W I R I N G I N S T R U C T I O N S
FOLLOW PROPER WIRING PRACTICES IN ACCORDANCE WITH ALL LOCAL REGULATORY
REQUIREMENTS. IF USING WITH LOW VOLTAGE POOL LIGHTING, SEE PAGE 8 FOR ADDITIONAL
REQUIRMENTS AND MATERIALS.
P o w e r C o n n e c t i o n s
To wire the WPC-2 use insulated COPPER wire only, 12 gauge minimum.
Run a ½” to ¾” conduit from the main breaker panel to one of the bottom left or middle knockouts of the WPC-2.
Pull appropriate wires from the main breaker panel to the WPC-2 unit.
To make power connections remove 3/8 inches of insulation from wire ends.
Connect bare wires to the Load Center as illustrated. T
ighten terminal screws firmly (20 lb-in minimum).
Connect the common to the Neutral bar (tighten to 20 lb-in minimum).
Install a 20 Amp circuit breaker and wire to the 120V LINE and the T/C POWER of the terminal block.
Wire the Neutral and T/C NEUTRAL terminals to the Neutral bar on the Load Center.
For use with an internal GFCI, punch out the GFCI knockout on the Load Center Cover Plate of the WPC.
Install a GFCI with appropriate hardware.
GROUND
GFCI
HOT LOAD SIDE
NEUTRAL LOAD SIDE
T/C POWER
T/C NEUTRAL
TO NEUTRAL
BAR
HOT LINE SIDE
120VAC 20AMP
CIRCUIT BREAKER