Menu Map 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

vEr 

 

What you want to do 

What you see 

What it means 

DFC Menu Map 

Column 1 

Column 2 

Set the lowest the user can adjust the 
temperature to in normal mode for setpoint. 
 

Adjust the discharge setpoint. 

 

Set the Valve Maximum Output percentage. 
 
Valve Reverse Output. 

 

Select the desired aggression/speed of the PID 
curve for the valve (Standard, Low, or High). 

 

Low (SPLo) can be set from 40°F - 240 °F and must be 
at least 10°F less than the High. High (SPhi) can set be 
from 50°F - 250°F and must be at least 10°F greater 
than the Low. These will limit how far the user can 
change the temperature outside of programming 
mode. 
Setpoint (SP) may be adjusted within the menu map or 
on the main screen with the up and down arrows, then 
pressing enter to save the selected setpoint.  
 
When adjusting the discharge setpoint temperature 
above the outside air it will result in turning the 
burner on and modulate the system at that specified 
setpoint. 

Column 1 shows the menu parameters 

Arrow Keys: 

 

Up and Down: to navigate or adjust a menu parameter  
Right: to access column 2 for editing a parameter 
Left: to return to column 1 without saving a parameter 
Enter: to return to column 1 with saving a parameter 

ENT

RT

UP

DN

LT

Column 2 shows the factory set defaults for each 
parameter. Temperature defaults are shown in °F. 

Figure 4: Menu Map 

PASS 

100 

dAbL 

EnAb 

 

1.0 

vdEL 

vLo 

LT

RT

SPhi  

SP  

rEtd

 

9 0 

7 0 

dAbL 

 

EnAb 

 

SPLo  

 

40 

DN

ENT

UP

Set the highest the user can adjust the 
temperature to in normal mode for setpoint. 

Enables or Disables the use of an external remote 
control for adjusting the setpoint. 

Set the Valve Startup Delay from 0 to 30 seconds. 

Set the Valve Minimum Output percentage. 

Remote (rEtd) allows the user to use the DFC’s built-in 
interface when disabled (dAbL) or an external remote 
control when enabled (EnAb) in order to adjust the 
setpoint. 
 

 

dAbL 

vhi 

Lo 

EnAb 

Std 

hi 

Pid 

rEvo 

° C 

° F 

toFS 

ForC 

 

Set a temperature offset. For examples, to correct 
for duct losses or sensor calibration errors. 
Set the control to convert the temperature to 
display either °F or °C. 

 

 

The password may either be enabled or disabled. 

 

View the software version number. 

 

Valve Minimum Output (vLo), controls the percentage 
the valve will operate when in the closed position 
 
Valve Maximum Output (vhi), controls the percentage 
the valve will operate when in the open position 
 
Valve Reverse Output (rEvo), causes the valve voltage 
output to be inverted. For example, if the discharge 
temperature increases then the valve voltage output 
will decrease 

DN

UP

Содержание DFC

Страница 1: ...02 Email info RTC Solutions com Davie FL 33314 Model No DFC DIGITAL ENHANCED GAS FIRED MODULATING CONTROL This manual covers the following product s DFC Direct Fired Control Table of Contents Overview 2 Normal Operation 2 Programming 3 Features 3 Valve Connections 4 Menu Map 5 Installation 6 Specifications 6 ...

Страница 2: ...o modulating outputs that will power both 0 24V DC and 0 10V DC valve User parameters are stored in non volatile memory and are retained even during a power outage Also the DFC is powered by 24V AC Normal Operation The DFC will always display the current discharge air temperature Press the or key to change the discharge setpoint temperature Once the key is pressed the LED will display the text for...

Страница 3: ...Ftd oPEn The user has the Remote rEtd parameter on the DFC enabled but no external control is found to take a reading 3 dFts ShortEd There is a short in the connection of the Discharge Temperature Sensor 4 dFtd ShortEd The user has the Remote rEtd parameter on the DFC enabled and there is a short in the connection To resolve an issue check the wiring connections Please refer to Installation on pag...

Страница 4: ... Fax 919 845 8102 Email info RTC Solutions com Davie FL 33314 Valve Connections DFC Solenoid ACT 4 0 Belimo Siemens Term 7 PWM PWM Term 8 24VDC 24VDC Red 24VDC 2 24VDC Red 24VAC Term 9 0 10V Output Green 0 10V Input 3 2 10V Input Gray 0 10V Input Term 10 Ground Blue Ground 1 Ground Black Ground ...

Страница 5: ...meter Left to return to column 1 without saving a parameter Enter to return to column 1 with saving a parameter ENT RT UP DN LT Column 2 shows the factory set defaults for each parameter Temperature defaults are shown in F Figure 4 Menu Map PASS 100 dAbL EnAb 1 0 vdEL vLo 0 0 LT RT SPhi SP rEtd 9 0 7 0 dAbL EnAb SPLo 40 DN ENT UP Set the highest the user can adjust the temperature to in normal mod...

Страница 6: ...meter Left to return to column 1 without saving a parameter Enter to return to column 1 with saving a parameter ENT RT UP DN LT Column 2 shows the factory set defaults for each parameter Temperature defaults are shown in F Figure 4 Menu Map PASS 100 dAbL EnAb 1 0 vdEL vLo 0 0 LT RT SPhi SP rEtd 9 0 7 0 dAbL EnAb SPLo 40 DN ENT UP Set the highest the user can adjust the temperature to in normal mod...

Страница 7: ... is convenient for the user with easy access to all terminal connections Specifications Power Requirements Current Rating 24V Output DFC Ambient Temperature Limits Operating Accuracy 24V AC Nominal 18VAC DC 26VAC DC 1A 40 149 F 40 65 C 3 F 1 C 4 84 4 93 4 50 1 527 Figure 7 DFC Terminal Number Layout 1 2 3 4 5 6 7 8 9 10 1 24VAC 2 24VAC 3 DFTS 4 DFTS 5 DFTD or RDU 6 DFTD or RDU 7 PWM For Solenoid V...

Отзывы: