3.6.3 Cooling slope
The cooling slope is used to adjust the target feed temperature to
the characteristics of the building depending on the respective
outside temperature (weather-dependent T-HS control, see
chap. 3.6.4). Warmer outside temperatures result in a colder
target feed temperature and vice versa.
Prerequisites for
cooling mode
:
– Outside temperature > set target room temperature value
– Outside temperature > set value of the parameter [Start T-Out
Cooling]
–
"Cooling"
operating mode activated.
a) Via rotary switch in
"Operating Mode"
position or
b) via room thermostat function (cooling
switching con-
tact closed)
– No heat request active in the heating system's RoCon sys-
tem.
Manually adjusting the heat slope
Do not make any corrections to the set values for 1 - 2
days, and then only make them in small increments.
●
Deactivate the external heat sources (e.g. stoves, direct
sunlight, open windows).
●
Fully open any radiator thermostat valves or actuators.
●
Activate "Heating" operating mode.
Approximate setting values:
– Radiators and system 70: 1.4 to 1.6.
– Floor heating: 0.5 to 0.9.
Fig. 3-14 Manual setting of the heat slope (illustration with "User" ac-
cess authorisation)
Configuration
Setup
System Configuration
Configuration
System Configuration
HC Configuration
DHW Configuration
HC Configuration
HC Function
T-Frost Protect
Heating
T-Outside lim night
Heat-Slope
Room Influence
Heat-Slope
Heat-Slope
Heat-Slope
HC Configuration
Insulation
Heating
Cooling
T
A
Outside temperature
T
R
Room temperature target
value
T
V
T-HS
Fig. 3-15 Heat slopes
Caution - risk of condensation!
In the event of malfunction or incorrect parame-
ter settings, the floor heating, the screed or the
floor structure could be damaged due to con-
densation.
●
Prior to initial commissioning and activation
of cooling mode, set the minimum temper-
ature limit to the minimum permissible
system temperature in the RoCon mb
controller (parameter [Min T-Flow Cooling]).