background image

Setpoint Button

The Setpoint button is located just to the right of the LCD display. This button 
adjusts the desired temperature setpoint up and down. To change the setpoint 
press the up or down arrow once. This displays the word Set on the LCD and 
puts the system in the mode to change the setpoint. Then, each press of the up 
or down arrow changes the setpoint up or down for the displayed zone by one 
degree per press of the button. 
The setpoints are not adjustable when the thermostat is turned off. Also setpoint 
is not adjustable for the displayed zone when the displayed zone is set to run Fan 
High or Fan Low in that zone, or if the displayed zone is turned to Off. 
The setpoints are stored permanently in memory for each zone in both heating and cooling.  
This allows the user to switch between heating and cooling at season changes and still have  
the same settings as the previous year.

Operation Slide Switch

The thermostat operation slide switch is located near the bottom center of the 
thermostat. This switch slides left and right to put the thermostat into either 
heating, cooling or off. 
The center position is the off position. When the switch is here, the system will 
not operate any heating or cooling appliances. However, the LCD display will still 
show the room temperatures in each zone. 
When the slide switch is in the far right position, the system is in heating. The heating appliance 
selected will operate when the zone room temperature is one degree below the desired setpoint 
temperature. The heating appliance will continue to run until the zone room temperature is one 
degree above the desired setpoint temperature. 
When the slide switch is in the far left position, the system is in cooling. The cooling appliance 
connected in the particular zone will operate according to the mode the zone is set to.

Mode/Zone Button

The mode/zone button is located on the lower right part of the thermostat. This 
button allows the user to toggle through the different area zones and the different 
modes for heating and cooling. 
By pressing the zone side of the button the user toggles through each zone. When the  
system is first powered up, it determines how many zones are in the system and only displays the 
detected zones. 
By pressing the mode side of the button, the user toggles through the different modes for the system. 
When the slide switch is set to cool, the thermostat will toggle through the following modes: Cool 
Auto, Cool High, Cool Low, Fan High, Fan Low and Off. When the slide switch is set to heat, the 
thermostat will toggle through the following modes: Gas Heat, Heat Elec and Off. However, this will 
only happen if the system has both gas and electric heat in a zone. For instance, if a system only 
has an air conditioner and a gas furnace in a zone, then when set to heat, the user will only be able 
to toggle through Gas Heat and OFF because there is not electric heat available. Furthermore, if 
the system does not have an appliance connected in a zone, then the user will not be able to toggle 
modes in that zone. 

Setting the Thermostat

The thermostat default setting for each zone upon initial startup is 78°F. for cooling and 68°F. for 
heating. The fan speed for the cooling mode is 

COOL AUTO

, which is set to vary the fan speed 

according to the cooling needs. The fan speed for the heating mode is dependent on the type of heat 
that is installed for each zone and can not be changed.

Note:

 

The temperature setpoint cannot be adjusted in the following situations: when the slide switch 
is set to OFF, when the zone is turned off for either heating or cooling mode or when the fan is 
set to be running continuously in either high or low speed.

Set Temperature

1. Place the slide switch in either the 

COOL

 or the 

HEAT

 position. The current room temperature for 

that zone will display.

2. Press either the 

UP

 or 

DOWN

 arrow once to place the thermostat in the 

SET

 mode. At this point 

the thermostat displays the current setpoint for the displayed zone. (

SET

 will show on the LCD 

display).

3. Press the appropriate arrow button to change the set point temperature to the desired setting. 

Each press of the up arrow will increase the setpoint temperature by one degree. Each press of the 
down arrow will decrease the setpoint temperature by one degree.

4. Pressing 

ZONE

 button to toggle to the next zone or letting the thermostat sit idle for a few seconds 

will store the temperature setting in the thermostat memory.

5. This process should be done for each zone. 

Set Fan Speed for Cooling Mode

1. Place the slide switch in the 

COOL

 position.

2. Pressing the 

MODE

 button will toggle through the available speeds.

•  “

COOL AUTO

” setting allows the fan speed to vary depending on the cooling needs. This is the 

default setting.

•  “

COOL HIGH

” or “

COOL LOW

” setting will set the fan speed to run continuously at high or low, 

but the upper unit will cycle when cooling is needed.

•  “

FAN HIGH

” and “

FAN LOW

” setting will set the fan to run continuously at high or low speed. The 

upper unit will not run to produce cooling. Setpoint is not adjustable in this mode.

•  “

OFF

” will turn the upper unit off for zone displayed. By continuing to press the “

MODE

” button, 

you can toggle through the settings for the zone displayed until you have determined the setting 
you desire. Setpoint is not adjustable in this mode.

3. Once you have established the settings for Zone 1, press the ZONE button to store settings in 

thermostat memory and proceed to the next zone. 

Repeat steps for each zone.

INSTALLATION, OPERATION & APPLICATION GUIDE

for 8330*331* and 8330*335*

MULTIPLE ZONE THERMOSTAT CONTROLLER SYSTEM

Note: Thermostat may be black 
with white markings or white 
with gray markings as shown.

 Last digit represents 

specific model number

Caution

This thermostat should be installed and programmed by trained technicians only. Adhere to all local 
and national codes. Disconnect all power to the system before installing, removing, or cleaning.

Application

The 

8330*331*

 and 

8330*335*

 zone thermostats create a climate control system that allows the 

operator to control up to four air conditioners or heat pumps and up to four heating sources with only 
one thermostat.
The thermostat system will operate in both heat and cool modes, but will not allow the user to 
run simultaneously in heat and cool mode. Depending on the system that has been installed and 
programmed into the thermostat, each zone can be set up for a combination of the following systems: 
cool only units, heat/cool units, heat pump units and heating appliances.
This thermostat will work with any RV Products air conditioner that is controlled with an RV Products 
zone control box.
A zone is an area of a motor coach that is climate controlled. This system can control up to four zones 
in a motor coach. 

Operation

8330*331*

 and 

8330*335*

 function identically. The only difference is the color of the thermostat.

Description of Controls: 

Liquid Crystal Display (LCD)

The LCD display screen is the main interface between the user and the thermostat. It is located in the 
upper left of the thermostat. This will display which zone the user is looking at. When the system is 
first powered up, the thermostat determines how many zones are connected to the system and only 
displays the zones detected. 
The LCD also displays the mode that the particular zone is currently in. These will range from Cool 
Auto, Cool High, Cool Low, Fan High, Fan Low and Off in cooling, and from Gas Heat, Heat Elec 
(heat pump or electric strip heat) and Off in heating. 
Also, the LCD displays the room temperature and setpoint temperature in the displayed zone. If the 
word Set is shown above the temperature then the setpoint or desired temperature is shown. If the 
word Set is not shown, then the temperature shown is the actual room temperature in the displayed 
zone. 

Note:

 

The thermostat is designed to display temperatures from 41°F to 103°F however it will operate 
from -40°F to +175°F. If temperature is between -40°F and 41°F then 41 will be displayed as 
the room temperature. Also if the temperature is between 103°F and 175°F then 103 will be 
displayed. When temperature extremes fall outside the operating limits of the thermostat, “Er” 
will display in the temperature space of the LCD to show that current ambient temperature 
has exceeded thermostat capabilities. Additionally, if there is a problem with one of the remote 
temperature sensors, “Er” will display on the thermostat.

Note:

 

If the system is in cooling and is programmed to have only a heating appliance connected in a 
zone then the thermostat will still display the room temperature in that zone. But the user will 
not be able to operate any cooling appliance in that zone because there is not one connected 
in that zone. Additionally, if the system is in heating and is programmed to have only a cooling 
appliance connected in a zone then the thermostat will still display the room temperature in that 
zone, but the user will not be able to operate any heating appliance in that zone because there 
is not one connected in that zone. Your homeowner packet should contain literature that will list 
what heating and cooling appliances are installed in each zone of your motor home.

Down button

Up button

Note:

 

There is a built-in delay between programming and operation of the new program. (Example: 
changing fan speed to low from high; it will take approximately 20 seconds until the fan speed 
is changed.) The thermostat must sit idle for five seconds before the signal is sent to the 
control board. The thermostat will then send the signal to the control board in the control box, 
then the signal is verified before the change is put into operation.

 

This delay also helps to eliminate “communication noise problems”.

Note:

 

Moving slide switch to OFF position will shut down all unit operations.

 

The following table lists the operations of the thermostat system in each of the possible 
settings. The chart shows the operations for all types of appliances possible. All systems will 
not necessarily have all available options.

 

The chart below shows the system functions with the 8330*331* and 8330*335* thermostats.

Slide

Switch

 

Mode

 

Zone

 

Demand

HP 

Jumper

 

Operation of Unit

Off

N/A

N/A

N/A

N/A

LCD is displaying temperature in Zone 1; User 
can toggle thru zones to see temperature in 
each zone

Cool

Cool 
Auto

1

No

N/A

Nothing is operating since there is no cooling 
demand
LCD is displaying temperature in Zone 1

Cool

Cool 
Auto

1

Yes

N/A

Compressor is energized; If 1 degree above 
setpoint, then Fan Low is energized; If 2+ 
degrees above setpoint, then Fan High is 
energized and locked in on high until the 
setpoint is satisfied

Cool

Cool 
High

1

No

N/A

Fan High is energized

Cool

Cool 
High

1

Yes

N/A

Compressor is energized; Fan High is 
energized

Cool

Cool 

Low

1

No

N/A

Fan Low is energized

Cool

Cool 

Low

1

Yes

N/A

Compressor is energized; Fan Low is 
energized

Cool

Fan 

High

1

N/A

N/A

Fan High is energized**

Cool

Fan Low

1

N/A

N/A

Fan Low is energized**

Cool

Off

1

N/A

N/A

This turns off cooling appliances operating in 
Zone 1**

Heat

Elec

1

No

Non HP

Nothing is operating in this mode since there 
is no heating demand

Heat

Elec

1

Yes

Non HP

Fan Low is energized; Strip Heat is energized-
System uses backup heat if necessary 

Heat

Elec

1

No

HP

Nothing is operating in this mode since there 
is no heating demand

Heat

Elec

1

Yes

HP

Compressor and Reversing Valve are 
energized; Fan High is energized; System 
uses backup heat if necessary

Heat

Gas

1

No

N/A

Nothing is operating in this mode since there 
is no heating demand

Heat

Gas

1

Yes

N/A

Thermostat output to gas heating device 
energized

Heat

Off

1

N/A

N/A

This turns off heating appliances operating in 
Zone 1**

Notes:

 

Operation same for Zone 2, 3, and 4   ** Setpoint is not adjustable in this mode

.

Heat Pump Lockout

 – If the system has both gas heat, (LP furnace or hydronic heat) and 

electric heat,(electric strip heat or heatpump) appliances installed in the same zone, then the system 
will automatically switch from Heat Electric to Gas Heat if the electric heat can not satisfy the desired 
setpoint temperature. Because of the nature of the electric heating systems, they tend to be less 
effective the lower the outside temperature. Therefore, at low temperatures, your electric strip heat 
or heatpump may not be able to satisfy the setpoint. The system switches from Heat Elec to Gas 
Heat when the actual zone room temperature is five degrees or more below the desired setpoint 
temperature. If this happens three times in a row, the electric heat is locked out for two hours and the 
gas heat is the primary heat source. When this happens, the LCD will continue to display Elec but the 
word Gas will flash on the LCD to alert the user that the electric heat source is locked out. See table 
below for an example of how the heatpump lockout system works.
Example of Electric Heat Operation to call for Backup Heating

Set-

point

In-

door 

Temp.

Operation

70

70+

Nothing is operating

69

Electric Heat turns on (Primary Heat Source) (“ELEC” is displaying on T’stat)

71

Electric Heat turns off (thermostat satisfied)

69

Electric Heat turns on (“ELEC” displaying on T’stat)

65

Gas Heat turns on (“ELEC” is displayed and “GAS” is flashing on T’stat) 
(Electric Heat unable to satisfy Thermostat) (First strike for backup heat 
counter)

71

Electric Heat and Gas Heat turn off (thermostat satisfied)

69

Electric Heat turns on (“ELEC” is displaying on T’stat)

65

Gas Heat turns on (“ELEC” is displayed and “GAS” is flashing on T’stat) 
(Electric Heat again unable to satisfy T’stat) (Second strike for backup heat 
counter)

71

Electric Heat and Gas Heat turn off (thermostat satisfied)

69

Electric Heat turns on (“ELEC” is displaying on T’stat)

65

Gas Heat turns on (Electric Heat is again unable to satisfy T’stat) (“ELEC” is 
displaying and “GAS” is flashing on T’stat) (Backup Heat Counter reaches 3rd 
strike and Electric Heat is locked out for 2 hours) any time Electric Heat runs 
for more than 20 minutes and does not call for backup heat then the backup 
heat counter is reset

71

Gas Heat turns off (thermostat satisfied)

69

Gas Heat turns on (becomes primary heat source) (“ELEC” is displaying and 
“GAS” is flashing on T’stat)

71

Gas Heat turns off (thermostat satisfied)

After 2 hour lockout

69

Electric Heat turns on (resumes as primary heat source) (“ELEC” is displayed 
on T’stat)

65

Gas Heat turns on (becomes primary heat source) (“ELEC” is displaying and 
“GAS” is flashing on T’stat) (Electric Heat is locked out for another 2 hours)

71

Gas Heat turns off (thermostat satisfied)

After 2 hour lockout

69

Electric Heat turns on (Resumes as Primary Heat source) (“ELEC” is displayed 
on T’stat)

71

Electric Heat turns off (thermostat satisfied) (Backup heat counter is reset any 
time Electric Heat satisfies Thermostat Setpoint and does not need backup 
Gas Heat)

Note:

 

“ELEC” will be displayed and “GAS” will flash when Backup Heat is operating to indicate to 
the user that they are using Backup heat.

Installation

Wiring the System

OEM must supply these mating parts to connect these thermostats as shown below. A minimum wire 
size of AWG 18 must be used for this system. Check with appliance manufacturers for exact wire size 
needed for each appliance. See “System Wiring Diagam” on other side.

Отзывы: