W I R I N G   I N S T R U C T I O N S

FOLLOW PROPER WIRING PRACTICES IN ACCORDANCE WITH ALL LOCAL REGULATORY 
REQUIREMENTS. IF USING WITH LOW VOLTAGE POOL LIGHTING, SEE PAGE 8 FOR ADDITIONAL 
REQUIRMENTS AND MATERIALS.

P o w e r   C o n n e c t i o n s

To wire the WPC-2 use insulated COPPER wire only, 12 gauge minimum.  
Run a ½” to ¾” conduit from the main breaker panel to one of the bottom left or middle knockouts of the WPC-2.  
Pull appropriate wires from the main breaker panel to the WPC-2 unit.  
To make power connections remove 3/8 inches of insulation from wire ends.  
Connect bare wires to the Load Center as illustrated.  T
ighten terminal screws firmly (20 lb-in minimum).  
Connect the common to the Neutral bar (tighten to 20 lb-in minimum).  
Install a 20 Amp circuit breaker and wire to the 120V LINE and the T/C POWER of the terminal block.  
Wire the Neutral and T/C NEUTRAL terminals to the Neutral bar on the Load Center.  
For use with an internal GFCI, punch out the GFCI knockout on the Load Center Cover Plate of the WPC.  
Install a GFCI with appropriate hardware.

GROUND

GFCI

HOT LOAD SIDE

NEUTRAL LOAD SIDE

T/C POWER

T/C NEUTRAL

TO NEUTRAL

BAR

HOT LINE SIDE

120VAC 20AMP 

CIRCUIT BREAKER

Содержание WPC2 T Series

Страница 1: ...AC 60Hz applications Installation Instructions Read these instructions in their entirety before performing any installation work FOR USE WITH POOL AND SPA PRODUCTS 4008814 ETL LISTED Conforms to UL ST...

Страница 2: ...2...

Страница 3: ...RING INSTRUCTIONS 7 Power Connections 7 Hooking up Low Voltage Lights to Circuit 1 8 Hooking up Low Voltage Lights to Circuit 2 9 Wiring Diagram 10 EXTERNAL MAGNETIC ANTENNA MOUNTING 11 PUMP CONNECTIO...

Страница 4: ...Relay 3 1 94 15264 00 WPC Receiver 2 circuit 4 1 94 15263 00 Remote Control 2 circuit Transmitter 5 1 PLX ANTKT S 3 meter magnetic mount antenna Kit 6 1 44 15037 00 Transformer 12V OPTIONAL ACCESSORY...

Страница 5: ...s Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause un...

Страница 6: ...rque Max Motor Load Continuous Duty General Purpose Branch Circuit Breaker Rating General Purpose Branch Circuit Maximum Current Capacity Line and Neutral Main Lugs Neutral and Ground 120V 240V AWG AM...

Страница 7: ...To make power connections remove 3 8 inches of insulation from wire ends Connect bare wires to the Load Center as illustrated T ighten terminal screws firmly 20 lb in minimum Connect the common to the...

Страница 8: ...tion to store service loop cable Use appropriate wire from the separate 12VAC output block terminals L1 L2 to supply Low Voltage power from the WPC2 XXXX T to the approved Pull Junction or Bell Box Us...

Страница 9: ...WPC 2 As illustrated connect lights that will be operated by the Circuit 2 Switch to the Circuit 2 terminal Connect the Neutral to the Terminal Block marked Neutral Connect the Ground to the Equip GND...

Страница 10: ...AL NEUTRAL CIRCUIT 2 12 VAC 12 VAC TC POWER TC NEUTRAL BK CIRCUIT 1 FOR USE ON WPC AUXILIARY RELAY KIT FOR TEMPERATURE FREEZE PROTECT SWITCH OPTION BK R BR BK 6 7 5 3 BK BR W R 1 2 8 4 6 9 5 8 4 7 3 2...

Страница 11: ...less NOTE The remote function of this device operates through radio frequency RF signals As with any RF device this is subject to interference through surroundings and installation location In the ev...

Страница 12: ...nnect a 240V 30AMP Circuit Breaker for each pump if this control box is equipped with optional pump relays Using an appropriately sized copper wires connect to the outer contacts of the JQX relays of...

Страница 13: ...he Timer function switch is set to Auto for timer control of the Pump as illustrated below To turn off timers automatic functions set the Timer function switch to OFF To manually turn on the Pump set...

Страница 14: ...OFF position NOTE If a toggle switch is in the OFF position wireless remote operation of the device will be disabled To re enable wireless remote operation flip the toggle switch back to the REMOTE po...

Страница 15: ...HANGE to toggle on and off the power of Zone 2 on the WPC panel Color Changing Operation To change LED pool light colors simply toggle the power OFF then ON using the button marked 1 or 2 within 1 sec...

Страница 16: ...C P O Box 400 Canby OR 97013 P 503 266 2231 TF 800 824 4387 srsmith com 2019 S R Smith All rights reserved 79 15224 00 REV C Questions Contact One of Our Dedicated Lighting Specialists 1 800 824 4387...

Отзывы: