Smart Positioner
YT-2600 series
Product manual
Ver. 1.30
40
8.6.6
PT1 (PT1) and PT2 (PT2) Values
PT value indicates the minimum time duration(unit: 0.1 msec) of internal signal controlling pilot valve.
PT1 is for increased input signal, and PT2 is for decreased input signal’s PT values.
→
→
<+>/<
-
>
→
Press <+> or
<
-
> button
if the above is not
displayed.
68 means 6.8 msec
<ESC>
3 times
→
8.6.7
Period T (PERIOd T)
Period T indicates the positioner’s internal control time interval. As default, positioner will check current
position respective to current input signal in every 100 msec.
8.6.8
Auto DZ (AUTO dZ)
After the auto calibration, the positioner will create deadzone automatically. However, depending on
the valve’s period of use, hunting or oscillation may occur due to packing friction or other reasons and
this function stabilizes the valve by detecting them automatically and increasing the deadzone at the
time of its occurrence. This will stabilize the valve but deadzone is increased.
→
→
<+>/<
-
>
→
Press <+> or
<
-
> button
if the above is not
displayed.
<ESC>
3 times
→