Ruud RP13 Скачать руководство пользователя страница 1

 

R-410A HEAT PUMP 

OUTDOOR UNITS

92-105074-04-03 (8/15) Printed in USA

[ ] indicates metric conversions.

Do not destroy this manual. 
Please read carefully and 
keep in a safe place for future 
reference by a serviceman.

WARNING

THESE INSTRUCTIONS 
ARE INTENDED AS AN AID 
TO QUALIFIED, LICENSED 
SERVICE PERSONNEL FOR 
PROPER INSTALLATION, 
ADJUSTMENT, AND 
OPERATION OF THIS UNIT. 
READ THESE INSTRUCTIONS 
THOROUGHLY BEFORE 
ATTEMPTING INSTALLATION 
OR OPERATION. FAILURE 
TO FOLLOW THESE 
INSTRUCTIONS MAY RESULT 
IN IMPROPER INSTALLATION, 
ADJUSTMENT, SERVICE, 
OR MAINTENANCE 
POSSIBLY RESULTING IN 
FIRE, ELECTRICAL SHOCK, 
PROPERTY DAMAGE, 
PERSONAL INJURY, OR 
DEATH. 

INSTALLATION INSTRUCTIONS

RP13 (13 SEER)

RP14 (14 SEER) AND RP15 (15 SEER)

WARNING:

 

RECOGNIZE THIS SYMBOL 
AS AN INDICATION OF 
IMPORTANT SAFETY 
INFORMATION

Содержание RP13

Страница 1: ...RSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN...

Страница 2: ...Testing 26 Wiring 27 28 Control Wiring 27 Conventional 24 VAC Thermostat Control Wiring 27 Typical Thermostat Wiring Diagrams 27 Power Wiring 28 Grounding 28 Start Up 29 33 Start Up 29 Checking Airfl...

Страница 3: ...pump and may also endanger life and property The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components accessories or devices CAUTION...

Страница 4: ...nd maintenance of the air conditioning system Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation Homeowner should retain this m...

Страница 5: ...4 1 4055 1913 143 4054 227 103 0 234 106 1 RP1448FC1NA 208 230 3 60 13 8 83 1 2 80 21 25 25 30 30 24 23 2 25 1 4379 2066 194 5500 257 116 6 264 119 7 RP1460AC1NA 208 230 3 60 15 9 110 0 1 00 21 25 25...

Страница 6: ...ANCE AIR INLET LOUVERS ALLOW 6 152 mm OF CLEARANCE ALL SIDES 12 305 mm RECOMMENDED R P 14 24 A J 1 N A MINOR SERIES Z TYPE 1 SINGLE STAGE P PISTON VOLTAGE J 1 PH 208 230 60 C 3 PH 208 230 60 D 3 PH 46...

Страница 7: ...harge and airflow may reduce energy efficiency and shorten equipment life MATCH ALL COMPONENTS OUTDOOR UNIT INDOOR COIL INDOOR AIR HANDLER FURNACE REFRIGERANT LINES INDOOR THERMOSTAT Specifications DI...

Страница 8: ...operation Closely follow the clearance recommendations on page 8 24 61 0 cm to the service panel access 60 152 4 cm above heat pump fan discharge unit top to prevent recirculation 6 15 2 cm to heat pu...

Страница 9: ...istribute unit weight evenly and prevent noise and vibration Where snowfall is anticipated raise the unit above the base pad to prevent ice buildup and coil damage Mount the unit high enough to be abo...

Страница 10: ...eport 23 Lexington 12 Kalispell 53 Winston Salem 17 Bristol 8 WISCONSIN Hartford 29 Louisville 11 Missoula 23 NORTH DAKOTA Chattanooga 6 Green Bay 36 New Haven 15 MAINE NEBRASKA Bismarck 25 Knoxville...

Страница 11: ...tible R 410A and air should never be mixed in tanks or supply lines or be allowed to accumulate in storage tanks Leak checking should never be done with a mixture of R 410A and air Leak checking can b...

Страница 12: ...orator The existing evaporator must be replaced with the factory specified TXV evaporator specifically designed for R 410A Location Do not install the indoor coil in the return duct system of a gas or...

Страница 13: ...to flash any superheated vapor prior to the expansion device of the indoor coil The flashing of refrigerant can occur for the following reasons Low refrigerant charge Improperly selected liquid line s...

Страница 14: ...sses System oil level adjustment Table 2 is used to determine if the application is considered to have a long line set The region of the chart that is shaded grey is considered to be a long line set a...

Страница 15: ...amount of additional refrigerant This addition al refrigerant needs to be managed throughout the entire ambient operating envelope that the system will go through during its life cycle O Cycle mi gra...

Страница 16: ...door unit below the indoor unit the following is required TXV or EEV at the IDunit Crankcase heater Some models have factory installed CCH s Refer to tables on pages 14 and 15 Start components may be...

Страница 17: ...it above the indoor unit the following is required TXV at the indoor unit Crankcase heater Some models have factory installed CCH s Refer to tables on pages 14 and 15 Start components maybe required d...

Страница 18: ...43 85 25 91 85 25 91 85 25 91 85 25 91 85 25 91 1 4 6 35 N R N R N R N R N R N R N R N R N R N R N R N R 5 16 7 94 25 7 62 35 10 67 10 3 05 N R N R N R N R N R N R N R N R N R 3 8 9 53 25 7 62 50 15 2...

Страница 19: ...5 22 86 75 22 86 70 21 34 70 21 34 65 19 81 60 18 29 55 16 76 50 15 24 45 13 72 40 12 19 7 16 11 12 25 7 62 50 15 24 75 22 86 85 25 91 85 25 91 85 25 91 80 24 38 80 24 38 80 24 38 75 22 86 75 22 86 70...

Страница 20: ...22 86 90 27 43 90 27 43 90 27 43 90 27 43 85 25 91 85 25 91 85 25 91 85 25 91 80 24 38 1 2 12 71 25 7 62 50 15 24 75 22 86 95 28 96 95 28 96 95 28 96 95 28 96 90 27 43 90 27 43 90 27 43 90 27 43 90 27...

Страница 21: ...27 43 1 4 6 35 25 7 62 30 9 14 N R N R N R N R N R N R N R N R N R N R 5 16 7 94 25 7 62 50 15 24 70 21 34 65 19 81 55 16 76 45 13 72 40 12 19 30 9 14 20 6 1 15 4 57 N R N R 3 8 9 53 25 7 62 50 15 24...

Страница 22: ...R 5 8 15 88 0 97 0 95 0 94 0 92 0 89 0 88 0 86 0 86 0 84 N R N R N R 3 4 19 05 0 99 0 99 0 98 0 97 0 96 0 96 0 95 0 94 0 93 N R N R N R 7 8 22 23 1 00 0 99 0 99 0 99 0 98 0 98 0 98 0 97 0 97 N R N R...

Страница 23: ...25 4 1 01 1 00 1 00 1 00 1 00 1 00 1 00 1 00 1 00 1 00 1 00 1 00 1 1 8 28 58 N R N R N R N R N R N R N R N R N R N R N R N R 5 8 15 88 0 98 0 97 0 95 0 94 0 92 0 91 0 89 0 88 0 87 0 86 0 85 N R 3 4 1...

Страница 24: ...99 1 00 0 99 7 8 22 23 N R N R N R N R N R N R N R N R N R N R N R N R 1 25 4 N R N R N R N R N R N R N R N R N R N R N R N R 1 1 8 25 58 N R N R N R N R N R N R N R N R N R N R N R N R 5 8 15 88 0 99...

Страница 25: ...25 N R Application not recommended INSTALLATION RP1518A RP1518B RP1524A RP1524B RP1530A RP1530B RP1536A RP1542A RP1548A RP1560A Tubing...

Страница 26: ...pump units and must be installed in the liquid line upon unit installation When replacing an R 22 system with an R 410A system and the line set is not replaced use a flush kit available through after...

Страница 27: ...ions Indoor coils have only a holding charge of dry nitrogen Keep all tube ends sealed until connections are to be made Use type L copper refrigeration tubing Braze the connections with the following...

Страница 28: ...to purge lines or pressurize system for leak test Oxygen reacts violently with oil which can cause an explosion resulting in severe personal injury or death Pressurize line set and coil through servic...

Страница 29: ...een thermostat and outdoor unit Typical Noncommunicating Thermostat Wiring Diagrams The following figures show the typical wiring diagrams for RH1T RHIV air handlers and 1 stage heat pump and dual fue...

Страница 30: ...make sure all connections are tight DO NOT connect aluminum field wire to the Comfort Control2 terminals Grounding WARNING The unit must be permanently grounded Failure to do so can cause electrical...

Страница 31: ...This ensures a comfortable living space These simple mathematical formulas can be used to determine the CFM in a residential or light commercial system Electric resistance heaters can use CFM volts x...

Страница 32: ...to false readings because of pressure drop through the fittings After adequate evacuation open both service valves by removing both brass service valve caps with an adjustable wrench Insert a 3 16 5 m...

