Ethernet Diagnostics Tab 

The numbers under the Ethernet Status can be further broken down by connection by using the 
Ethernet Diagnostics table at the bottom of this page. Here, the user can filter a specific IP address, if 
desired.  

 

 

 
The columns are briefly described as follows: 

Field 

Description 

IP Address

 

IP Address associated with the connection. 

Port

 

Remote Port associated with the connection. 

TX 

Number of packets transmitted. 

RX

 

Number of packets received.  

IN/OUT

 

Identifies a connection as either a client (OUT) or server (IN). 

Errors

 

Number of connection errors. 

IP Blocked

 

Number of blocked connection attempts. 

 

 

 

Содержание 515RTAENI

Страница 1: ...Real Time Automation Inc 1 1 800 249 1612 515RTAENI N34 Protocol Gateway Product User Guide Firmware Version 4 25...

Страница 2: ...consequential damages therefore the limitations set forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect to use of information circuits equ...

Страница 3: ...Page Does Not Launch 13 Web Configuration Tabs 14 Committing Changes to the Gateway 15 Network Tab 16 Ethernet Settings 16 Changing from DHCP to Static IP 17 Additional Fields under Ethernet Settings...

Страница 4: ...Ethernet Status Counters 31 Logging 32 Msg Log Tab 32 Serial Diagnostic Tab 33 Ethernet Diagnostics Tab 34 LED Behavior 35 DF1 Node Descriptions Reference Table 36 Use of Existing 1761 NET ENI W Tool...

Страница 5: ...of at least 1 Admin when security is enabled 8 Minor webpage layout fixes 4 16 7 3 2018 Bug Fixes 1 Minor Web Updates 2 EDS File Updated 3 Node 244 and 245 removed Node 248 functional 4 18 12 14 2018...

Страница 6: ...l messages via Simple Mail Transport Protocol SMTP Allows ability to easily upload and download programs using standard Rockwell Automation tools Writes to Ethernet controllers like ControlLogix Howev...

Страница 7: ...e of 8 28VDC 125mA at 24VDC Power can be received over serial cable TEMPERATURE Industrial Temperature Range 40 C to 85 C CERTIFICATIONS UL C UL CE FCC CLASS 1 DIV 2 MOUNTING Din Rail Panel SIZE 4 2 x...

Страница 8: ...nder the DIN Rail 3 While pressing the 515RTAENI against the rail press up to engage the spring loaded lower clip and rotate the unit parallel to the DIN Rail 4 Release upward pressure Removing Follow...

Страница 9: ...WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I Division 2 THIS EQUIPMENT IS AN OPEN TYPE DEVICE AND IS MEANT TO BE INSTALLED IN AN ENCLOSURE SUITABLE FOR THE E...

Страница 10: ...tre l ad quation la classe I division 2 CET APPAREIL EST UN DISPOSITIF DE TYPE OUVERT ET IL FAUT L INSTALLER DANS UN ENCEINTE ADAPT L ENVIRONNEMENT TEL QU IL N EST ACCESSIBLE L UTILISATION D UN OUTIL...

Страница 11: ...ww rtautomation com product generic micrologix programming cable CBL FF 6 o https www rtautomation com product null modem cable 1784 CP10 o https www rtautomation com product 1784 cbl IMPORTANT The 17...

Страница 12: ...a Change the gateway s IP address to match that of your PC if DHCP has failed i You will know DHCP has failed if the gateway s IP address is AutoIP at 169 254 X Y ii If successful it will say DHCP d a...

Страница 13: ...ss Subnet and Default Gateway 2 The gateway must be on the same Network Subnet as the PC whether it s set up for DHCP or Static Once you have both devices on the same network you should be able to pin...

Страница 14: ...t of tabs and what information can be found on each one 1 Home used for diagnostics and status messages for both the DF1 and Ethernet sides 2 Data View used to read write and display data from the con...

Страница 15: ...under that section will change into text boxes or dropdown lists See the screenshot below as an example The only field in this section that isn t configurable is the Serial Mode 3 Changes will not ta...

Страница 16: ...ns for the gateway to get an IP address 1 DHCP Attempts to receive an IP Address every time that the gateway is powered up If DHCP fails then an AutoIP address is used to make the webpages accessible...

Страница 17: ...under Ethernet Settings Field Description DNS This is the IP of the DNS server on the network where the gateway looks up IP addresses This is mandatory for email PLC Security Mask 1 This field limits...

Страница 18: ...st used baud rates Serial Mode Cannot be changed DF1 RS232 8N1 8N1 meaning 8 data bits no parity bit 1 stop bit Timeout ms Elapsed time in milliseconds for sending or receiving data before an error is...

Страница 19: ...lds are filled in if the email Server requires SMTP authentication If the email server does not require SMTP authentication the values here will be ignored and can be left blank The maximum length for...

Страница 20: ...node ID will be forwarded to the associated To address The controller will send a 485CIF write message to the DF1 destination node that is mapped to the destination email address For the 515RTAENI to...

