Check after installation
If the LED is not lit, it must be ascertained that the charging is not inhibited due to a missing voltage supply,
due to a line interruption to the battery or due to a defective charging unit. The LED is blinking red, when
the mains voltage is connected but the battery feed line is interrupted.
Tests
Self-contained safety luminaires are to be tested at their mounting location in compliance with the
regulations. Any defects have to be repaired immediately. Test results need to be documented in the test log.
Luminaires with automatic self-test
All luminaires of series TENUO are assembled with an automatic self-test system, testing the luminaires
independently. Weekly tested are the electronic system,the lamp and the battery. Additionally, every year the
battery capacity is measured by simulating a mains power failure. The first capacity test is performed 8 days
after installtion or fault repair. The load control (LED) must be checked after the first
self-test, shown on the luminaire as described here after:
Luminaires in combination with Multidigit S63:
These luminaires (suffix .04) are assembled with a connecting terminal and are addressed with serial
numbers from 1 to 63 (factory-made). The number is indicated on the luminaire. Already addressed safety
luminaires must be replaced only by safety luminaires with the same number.
Luminaires for Monitoring Systems MULTIDIGIT and MWEB plus (.04)
These luminaires (suffix .04) are assembled with a connecting terminal and are addressed with serial
numbers from 1 to 125 (factory-made). The number is indicated on the luminaire. Already addressed safety
luminaires must be replaced only by safety luminaires with the same number.
Additional documentations are available upon request; For planning, installation, commissioning and usage
of monitoring systems MULTIDIGIT and MWEB plus.
LED off, LED is not lit:
No mains connection
or the emergency electronic gear is damaged.
LED red, blinking:
The lamp is damaged.
The alarm is reset approximately 1 minute after
the fault is repaired.
LED red, continuous light:
The capacity of
the battery is low or the battery connector is
interrupted. The alarm is reset immediately
after the fault is repaired.
LED green, continuous light:
No fault
red:
blinking
off:
LED is not lit
red:
Continuous light
green:
Continuous light
9
8
nur bei .04
only for .04
BUS
BUS
BUS
6
BUS
../../....
Inbetriebnahmedatum /
start-up date
7
BUS
Tx15
1.
2.
BUS
www.rzb.de
6/7
www.rzb.de
3/7
09-3064.152
47-2012
Instruction:
09-3064.152
47-2012
Instruction:
+