Страница 33: ...versing valve and compressor are to be used Confirm ID Airflow and Coils Are Clean Confirm adequate indoor supply airflow prior to starting the system See the Technical Specification Sheet for rated a...

Страница 34: ...nditions ONLY Cooling Mode ONLY 55 F 12 8 C outdoor dry bulb and above Heating Mode ONLY Between 40 F 4 4 C and 60 F 15 6 C outdoor dry bulb 3 Locate and note the design pressures The correct liquid a...

Страница 35: ...re gauges from pressure ports then replace the pressure port caps and tighten adequately to seal caps Do not overtighten Replace the service valve caps finger tight and then tighten with an open end w...

Страница 36: ...12 lbs ZP49K6E TF5 130 ZP31K5E TFD 13R ZP36K5E TFD 13R ZP42K5E TFD 13R ZP49K6E TFD 130 12 lbs 9 6 lbs 9 6 lbs 12 lbs 12 lbs Components MAXIMUM SYSTEM CHARGE VALUES Charge Limit Model Compressor Withou...

Страница 37: ...en minutes has elapsed or the coil temperature has reached the selected termination temperature The factory setting is 70 F but can be changed to 50 F 60 F or 80 F by relocating the jumper on the cont...

Страница 38: ...ing operation the defrost control will lock out compressor and fan operation Heating Mode The compressor and fan motor will stop when the low pressure control opens and will start again when the low s...

Страница 39: ...t for better thermostat temperature display Heat Pump Thermostat Warning Light Kit RXPX D01 This component senses a compressor lock out and tells the thermostat service light to come on This will let...

Страница 40: ...ve Closed Restricted Indoor Metering Device Restricted Filter Drier Dirty Outdoor Coil Inoperative Outdoor Fan Overcharge Recirculation of Outdoor Air Noncondensibles HigherThan Ambient Air Entering O...

Страница 41: ...alve Closed Restricted Outdoor Metering Device Restricted Filter Drier Dirty Indoor Coil Inoperative Indoor Fan Overcharge Noncondensibles Dirty Filters Inadequate Ducts Wrong Indoor Fan Rotation Outd...

Страница 42: ...Defrost No Defrost Wrong Defrost Control Timer Setting Poor Sensor Location Low System Charge Poor Sensor Location Wrong Defrost Control Timer Setting ReversingValve Stuck No DefrostTimer Control Powe...

Страница 43: ...n Charge per procedure attached to unit service panel Recover refrigerant Evacuate and recharge Add filter drier Compressor short cycles Incorrect voltage Defective overload protector Refrigerant unde...

Страница 44: ...unit Correct and complete diagnosis High line voltage Power company problem Have problem corrected High head pressure Overcharge Check system charge Dirty heat pump coil Clean coil Faulty or wrong siz...

Страница 45: ...k for correct ohms Voltage present on line side of com pressor contactor only Thermostat Check for control voltage to contactor coil Compressor control circuit High pressure switch Low pressure switch...

Страница 46: ...REMEDY Compressor failures Line tubing too large Reduce pipe size to improve oil return Low suction pressure Low charge Check system charge Refrigerant leaks Repair and recharge Cold noisy compressor...

Страница 47: ...Remove external equalizer line restriction Undersized TEV Replace with correct valve Loss of charge from power head sensing bulb Replace power head or complete TEV Charge migration from sensing bulb...

Страница 48: ...il Ensure blower is moving proper air CFM Remove Correct any airflow restriction Superheat and suction pressure fluctuate valve is hunting Expansion valve is oversized Install correct TEV Sensing bulb...

Страница 49: ...r TXV Feeler Bulb Charge Lost Low Low High High Low Poorly Insulated Indoor Sensing Bulb High High Low Low High HEATING MODE TROUBLESHOOTING TIPS SYSTEM PROBLEM INDICATORS DISCHARGE PRESSURE SUCTION P...

Страница 50: ...50 FOR SINGLE PHASE WITH PSC FAN MOTORS WIRING DIAGRAMS Wiring Diagrams...

Страница 51: ...51 Wiring Diagrams WIRING DIAGRAMS 3 PHASE 208 230V MODELS...

Страница 52: ...52 Wiring Diagrams WIRING DIAGRAMS FOR 3 PHASE 460 575V...

Страница 53: ...lador exterior Optional Opcional Run capacitor Capacitor de marcha Resistor Reostato Start capacitor Capacitor de arranque Start relay Rel de arranque Terminal block Enfermedad de bloque Time delay co...

Страница 54: ...54...

Страница 55: ...55...

Страница 56: ...56 CM 0815...