CompTrol Interface V4.0.x | Issue 21-05-2021 | 1000932
Program 3 – temperature setpoint definition for equipment rooms with temperature limit alarm
The temperature limit value can be adjusted in increments of 2 K in the range from 24 °C to 30 °C
using DIP switches
S2-3
and
S2-4
.
Temperature limit value
[°C]
S2-3
S2-4
24
OFF
OFF
26
ON
OFF
28
OFF
ON
30
ON
ON
Table 26: Setting the temperature limit value
9.5 Digital input assignment in program 3
Input
Function
Description
X2a-D1
Remote ON/OFF
The indoor unit or group of indoor units can be switched on and off via
the digital input. Forced mode can be activated with DIP switch
S2-5
(see “5.2.2 Remote ON/OFF” on page 26).
X2a-D2
Cooling mode
The signal switches the indoor unit to Cooling mode. The mode can
then no longer be changed using the wired remote control.
X2b-D3
Center/
Center-Remote
When voltage is applied, the CompTrol Interface operates in Center
mode and the wired remote control is disabled. Without voltage, the
CompTrol Interface and the wired remote control operate in Center-Re
-
mote mode (see “5.2.4 Center/Center-Remote” on page 26).
X2b-D4
Analog input
evaluation
Analog input
X3-S
is only evaluated if a signal is applied to
X2b-D4
(see
“5.2.1 Evaluating the analog input” on page 25). If no signal is
applied, a setpoint can be specified via the wired remote control.
X2c-D5
Fan speed
F1
(low)
The signal switches the indoor unit to fan speed
F1
. The fan speed can
then no longer be changed using the wired remote control.
X2c-D6
Fan speed
F2
(medium)
The signal switches the indoor unit to fan speed
F2
. The fan speed can
then no longer be changed using the wired remote control.
X2c-D5
and
X2c-D6
Fan speed
F3
(high)
If fan speed
F1
and fan speed
F2
signals are both applied simultane-
ously, the indoor unit switches to fan speed
F3
. The fan speed can then
no longer be changed using the wired remote control.
Table 27: Digital inputs in program 3