Страница 21: ...to 99 that corresponds to the destination email address In this case since we are writing to node address 50 the email address that will be use is the email address configured in node address 150 in...

Страница 22: ...n allows 40 user configurable descriptions for the reads and writes associated with the data table address ranges of N50 0 27 used in node 202 and F51 0 11 used in node 203 Depending on the refresh ra...

Страница 23: ...apping Node The 515RTAENI can route a DF1 message received from the attached controller to a compatible destination TCP IP device using DF1 node addresses 0 through 49 Node 45 49 must be used if talki...

Страница 24: ...Real Time Automation Inc 24 1 800 249 1612 IP Routing Table example Configure Node 100 Function Configure route 0 address Execute Node 0 Function Send message to IP address DF1 node 100...

Страница 25: ...ay to use a previously saved configuration file Import Configuration 1 Click the Choose File button and search for the configuration to load into the gateway 2 Click the Upload button to begin install...

Страница 26: ...art the firmware upgrade process The firmware will automatically install and the gateway will automatically reboot after the new firmware has been upgraded The upgrade process will take approximately...

Страница 27: ...log values Up to 50 data strings can be displayed here by writing to node 204 at element 0 with the newest event log displayed at the top Writing a string to node 205 or a click on the Clear Event Lo...

Страница 28: ...Access Users can either have Full Access or View Only access to all the gateway s configuration pages Username Enter a name for the security user up to 32 characters Password Enter a password for the...

Страница 29: ...Real Time Automation Inc 29 1 800 249 1612...

Страница 30: ...he total number of DF1 messages transmitted to the attached serial controller Total Num Messages Received Displays the total number of DF1 messages received from the attached serial controller Total N...

Страница 31: ...timed out Timeout period is set to 2 minutes Total Num Messages Discarded Displays the total number of Ethernet messages that have been discarded Total Num Bad Packets Displays the total number of co...

Страница 32: ...800 249 1612 Logging Msg Log Tab This tab displays the gateway s internal system status log messages and is only used for advanced troubleshooting The log can be filtered by Start Up Error Event Asse...

Страница 33: ...splay Timeouts Display Bad BCC CRC or Display Queue Full The columns are briefly described as follows Field Description DF1 Node DF1 message destination or source node Req TX Number of requests transm...

Страница 34: ...er can filter a specific IP address if desired The columns are briefly described as follows Field Description IP Address IP Address associated with the connection Port Remote Port associated with the...

Страница 35: ...ured Blink Green No active communications Idle Blink Red No active communications Timeout Solid Red Fatal Error LED 2 Ethernet Status Solid Green Ethernet communication is active and messages are succ...

Страница 36: ...sent to node n is sent to the IP address at node n 100 Therefore a message sent to node 0 is sent to the IP address stored in node 100 Mapping Tab p23 50 99 Writes to nodes 50 99 are used by the seri...

Страница 37: ...to define Each URL string can be up to 45 characters Reference Links p26 Offset Link 4 1 6 2 8 3 10 4 12 5 14 6 16 7 18 8 20 9 22 10 201 A write to node 201 is used to change the Data Description colu...

Страница 38: ...er events are pushed down the page when new events are added 205 A controller write to node 205 will clear all events displayed on the NET ENI Event Log Values page i e Clears the event list 241 A con...

Страница 39: ...bnet Mask Integer 4 words Class A address First octet is 1 to 126 255 0 0 0 Class B address First octet is 128 to 191 255 255 0 0 Class C address First octet is 192 to 223 255 255 255 0 Gateway Intege...

Страница 40: ...mically Ethernet Settings p16 253 A controller write to node 253 can set the serial baud rate in the 515RTAENI NOTE Auto baud is NOT supported by the 515RTAENI gateway Value Baud Rate 1 1200 2 2400 3...

Страница 41: ...ENI ENIW Utility configuration tool If you are doing a device replacement use the ENI ENIW Utility tool to get the configuration file from the old ENI and then do a Save To the 515RTAENI gateway Note...

Страница 42: ...ible via the Ethernet driver If not accessible verify the serial settings in the 515RTAENI with your PLC If you do not know the serial settings for your PLC then reference the PLC Serial Setting secti...

Страница 43: ...e the RSLogix Controller Communications Comms Path why do I get a 0x10 error after clicking the Apply button The 0x10 error indicates that either the serial baud rates do not match or there is an issu...

Страница 44: ...puter for the EDS installation tool to successfully install the file Once the EDS file is installed and the Ethernet and serial settings have been set you should be able to discover the 515RTAENI gate...

Страница 45: ...t Add Device From the Device Selection tool select the NETENI connected PCCC devices select the appropriate processor family folder and then choose your PLC from the list in the processor folder and c...

Страница 46: ...over Ethernet to the serial input of the controller using the 515RTAENI gateway If this procedure doesn t work the first time delete the original target and rebuild the Comms as described above IMPOR...

Страница 47: ...need to do the following to gather data from a SLC 5 03 SLC 5 04 or MicroLogix using the 515RTAENI 1 Create a new item name it and then select a channel to use For that channel select the Device driv...

Отзывы: