407H-16 / 407H-16-O3
GERMICIDAL UV SYSTEM FOR USE WITH
RS4 WHOLE HOUSE IAQ SYSTEM
Installation & Maintenance Instructions
UNPACKING THE UNIT
Each unit is shipped with the germicidal lamps placed in a box with protective
packaging. When handling lamps take care to not touch the glass portion of the
lamp with bare hands. Oils from the hands can cause “hot spots” which reduce lamp
life. Handle by the porcelain caps or use a soft cloth. If you accidentally touch a
lamp, clean it using a soft cloth dampened with rubbing alcohol. The lamp is
fragile and proper care must be taken when removing from packaging.
The following parts are included:
• 407H UVC Germicidal Unit
• Germicidal Twin H Lamp
(packed in lamp box)
• Lamp reflector
• Four #8-32 x 3/8” mounting screws
• One #8-32 x 3/4” screw to activate safety switch
• Four nuts for reflector
• Installation & maintenance instructions
• 120 VAC Power Cord
When installing and using this electrical equipment, basic safety precautions should always be followed including the following:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. SAVE THESE INSTRUCTIONS.
3.
Always be sure the unit is unplugged during installation or service procedures.
4.
The ultraviolet light produced by the UV lamp is harmful to your eyes. Do not look directly at
the lamp. Should it become necessary to view the lamp, use UV-protected sunglasses.
Lors de l’installation et de l’utilisation de cet équipement, des précautions devront être suivies.
1- Lire et suivre les étapes attentivement.
2- Conserver ces instructions.
3-
Assurez vous de toujours débrancher avant l installation ou le service.
4-
Ne pas regarder la lampe directement avec les yeux. Si nécessaire de le faire,
veuillez porter les lunettes de soleil contre les rayons U.V.
IMPORTANT: SAFETY INSTRUCTIONS
IMPORTANT: Instructions de securité
TROUBLESHOOTING
• The LED should light when the unit is operating.
If the LED does not light:
1. Check to be sure there is power to the unit.
2. Be sure lamp connector is fastened securely.
3. If the LED still does not light, replace lamp.
4. If still not operating, replace ballast.
5. To ensure Safety Switch has not cut power, first check to make sure RS4 access panel
latches are fully engaged. You should be able to hear the safety switch click on and off.
Back out the safety switch screw until it engages properly.
WARRANTY
All electronic components carry a lifetime warranty to the original homeowner. In addition there is a
four-year warranty from the date of installation for any subsequent owner. The manufacturer reserves the
right to send replacement parts or to replace the unit at its discretion. This warranty does not cover any
labor or damage resulting from improper installation or abuse. Use of any lamp other than the
manufacturer’s lamp designed for this device will void the warranty.
The original lamps are warranted for a period of two years. This warranty does not cover lamps
broken during shipping, installation or as a result of improper handling.
All returns are routed through your contractor/wholesaler and must be approved and accompanied by
an RGA#. Please call 800-578-7873 and we will guide you through the return procedure.
This warranty gives you specific legal rights and you may also have other rights which vary
from state to state.
For Technical Support Call (800) 578-7873
© 2016 Form GEN-213 (09/16)