Diagnostics
– BACnet/IP Server
Select the
BACnet/IP Server
in the drop-down menu on the Diagnostics Page. Additional diagnostic
information can be found by clicking the
Help
button.
NOTE
: This page will auto-refresh every five seconds with the latest data.
Clear All Values
- This will only affect displayed values.
1)
This will reset all displayed values back to zero and clear the Status Strings.
2)
If viewing BACnet/IP Server, this will only clear the values for the BACnet/IP Server section of the
gateway.
Device Status:
1)
Connected
–
The gateway is connected to a BACnet/IP client.
2)
Not Connected
–
The gateway is not connected to a BACnet/IP client.
3)
Error: Timeout
–
The gateway has not received a read/write request in the amount of time specified
by the Inactivity Timeout.
LED Status:
1)
Good Communication (Solid Green)
–
Connected to a BACnet/IP client.
2)
Never Connected (Blink Green)
–
Gateway has never been connected to a BACnet/IP client.
3)
Connection Timeout (Blink Red)
–
The gateway has not received a read/write request in the amount
of time specified by the inactivity timeout.