Domestic water heating operation (

)

For the domestic water heating mode, several operations are
possible:

storage operation (either automatic or manually set)

reheat operation

disinfection operation

The purpose of each operation, and how the configuration is done, is
explained below.

Domestic water heating modes

Automatic storage

In this mode, the indoor unit will deliver hot water to the domestic hot
water tank based on the daily fixed pattern. This mode will continue
until the storage temperature set point is reached. During operation
of this mode, the 

 icon will be blinking with 1 second intervals. 

Automatic storage is the recommended domestic hot water mode. In
this mode, water heats up during the night (when space heating
requirements are lower) until the storage temperature set point is
reached. The heated water is stored in the domestic hot water tank at
a higher temperature so it can fulfil the domestic hot water
requirements throughout the day.

The storage temperature set point and the timing are field settings.
Refer to the chapter 

"Field settings" on page 16

 for a detailed

description how to set one or more field settings.

[1-00]

 Status: defines whether the domestic water heating

(storage mode) during night is enabled (1) or not (0).

[1-01]

 Start time: time of the night at which the domestic water

should be heated.

[1-02]

 Status: defines whether the domestic water heating

(storage mode) during daytime is enabled (1) or not (0).

[1-03]

 Start time: time of the day at which the domestic water

should be heated.

[b-03]

 set point: storage temperature (see figure 

"Domestic

water heating modes" on page 7

) only valid if [b-02]=0.

[b-02]

 Status: defines whether the weather dependent domestic

water heating is turned ON (1) or OFF (0).

If enabled, the storage set point will be set weather dependent.
In case of a higher ambient temperature (e.g. during summer-
time), temperature of supply water to the domestic hot water
tank will be higher too, so that storage temperature set point can
be set lower in order to keep the overall equivalent hot water
amount the same during the whole year. Therefor it is
recommended to use this function.

[b-04]

 Automatic maximum domestic hot water storage

temperature: default = 70°C.

NOTE

Any domestic water heating operation is impossible
when the domestic hot water tank is not installed.

A

Storage operation (if activated)

B

Reheat operation (if activated)

C

Disinfection operation (if activated)

Field settings

D

Disinfection operation temperature [5-00] (e.g. 70°C)

E

Hot water storage temperature [b-03] (e.g. 60°C)

F

Reheat maximum water temperature [b-01] (e.g. 45°C)

G

Reheat minimum water temperature [b-00] (e.g. 35°C)

t

Time

T

Domestic hot water tank temperature

A

B

C

D

E

F

G

T

t

[5-01]

NOTE

Remark that the 

 icon will only be blinking during

effective automatic storage operation. Presence of the
permanently lit 

 icon does not mean that automatic

storage is enabled, but only means that reheat is
enabled.

During operation it is always possible to cancel the
operation by pushing the 

 button once.

Be aware that after pushing the 

 button, it is possible

that the permanently lit 

 icon still displays.

Be aware that despite the automatic storage is a
pre-programmed schedule timer, it is only active when the
schedule timer is enabled. This means that you have to
push the 

 button and confirm that the   is displayed to

make sure that the automatic storage will operate.

A

Ambient temperature

T

Domestic hot water storage temperature

NOTE

The ambient temperatures for weather dependent
domestic water heating (see figure) are fixed and can
not be changed.

T

A

[b-04]

55

°

C

15

°

C

25

°

C

4PEN403582-1B_2017_09.book  Page 7  Saturday, October 7, 2017  11:02 AM

Содержание RKHBRD011ADV17 RKHBRD014ADV17 RKHBRD016ADV17

Страница 1: ...RKHBRD011ADV17 RKHBRD014ADV17 RKHBRD016ADV17 RKHBRD011ADY17 RKHBRD014ADY17 RKHBRD016ADY17 Indoor unit for air to water heat pump system and options 4PEN403582 1B_2017_09 book Page 1 Saturday October...

Страница 2: ...d knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not pla...

Страница 3: ...ge on page 7 The icon will display Hot water will be produced at next scheduled action When water heat up starts the icon will be blinking 1 second interval Manual storage one time water heat up refer...

Страница 4: ...T AVAILABLE This icon is displayed whenever a non installed option is addressed or a function is not available A function not available can mean insufficient permission level or can mean that a slave...

Страница 5: ...case not zero will display 31 ROOM TEMPERATURE ADJUST BUTTONS and These multi purpose buttons are used to adjust the current room temperature set point in normal operation mode or in schedule timer p...

Страница 6: ...mode heating will be activated as required by the water temperature set point The set point can be set manually through the schedule timer or weather dependent automatic Selecting space heating operat...

Страница 7: ...e Lo_A low outdoor temperature 3 01 High ambient temperature Hi_A high outdoor temperature 3 02 Set point at low ambient temperature Lo_Ti the target outgoing water temperature when the outdoor temper...

Страница 8: ...dependent domestic water heating is turned ON 1 or OFF 0 If enabled the storage set point will be set weather dependent In case of a higher ambient temperature e g during summer time temperature of s...

Страница 9: ...storage temperature is reached It can also be stopped at any time by pushing the button NOTE If weather dependent domestic water heating is enabled b 02 the storage temperature will be set automatica...

Страница 10: ...there are no error conditions in leaving or returning water thermistors the heater kit can start to follow emergency operation Other operation modes Start up operation During start up the icon display...

Страница 11: ...ule timer The actions programmed in the schedule timer will be executed automatically The schedule timer is enabled icon displayed or disabled icon not displayed by pressing the button Space heating R...

Страница 12: ...ve until the next programmed command 19 00 occurs So in order to know the actual setting one should consult the last programmed command It is clear that the last programmed command may date from the d...

Страница 13: ...ram depending on remote controller model 4 or 5 actions can be programmed per mode The same actions are repeated on a daily basis Take your time to enter all data accurately Try to program the actions...

Страница 14: ...s to set the room temperature 11 Use the button to select to switch heating and the remote controller off to select automatic temperature calculation for leaving water temperature Use the and buttons...

Страница 15: ...en action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted By pressing the button several times you return to previous steps in this procedure and finally return to normal op...

Страница 16: ...er action number than the one that is displayed E g when the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted Deleting a mode 1 Press the button...

Страница 17: ...for a minimum of 5 seconds to enter FIELD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2 Press the button t...

Страница 18: ...w ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day sel...

Страница 19: ...04 Automatic maximum hot water tank storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Installation related setting 80 37 80 1 C 01 Installation related setting 25 25 37 1 C 02 No...

Страница 20: ...e information If the supply cord is damaged it must be replaced by the manufacturer its agent or similar qualified persons in order to avoid hazards During longer periods of standstill e g during summ...

Страница 21: ...4PEN403582 1B_2017_09 book Page 1 Saturday October 7 2017 11 02 AM...

Страница 22: ...4PEN403582 1B_2017_09 book Page 2 Saturday October 7 2017 11 02 AM...

Страница 23: ...4PEN403582 1B_2017_09 book Page 1 Saturday October 7 2017 11 02 AM...

Страница 24: ...nd Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http de rotex heating com ueber rotex international 4P4...

Отзывы: