RUGGEDCOM RSG2300
Installation Guide
Chapter 2
Installing Device
Mounting the Device to a Panel
11
Section 2.3.3
Mounting the Device to a Panel
For panel installations, the RUGGEDCOM RSG2300 can be equipped with panelDIN rail adapters pre-installed on
each side of the chassis. The adapters allow the device to be attached to a panel using screws.
To mount the device to a panel, do the following:
1. Place the device against the panel and align the adapters with the mounting holes.
2
1
1
Figure 4: Panel Mounting
1.
Screw
2.
Panel/DIN Rail Adapter
2. Install the supplied screws to secure the adapters to the panel.
Section 2.4
Connecting the Failsafe Alarm Relay
The failsafe relay can be configured to latch based on alarm conditions. The NO (Normally Open) contact is closed
when the unit is powered and there are no active alarms. If the device is not powered or if an active alarm is
configured, the relay opens the NO contact and closes the NC (Normally Closed) contact.
NOTE
Control of the failsafe relay output is configurable through ROS. One common application for this relay
is to signal an alarm if a power failure occurs. For more information, refer to the ROS User Guide for
the RUGGEDCOM RSG2300.
Содержание RuggedSwitch RSG2300
Страница 4: ...RUGGEDCOM RSG2300 Installation Guide iv...
Страница 10: ...Preface RUGGEDCOM RSG2300 Installation Guide x Customer Support...
Страница 16: ...Chapter 1 Introduction RUGGEDCOM RSG2300 Installation Guide 6 Supported Fiber Optic Cables...
Страница 28: ...Chapter 2 Installing Device RUGGEDCOM RSG2300 Installation Guide 18 Wiring Examples...
Страница 38: ...Chapter 4 Communication Ports RUGGEDCOM RSG2300 Installation Guide 28 Removing a GBIC Optical Port...