated in this device variant This internal one way rectifier on AC supply voltage The output signal is to be tapped by a measuring instrument The output sign...

Страница 16: ...el with current carrying lines is to be avoided and EMC directives are to be observed This device shall only be used for its intended purpose Respective safety regulations issued by the VDE the states...

Страница 17: ...V CA RFTM PS CO2 W typique 4 4 W 24 V CC 6 4 VA 24 V CA pointe de courant 200 mA Sortie RPS SD 0 10 V r gl par d faut RFTM PS CO2 W 0 10 V ou 4 20 mA charge 800 s lectionnable via interrupteur DIP la...

Страница 18: ...n CO2 et du point de commutation AERASGARD RPS SD Sonde d ambiance pour particules fines PM Standard RFTM PS W Sonde d ambiance multifonctions pour l humidit la temp rature et les particules fines PM...

Страница 19: ...g m3 default ON OFF 0 300 g m3 OFF ON 0 500 g m3 ON ON Particules fines PM Taille de particules DIP 3 PM 2 5 default ON PM 10 OFF Teneur en CO2 DIP 4 0 2000 ppm default OFF 0 5000 ppm ON Point z ro au...

Страница 20: ...en 7 jours le niveau air frais 350 400 ppm Cela devrait g n ralement avoir lieu dans les p riodes pendant lesquelles les locaux ne sont pas occup s Le capteur atteint sa pr cision normale au bout de 2...

Страница 21: ...B 0 5000 ppm Pour les autres grandeurs de mesure la valeur minimale respective est directement utilis e comme valeur de base PM 10 95 de la plage de mesure g m Temp rature 5 48 C Humidit 10 95 h r L a...

Страница 22: ...signal de sortie doit tre pr lev avec un appareil de mesure Ce faisant le signal de sortie est mesur e par rapport au potentiel z ro O V de la tension d entr e Si cet appareil est aliment en courant c...

Страница 23: ...d s ne pas poser les c bles de sondes en parall le avec des c bles de puissance les directives CEM sont respecter Cet appareil ne doit tre utilis que pour l usage qui est indiqu en respectant les r gl...

Страница 24: ...RPS SD 0 10 RFTM PS CO2 W 0 10 4 20 800 DIP 10 RPS SD RFTM PS CO2 W 24 1 A DIP RH C RH 0 100 RH 0 10 B 4 20 DIP RH 2 0 20 80 25 C 3 0 C 0 50 C C 0 10 B 4 20 DIP C 0 2 K 25 C DIP 0 50 0 100 0 300 0 500...

Страница 25: ...0 3 W 1501 2116 7301 000 RFTM PS W LCD 0 100 0 50 C 4x W 1501 2116 7321 000 RFTM PS CO2 W RFTM PS CO2 W 0 100 0 50 C 0 50 3 0 100 3 0 300 3 0 500 3 0 2000 1 0 5000 1 W 1501 2113 7301 000 RFTM PS CO2 W...

Страница 26: ...OM NO relay switch point humidity r H fine dust g m3 Outputs temperature C DIP RFTM PS xx DIP 1 DIP 2 0 50 3 OFF OFF 0 100 3 default ON OFF 0 300 3 OFF ON 0 500 3 ON ON DIP 3 2 5 default ON 10 OFF CO2...

Страница 27: ...27 r CO2 350 1 1 75 0 2000 1 0 7 0 5000 1 automatic background logic CO2 350 400 1 7 24 CO2 400 1 4 21 DIP CO2 500 1 ZERO CO2 AUTO 0 600 CAL 0...

Страница 28: ...28 r 30 50 10 95 SET CO2 10 400 1 600 1900 1 0 2000 1 900 4700 1 0 5000 1 10 95 h 3 5 48 C 10 95 DIP DIP 7 DIP 8 10 CO2 ppm 3 C r H C CO2 P T H r H...

Страница 29: ...6 85 8 5 17 6 40 4 0 10 4 90 9 0 18 4 45 4 5 11 2 95 9 5 19 2 100 10 0 20 0 0 50 C C UA IA A 0 0 0 4 0 5 1 0 5 6 10 2 0 7 2 15 3 0 8 8 20 4 0 10 4 25 5 0 12 0 30 6 0 13 6 35 7 0 15 2 40 8 0 16 8 45 9...

Страница 30: ...30 r VOC 10 95 0 50 C 24 ZVEI VDE EMV...

Страница 31: ...wledge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are...

Страница 32: ...32 AERASGARD RPS SD AERASGARD RFTM PS xx D G F r...