Check after installation

If the LED is not lit, it must be ascertained that the charging is not inhibited due to a missing voltage supply, 
due to a line interruption to the battery or due to a defective charging unit. The LED is blinking red, when
the mains voltage is connected but the battery feed line is interrupted.

Tests

Self-contained safety luminaires are to be tested at their mounting location in compliance with the 
regulations. Any defects have to be repaired immediately. Test results need to be documented in the test log.

Luminaires with automatic self-test

All luminaires of series TENUO are  assembled with an automatic self-test system, testing the luminaires 
independently. Weekly tested are the electronic system,the lamp and the battery. Additionally, every year the 
battery capacity is measured by simulating a mains power failure. The first capacity test is performed 8 days 
after installtion or fault repair. The load control (LED) must be checked after the first 
self-test, shown on the luminaire as described here after:

Luminaires in combination with Multidigit S63:

These luminaires (suffix .04) are assembled with a connecting terminal and are addressed with serial 
numbers  from 1 to 63 (factory-made). The number is indicated on the luminaire. Already addressed safety 
luminaires  must be replaced only by safety luminaires with the same number. 

Luminaires for Monitoring Systems MULTIDIGIT and MWEB plus (.04)

These luminaires (suffix .04) are assembled with a connecting terminal and are addressed with serial 
numbers  from 1 to 125 (factory-made). The number is indicated on the luminaire. Already addressed safety 
luminaires  must be replaced only by safety luminaires with the same number. 
Additional documentations are available upon request; For planning, installation, commissioning and usage 
of monitoring systems MULTIDIGIT and MWEB plus.

LED off, LED is not lit:

 No mains connection 

or the emergency electronic gear is damaged.

LED red, blinking: 

The lamp is damaged. 

The alarm is reset approximately 1 minute after 
the fault is repaired.

LED red, continuous light: 

The capacity of 

the battery is low or the battery connector is 
interrupted. The alarm is reset immediately 
after the fault is repaired.

LED green, continuous light: 

No fault

red:

blinking

off:

LED is not lit

red:

Continuous light

green:

Continuous light