CompTrol Interface V4.0.x | Issue 21-05-2021 | 1000932 33
Program 0 – temperature setpoint definition via analog signal
7.2.2 Setting program 0 on DIP switch S1
S1-1 S1-2 S1-3 S1-4
Designation
OFF OFF OFF OFF
Program 0: Temperature setpoint definition via analog signal
Table 13: DIP switch setting for program 0
7.2.3 Setting the functions for program 0 via DIP switch S2
The following table lists the functions for program 0 in brief. See
Interface expansion module” on page 23
for a detailed description of the functions.
DIP switch
Status
Function
S2-1
ON
OFF
CompTrol Interface is configured as master in the X/Y remote control bus
CompTrol Interface is configured as slave in the X/Y remote control bus
S2-2
ON
OFF
X4b-II
, operating signal;
X4c-III
, heating signal
X4b-II,
compressor signal;
X4c-III
, defrost signal
S2-3
OFF
Inoperative, switch setting is always
OFF
S2-4
ON
OFF
Automatic fan speed control
Inoperative
S2-5
ON
OFF
Forced mode
Inoperative
S2-6
ON
OFF
All digital outputs are closed without a signal (NC).
All digital outputs are open without a signal (NO).
S2-7
ON
OFF
Setting determines the value shown on the 7-segment display (see
7-segment display” on page 21).
S2-8
ON
OFF
Setting determines the value shown on the 7-segment display (see
7-segment display” on page 21).
Table 14: Functions in program 0
7.2.4 Setting the analog signal type on S4 and S7
The position of the jumpers on pin headers
S4
and
S7
determines the current analog signal type
(see “4.4.1 Analog input X3” on page 19).
7.3 Analog input
Note
●
If a signal exceeds or falls below a boundary value at analog input
X3-S
, the temperature set-
point 23 °C is transferred. (see “5.3.4 Signal boundary value monitoring” on page 27)
●
Analog input
X3-S
is only evaluated if a signal is applied to digital input
X2b-D4
(see
Содержание CompTrol
Страница 125: ......